139-0498-02.13
13
Chapter Four--Wiring
2. At the RPS Slave panels, strip the cable sheath back
approximately 20 inches. Cut the conductors for Left Bus
B, Left Bus A, – and + down to approximately 4 inches
and terminate them in the Left Bus screw-terminal
header from left to right. Terminate the remaining two
conductors in the Right Bus B and Right Bus A positions
of the Right Bus screw-terminal header.
3. Using two cut lengths of 18 AWG wire, install jumpers
from Left Bus – and + to Right Bus – and +. Right Bus will
not operate without these jumpers installed to provide
24VDC power and common.
4. Set the slave address selectors as follows:
Table 4-2
Left Control Bus
Right Control Bus
Panel #2
2
3
Panel #3
4
5
Panel #4
6
7
Master Panel
Slave Panel 2
Slave Panel 3 Slave Panel 4