background image

PROGRAMMABLE ITEMS

The following items can be monitored and programmed.  For detailed explanations, please refer to the Operation Manual for 
Model PU-2x (EM-9255), Section A.

[GROUP 01]

ITEM

MDFY.

DATA INPUT

DISPLAY

CONTENTS

01

S

MAINTENANCE SWITCH (lock command)

0

MTSW: MON.MODE

MONITOR mode: data monitoring only

1

MTSW: PRG.MODE

PROGRAM mode: “P” marked data modifiable

02

P

Alphabets & No.

TG: XXXXXXXXXX

Tag name entry (10 characters max.)

03
05

P

D

Number (%)
No input

OUTPER XXX.XX
INPPER XXX.XX

Output status monitor (%) & simulation output
Input status monitor (%)

10

P

LINEARIZATION

41

Pm-1: straight

Without

42

Pm-2: curved

With (ITEM 60 to 91 for data input)

19

P

Percentage

FINZER

Fine zero adjustment
Initial status shows actual bias (%).
When data is entered, output (%) is shown.

20

P

Percentage

FINSPN

Fine span adjustment
Initial status shows actual gain (%).
When data is entered, output (%) is shown.

LINEARIZATION TABLE

60

P

Percentage

X (01) : XXX.XX

Input 1

61

P

Percentage

Y (01) : XXX.XX

Output 1

:

:

  

:

  

:

  

:

:

:

  

:

  

:

  

:

91

P

Percentage

Y (16) : XXX.XX

Output 16

Modification Code

D: No modification (writing) possible.  Used only for monitoring (reading).
S: Modifiable at any time.
P: Modifiable only when the MAINTENANCE SWITCH is in the “PRG” mode.

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%, 75% and 100% input signal.  Check that the output 
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of 
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.

18KJM

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: 

+81(6)6659-8510  E-mail: [email protected]

EM-0465  Rev.1  P. 5 / 5

Summary of Contents for 18KJM

Page 1: ...r supply and input signal for safety ENVIRONMENT Indoor use When heavy dust or metal particles are present in the air install the unit inside proper housing with sufficient ventilation Do not install the unit where it is subjected to continuous vibration Do not subject the unit to physical impact Environmental temperature must be within 5 to 55 C 23 to 131 F with relative humidity within 30 to 90 ...

Page 2: ...IAGRAM 5 6 1 3 2 Use either of module or external field terminals OUTPUT 2 OUTPUT 1 POWER Module Field Terminals Section A External Field Terminals Section A Section A Field Terminals CONNECTOR OUTPUT 2 PU 2x MODULARJACK 2 3 1 3 2 1 POTENTIOMETER max min TERMINAL ASSIGNMENTS 1 2 3 4 7 8 5 6 18KJM 5 2 55 Minamitsumori Nishinari ku Osaka 557 0063 JAPAN Phone 81 6 6659 8201 Fax 81 6 6659 8510 E mail ...

Page 3: ...match the actual input resistance range by using the linearization table ITEM 60 through 91 to compensate unused resistance ranges See the following figures If upper and lower overranges need not to be considered only two calibration points will suffice X 02 X 01 0 Y 02 100 Y 01 OUTPUT INPUT a c Unused Resistance Total Resistance Input Resistance b Input Resistance Actual Resistance Range 100 a b ...

Page 4: ...inearization table ITEM 10 Pm 2 curved in order to activate the settings X nn Input Signal in Y nn Output Signal in X or Y 15 00 to 115 00 15 0 X01 X02 X03 X04 X05 115 Y01 Y02 Y03 Y04 100 Y05 INPUT OUTPUT Figure 3 Linearization Table GROUP 01 ITEM MDFY DATA EXAMPLE 60 P X 01 XXX XX 61 P Y 01 XXX XX 62 P X 02 XXX XX 63 P Y 02 XXX XX 64 P X 03 XXX XX 65 P Y 03 XXX XX 66 P X 04 XXX XX 67 P Y 04 XXX X...

Page 5: ...ered output is shown LINEARIZATION TABLE 60 P Percentage X 01 XXX XX Input 1 61 P Percentage Y 01 XXX XX Output 1 91 P Percentage Y 16 XXX XX Output 16 Modification Code D No modification writing possible Used only for monitoring reading S Modifiable at any time P Modifiable only when the MAINTENANCE SWITCH is in the PRG mode MAINTENANCE Regular calibration procedure is explained below CALIBRATION...

Reviews: