Fine Output Calibration

Using the Programming Unit (ITEM 19, 20)

ITEM 19 is for Zero, and ITEM 20 is for Span.

  1 ) Turn the unit into Program mode (ITEM 01).
  2 ) Apply simulated 0% input.  Increase/decrease values 

(default: 0%) at ITEM 19 until the output signal is cali-

brated to actual 0%.

  3 ) Apply simulated 100% input.  Increase/decrease value 

(default: 100%) at ITEM 20 until the output signal is 

calibrated to actual 100%.

  4 ) Apply simulated 0% input again and check 0% output.
  5 ) When 0% value is changed, repeat the above procedure 

2) - 4). 

 

The 0% value may be shifted when the output span is 

greater than the input span (gain > 1).

• 

Using Linearization Table

Please have the PU-2x Operation Manual ready at hand.   
Max. 16 calibration points defined by sets of input and out-
put values can be programmed.  Use only necessary number 
of points, arranged in order from the smallest input value.
Enable use of the linearization table (ITEM 10: Pm-2: 
curved) in order to activate the settings.
     

X (nn) : Input Signal in %

     

Y (nn) : Output Signal in %

     

X or Y : -15.00 to +115.00%

-15%

0

X01

X02

X03

X04

X05 +115%

Y01

Y02

Y03

Y04

+100%  Y05

INPUT

OUTPUT

Figure 3. Linearization Table

[GROUP 01]

ITEM

MDFY.

DATA EXAMPLE

60

P

X (01) : XXX.XX

61

P

Y (01) : XXX.XX

62

P

X (02) : XXX.XX

63

P

Y (02) : XXX.XX

64

P

X (03) : XXX.XX

65

P

Y (03) : XXX.XX

66

P

X (04) : XXX.XX

67

P

Y (04) : XXX.XX

68

P

X (05) : XXX.XX

69

P

Y (05) : XXX.XX

70

P

X (06) : XXX.XX

71

P

Y (06) : XXX.XX

72

P

X (07) : XXX.XX

73

P

Y (07) : XXX.XX

74

P

X (08) : XXX.XX

75

P

Y (08) : XXX.XX

76

P

X (09) : XXX.XX

77

P

Y (09) : XXX.XX

78

P

X (10) : XXX.XX

79

P

Y (10) : XXX.XX

80

P

X (11) : XXX.XX

81

P

Y (11) : XXX.XX

82

P

X (12) : XXX.XX

83

P

Y (12) : XXX.XX

84

P

X (13) : XXX.XX

85

P

Y (13) : XXX.XX

86

P

X (14) : XXX.XX

87

P

Y (14) : XXX.XX

88

P

X (15) : XXX.XX

89

P

Y (15) : XXX.XX

90

P

X (16) : XXX.XX

91

P

Y (16) : XXX.XX

Modification Code

S: Modifiable at any time.
P: Modifiable only when the MAINTENANCE SWITCH is in 
the “PRG” mode.

18KJM

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: 

+81(6)6659-8510  E-mail: [email protected]

EM-0465  Rev.1  P. 4 / 5

Summary of Contents for 18KJM

Page 1: ...r supply and input signal for safety ENVIRONMENT Indoor use When heavy dust or metal particles are present in the air install the unit inside proper housing with sufficient ventilation Do not install the unit where it is subjected to continuous vibration Do not subject the unit to physical impact Environmental temperature must be within 5 to 55 C 23 to 131 F with relative humidity within 30 to 90 ...

Page 2: ...IAGRAM 5 6 1 3 2 Use either of module or external field terminals OUTPUT 2 OUTPUT 1 POWER Module Field Terminals Section A External Field Terminals Section A Section A Field Terminals CONNECTOR OUTPUT 2 PU 2x MODULARJACK 2 3 1 3 2 1 POTENTIOMETER max min TERMINAL ASSIGNMENTS 1 2 3 4 7 8 5 6 18KJM 5 2 55 Minamitsumori Nishinari ku Osaka 557 0063 JAPAN Phone 81 6 6659 8201 Fax 81 6 6659 8510 E mail ...

Page 3: ...match the actual input resistance range by using the linearization table ITEM 60 through 91 to compensate unused resistance ranges See the following figures If upper and lower overranges need not to be considered only two calibration points will suffice X 02 X 01 0 Y 02 100 Y 01 OUTPUT INPUT a c Unused Resistance Total Resistance Input Resistance b Input Resistance Actual Resistance Range 100 a b ...

Page 4: ...inearization table ITEM 10 Pm 2 curved in order to activate the settings X nn Input Signal in Y nn Output Signal in X or Y 15 00 to 115 00 15 0 X01 X02 X03 X04 X05 115 Y01 Y02 Y03 Y04 100 Y05 INPUT OUTPUT Figure 3 Linearization Table GROUP 01 ITEM MDFY DATA EXAMPLE 60 P X 01 XXX XX 61 P Y 01 XXX XX 62 P X 02 XXX XX 63 P Y 02 XXX XX 64 P X 03 XXX XX 65 P Y 03 XXX XX 66 P X 04 XXX XX 67 P Y 04 XXX X...

Page 5: ...ered output is shown LINEARIZATION TABLE 60 P Percentage X 01 XXX XX Input 1 61 P Percentage Y 01 XXX XX Output 1 91 P Percentage Y 16 XXX XX Output 16 Modification Code D No modification writing possible Used only for monitoring reading S Modifiable at any time P Modifiable only when the MAINTENANCE SWITCH is in the PRG mode MAINTENANCE Regular calibration procedure is explained below CALIBRATION...

Reviews: