background image

3

Installation

In order to install the LUT in accordance with national/local code requirements, a qualified electrician 
should review & understand the installation instructions.  Check voltage & current requirements.  
Verify & lock out circuit breakers on both regular (utility) power & 24 hour emergency generator or 
inverter circuit.  Install a self-adhesive 2" x 3" caution label in each fixture or load controlled by an LUT 
cautioning that the load is supplied from 2 different power sources, normal & emergency.  Review 
wiring diagram & connect wires, one at a time, in accordance with the numeric identification.  In order 
to provide a safe light level, when regular power is interrupted, it is recommended that a minimum of 
appproximately 5000 lumen are controlled by a 24 hour emergency circuit & are spaced no farther 
than 24' in any direction from each other in a normal 9' white ceiling environment.

Initial Testing and Troubleshooting

In a new installation, where hundreds of devices may be used, each having as many as 14 wires to 
be correctly connected, it is important that a fast, convenient method is used to check connections.  
In order to test that the wires are connected correctly, without any inconvenience to occupants, do 
not turn off regular (utility) power off until you have checked each device as follows:

1)  Check that regular branch circuit breaker is connected & utility power is available.  Green LED 
should be lit.  If green LED is not lit, check connections & continuity to branch circuit breaker. 
2)  Check that emergency branch circuit breaker is connected & emergency power is available.  Red 
LED should be lit.  If red LED is not lit, check connections & continuity to branch circuit breaker. 
3)  Normal Operation Test:  Turn dimmer or other control device to the “ON” position.  Normal & 
emergency lights should turn on.  Reduce dimmer to ~50%, normal and emergency lights should dim 
together.  Turn room switch or control to the “OFF” position.  Normal lights should turn off immediate-
ly.  If blue loop is connected, emergency lights should stay on for at least 2.5 seconds.  If blue 
jumper is cut and capped, emergency lights should turn off immediately.
4)  Emergency Operation Test:  Press and hold test button, emergency lights should illuminate at full 
brightness until test button is released.

Maintenance

No maintenance is required to keep the LUT functional.  However, regular testing should be 
performed when the lamps or ballasts have been replaced or when remodeling has taken place.  

Single Line Drawings

















Normal/Utility 
Power Source

Emergency 

Power Source

Neutral 

Not Shown





One Fixture Mounted LUT is suggested per 
emergency fixture.

NORMAL 

ROOM LIGHTS 

(optional)

DESIGNATED 

EMERGENCY 

LIGHT

EMERGENCY 

POWER 

CONTROL

LIGHTING CONTROL 

DEVICE (SWITCH, 
SENSOR, POWER 

PACK, RELAY PANEL)

NORMAL

POWER

PANEL

EMERGENCY 

POWER

PANEL

UL 1008

Transfer 

Switch Or 

Equivalent

EMERGENCY 

POWER CONTROL

EMERGENCY 

POWER CONTROL

Reviews: