background image

27PM

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-7657-A  Rev.2  P. 2 / 3

TERMINAL CONNECTIONS

Connect the module as in the diagram below.

 

EXTERNAL DIMENSIONS  unit : mm (inch)

44 (1.73) dia.

6.3

(.25)

33 (1.30)

6 (.24) dia.

16.5 (.65)

6–M3 SCREW

2–4.5 (.18) dia.

MTG HOLE

20.7 (.81)

19.5 (.77)

12.7 (.5)

1

4

3

2

+

7.6 (.30) dia.

 

CONNECTION DIAGRAM

LOAD

OUTPUT

24V DC

4 – 20mA DC

*

1

POTENTIOMETER

*

1. Limited to 250 – 500Ω when using the communication to configure 

      the module.

+

4

1

3

3

2

1

max.

min.

+

WIRING INSTRUCTIONS

 

SCREW TERMINAL 

Torque: 0.5 N·m

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Input:  Check that the voltage between terminal 3 – 4 is 

within 0 – 100% of full-scale.

  If the potentiometer wires are broken, the output goes 

over 100% (below 0% with downscale) due to burnout 

function.  Check leadwires in such a case.

3) Output:  Check that the load is within the permissible 

limit including wiring resistance.

Load Resistance (Ω) = 

Supply Voltage (V) – 9 (V)

0.023 (A)

(including leadwire resistance)

ADJUSTMENT PROCEDURE

To calibrate the signal to match with a receiving instru-
ment or to change the factory-set configurations, use the PC 
Configurator software installed on a Windows PC via the 
Bell202 Modem (model COP-HU).
The PC Configurator software is downloadable at M-Sys-
tem’s web site: http://www.m-system.co.jp

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.