M Design RD 1000 Instructions For Installation And Use Manual Download Page 5

5

 

 

must  be  positioned  so  as  to  maintain  the  safety  distance  from  any  flammable  materials  that  could  not  fire. 
However, if you decide to carry out the work on your own, we advise you to do the following: 

 

Refer to the terms and conditions of our contract of guarantee 

 

Ask your supplier for advice. 
 

2.2

 

 

LIST OF STANDARDS TO BE OBSERVED DURING ASSEMBLY AND 

OPERATIONS  

The fireplace type „RD“ complies with STN EN 13229. For installation and operation of the fireplace 

type „RD“ should proceed in accordance with STN 92 0300 „Local fire safety appliances and heat sources“ and 
STN 73 4201 „The design of chimneys and flues“.  

 

2.3

 

 

SAFE DISTANCE FIREPLACE STOVES TYPE „RD“ FROM FLAMMABLE 

MATERIALS, LOCATION OF THE STOVE AND SMOKE PIPES 

Fireplace type series „RD“ must be installed in accordance with Decree  MV SR No. 95/2004 statute, 

coll  establishing  specifications  and  requirements  for  fire  safety  during  installations  and  operation  of  heating 
appliances, electro thermal appliances and central heating installations and the constructions and use of chimneys 
and flues. It is also necessary to respect the STN 73 4210 „Running of the chimneys and flues and connecting 
fuel  appliances“.  The  manufacturer  recommends  the  installation  of  the  fireplace  furnace  type  series 
„RD“conducted  by  qualified  Professional  who  is  responsible  for  the  material  used  for  installation.  The 
manufacturer is responsible for the delivered product. 

 

 
When installing the fireplace type series „RD“ must be complied with 1000 mm safety clearance from 

combustible materials 

 
The fireplace type series „RD“  must be installed so that before it left space on the layout, about 1x1 m. 
 
Basis  respectively  base  under  fireplace  type  series  „RD“  must  be  straight  fire  material  and  must 

withstand  heat  stress.  Also,  wall  and  ceiling  material,  which  the  fireplace  type  series  „RD“  may  not  be  from 
combustible materials, respectively should be used for good thermal insulation. 

 

Combustion pipe must be fitted to the fireplace chimney`s mouthpiece furnace type series „RD“ so that 

it is firmly and tightly connected. 

 
The  combustion  pipe  might  be  of  black  respectively  stainless  steel  pipes  and  elbows.  The  flue 

connection  must  be  made  by  the  shortest  route  to  the  flue  by  STN  73  4210.  The  combustion  pipe  should  be 
implemented and consolidate  in order to be released accidentally or spontaneously. Pipes that are plugged into 
each other should be inserted in the direction of flow of exhaust gases. Where the flue passes through building 
structure,  which  contains  flammable  materials  or  surface  modified  flammable  materials  should  be  insulated  to 
protect the crossing design and implement in accordance with Decree MV SR No. 95/2004 statute. 

 
Connection the combustion pipe of the furnace type series „RD“ can only be the chimney, which has 

been  expertly  tested.  Based  on  expert  examination  of  the  appliance  flue  connection  and  issue  a professionally 
qualified  person  „Certificate  examination  on  implementation  of  the  chimney,  where  a professionally  qualified 
person to deliver state of the chimney and flue for their safe and reliable operation. 

 

2.4

 

LOCATION THE FIREPLACE STOVE TYPE SERIES „RD“ ON THE FLOOR 

In the place of installation fireplace insert type  series „RD“ on the  floor must be ensured a minimum 

floor load 1000 kg.m

-2

. The floor before the fireplace insert type series „RD“ must be fire-resistant material at 

a distance of at least 1000 mm from front wall of the fireplace insert type series „RD” . 

 

2.5

 

 REQUIREMENTS FOR PASSING COMBUSTION AIS 

The  fireplace  furnace  type  series  „RD“  can  be  placed  directly  in  the  heated  respectively  outside  the 

heated space. The combustion of fuel used airs from the area where the fireplace furnace is, or it is possible to 
transport external admission of air and connect it according to the point 2.7. In case of insufficient ventilation of 

Summary of Contents for RD 1000

Page 1: ...1 COLLECTION RD 750 1000 INSTRUCTION FOR INSTALLATION AND USE ...

Page 2: ...ES TYPE RD FROM FLAMMABLE MATERIALS LOCATION OF THE STOVE SMOKE PIPES 5 2 4 LOCATION THE FIREPLACE STOVE TYPE SERIES RD ON THE FLOOR 5 2 5 REQUIREMENTS FOR PASSING COMBUSTION AIS 5 2 6 INSTALLATION THE FIREPLACE MODEL SERIES RD ON THE PLACE OF USE 6 2 7 LOCATION FIREPLACE STOVE 6 2 8 ISOLATION AND SURROUND 6 2 9 VENTILATION 6 2 9 1 Natural convection 6 2 9 2 Hot air distribution 7 2 10 CHIMNEY 7 3...

Page 3: ... screw cover back with screw 1 and 2 Pic 2 For security reasons the door is locked from both left and right site Before installation of the stove please check lifting door lifting up down and opening see Pic 4 1 2 FUEL 1 2 1 Recommended fuel Wood hard soft damp cca 16 The quality of the wood is extremely important for the optimal function of the stove output clear glass etc The ideal is to use dri...

Page 4: ...e paint will harden and that give off smoke and a smell which starts after the fire has burned for about 10 minutes and lasts for about 15 minutes See to it that there is ample ventilation in the room The combustion chamber should be kept closed except for fuelling to prevent entry of gases into the room CAUTION It is not necessary to overload the fireplace with wood 1kg dried wood gices a 4kW pow...

Page 5: ... series RD may not be from combustible materials respectively should be used for good thermal insulation Combustion pipe must be fitted to the fireplace chimney s mouthpiece furnace type series RD so that it is firmly and tightly connected The combustion pipe might be of black respectively stainless steel pipes and elbows The flue connection must be made by the shortest route to the flue by STN 73...

Page 6: ... CM AIR INLET OPEN ALSO FOR EXTERNAL AIR INLET IS LOCATED AT THE BACK SIDE DOWN OF THE FIREPLACE STOVE SEE PIC 6 Setting up the high of fireplace insert can be in two ways 1 to do a special higher floor or to use steel construction 2 soft setting with a set screw M16 cca 50mm see Pic 1 2 8 ISOLATION AND SURROUND FOLLOW THESE INSTRUCTIONS IF YOU DO NOT FOLLOW THE INSTRUCTIONS QUIPMENT MAY OVERHEAT ...

Page 7: ...at register We recommend that you use the design grill M design which have many advantages Pic 7 8 NOTE The circulation of hot air is required to be in the room because of the reason to do not produce any vacuum Grill under close to the floor inlet cold air Pic 8 Do not connect it through a tube Air itself will find a way to get to the right place If possible mount all the accessories using the sa...

Page 8: ...ameter 200 mm Some chimneys may require different standard diameters In this case refer to the table for the height of the chimney and by reducing the possibility of reduction Chimney fireplace insert LUNA HC can connect from the top Pic 9 3 CONTROL REGULATION Regulation of inlet of air for fireplace RD is controlled by regulation on the front bar see pic 10 by using of key as you can see bellow P...

Page 9: ...egal requirement but it also makes sense for your own safety Refractory bricks babble may still work perfectly even if they are cracked However if there are missing pieces of bricks material bricks must be replaced in order to effectively protect the combustion chamber To remove the ash residue use the ash holder see Pic 12 4 1 1 CLEANING GLASS Close the door see Pic 4 Unlock the door Pic 13 move ...

Page 10: ...stove type series RD During operating the fireplace stove type series RD is forbidden give the hand into the flow of heated air because of the security reasons there is too high temperature Fire in the fireplace stove type series RD never extinguishes with water The space where it is located fireplace stove type series RD must be ensured with adequate air inlet for combustion of fuel Loading doors...

Page 11: ... serial number see Pic 15 TYPE fireplace stove RD RD 750 RD 1000 Rated thermal power kW 14 7 15 7 Average efficiency 82 82 Heat flow into the space kW 14 7 15 7 Power range kW 4 2 15 5 2 16 Flue gas temperature at rated output C 176 2 176 2 Avg CO concentration at 13 O2 0 1 0 1 The average volume concentration of CO at 13 O2 mg m 3 1219 1219 Minimum blast Pa 12 12 The weight of the fireplace furna...

Page 12: ...885 705 1327 5 1362 5 453 4 2 6 0 933 508 562 1091 750 RD ...

Page 13: ...1135 705 1327 5 562 1220 63 1183 4 2 6 0 210 508 1362 5 1341 453 1000 RD ...

Page 14: ...ructions Assembly installation or repair by a third party including the buyer Heat cracks which normally occur in the mantel In cases where changes have been made to the appliance without our consent In cases where the buyer cannot show his her warranty card with the purchase invoice Likewise where the guarantee and or the invoice show s signs of tampering or forgery cros sed out date legible modi...