4
Wiring Diagram #1 (Suggested):
A dimmer (fed by normal power) controls emergency
lighting in a space. Upon loss of normal power, the emergency lighting comes on at full brightness regard-
less of dimmer position.
#4 WHITE/BLUE
TEST
EMERGENCY
POWER
UTILITY
POWER
#6 BLUE
#5 YELLOW
EMERGENCY
PANEL
OR
INVERTER
EMERGENCY
NEUTRAL
EMERGENCY LIGHT
EMERGENCY
HOT
NORMAL
(UTILITY)
PANEL
NORMAL
NEUTRAL
NORMAL
HOT
20A
20A
#3 WHITE
#1 BLACK
#2 RED
Optional normally open occupancy sensor/power pack/relay panel.
FREQUENTLY ASKED QUESTIONS:
Can I power more than 1 light from the LUT-ALCR-D-FM?
It is recommended that the LUT-ALCR-D-FM power only one fixture/luminaire. If you want
to control more than one fixture/luminaire, use the higher rated LUT-ALCR-D-FM
Do I need a separate normal and emergency ballast/driver?
NO, the emergency light only needs a single ballast/driver.
Can I use the LUT-ALCR-D-FM with 3-way dimmers?
YES
Why is my LUT-ALCR-D-FM buzzing/humming/chattering?
This can occur with some dimmers when they do not have enough load on them. Changing
to Wiring Diagram #2 should eliminate this issue, contact LVS for further assistance.
How do I wire the LUT-ALCR-D-FM with DALI/EcoSystem loads?
Please check this link: http://www.lvscontrols.com/assets/EPC2DDALI.pdf
Wiring Diagram #2 (Shunt):
A dedicated dimmer (fed by emergency power) controls emergency
lighting in a space. Upon loss of normal power, the emergency lighting comes on at full brightness regard-
less of dimmer position.
#4 WHITE/BLUE
TEST
EMERGENCY
POWER
UTILITY
POWER
#6 BLUE
#5
YELLOW
EMERGENCY
PANEL
OR
INVERTER
EMERGENCY
NEUTRAL
EMERGENCY LIGHT
EMERGENCY
HOT
NORMAL
(UTILITY)
PANEL
NORMAL
NEUTRAL
NORMAL
HOT
20A
20A
#3 WHITE
#1 BLACK
#2 RED
DIMMER
(CAP OFF)
VIOLET
ORANGE
GRAY
VIOLET
VIOLET
GRAY
DIMMER/ROOM
CONTROLLER
VIOLET
GRAY
VIOLET
ORANGE
GRAY
VIOLET
Connect to violet
from dimmer
Connect to gray
from dimmer
YELLOW
(CAP)
YELLOW
(CAP)