Wiring Diagram #1 (Suggested): 

A  dimmer  (fed  by  normal  power)  controls  emergency        

lighting in a space.  Upon loss of normal power, the  emergency lighting comes on at full brightness regard-

less of dimmer position.

#4 WHITE/BLUE

TEST

EMERGENCY

POWER

UTILITY

POWER

#6 BLUE

#5 YELLOW

EMERGENCY 

PANEL 

OR 

INVERTER

EMERGENCY 
NEUTRAL

EMERGENCY LIGHT

EMERGENCY 
HOT

NORMAL

(UTILITY)

PANEL

NORMAL 

NEUTRAL

NORMAL 

HOT

20A

20A

#3 WHITE

#1 BLACK

#2 RED

Optional normally open occupancy sensor/power pack/relay panel.

FREQUENTLY ASKED QUESTIONS: 
Can I power more than 1 light from the EPC-2-D-FM?

It is recommended that the EPC-2-D-FM power only one fixture/luminaire.  If you want to 
control more than one fixture/luminaire, use the higher rated EPC-2-D.

Do I need a separate normal and emergency ballast/driver? 

 

NO, the emergency light only needs a single ballast/driver.  

Can I use the EPC-2-D-FM with 3-way dimmers?

YES

Why is my EPC-2-D-FM buzzing/humming/chattering?

This can occur with some dimmers when they do not have enough load on them.  Changing 
to Wiring Diagram #2 should eliminate this issue, contact LVS for further assistance.  

How do I wire the EPC-2-D-FM with DALI/EcoSystem loads?

Please check this link:  http://www.lvscontrols.com/assets/EPC2DDALI.pdf

Wiring Diagram #2 (Shunt): 

A dedicated dimmer (fed by emergency power) controls emergency 

lighting in a space.  Upon loss of normal power, the emergency lighting comes on at full brightness regard-

less of dimmer position.

#4 WHITE/BLUE

TEST

EMERGENCY

POWER

UTILITY

POWER

#6 BLUE

#5 

YELLOW

EMERGENCY 

PANEL 

OR 

INVERTER

EMERGENCY 
NEUTRAL

EMERGENCY LIGHT

EMERGENCY 
HOT

NORMAL

(UTILITY)

PANEL

NORMAL 

NEUTRAL

NORMAL 

HOT

20A

20A

#3 WHITE

#1 BLACK

#2 RED

DIMMER

(CAP OFF)

VIOLET

ORANGE

GRAY

VIOLET

VIOLET

GRAY

DIMMER/ROOM 

CONTROLLER

VIOLET

GRAY

VIOLET

ORANGE

GRAY

VIOLET

Connect to violet

 from dimmer

Connect to gray 

from dimmer

YELLOW

(CAP)

YELLOW

(CAP)

Summary of Contents for EPC-2-D-FM

Page 1: ... be used with LED ballast tungsten and general use loads 2 Make sure all connections are in accordance with the National Electrical Code and local regulations 3 To reduce the risk of electric shock disconnect both normal and emergency power supplies before servicing 4 This product is intended to be used to control indoor and outdoor located loads 5 An unswitched AC power source is required 120 240...

Page 2: ...gh inrush electronic ballasts or drivers highbay or 347V applications use EPC 1 D HV Patented Automatic Diagnostic When the room switch is turned off EPC 2 D FM tests itself for 2 5 seconds testing that an emergency power source is available and that the EPC 2 D FM ballast and lamp s are functioning correctly This feature eliminates the need for manual monthly testing and is approved for this purp...

Page 3: ...t breaker is connected utility power is available Green LED should be lit If green LED is not lit check connections continuity to branch circuit breaker 2 Check that emergency branch circuit breaker is connected emergency power is available Red LED should be lit If red LED is not lit check connections continuity to branch circuit breaker 3 Normal Operation Test Turn dimmer or other control device ...

Page 4: ...last driver Can I use the EPC 2 D FM with 3 way dimmers YES Why is my EPC 2 D FM buzzing humming chattering This can occur with some dimmers when they do not have enough load on them Changing to Wiring Diagram 2 should eliminate this issue contact LVS for further assistance How do I wire the EPC 2 D FM with DALI EcoSystem loads Please check this link http www lvscontrols com assets EPC2DDALI pdf W...

Reviews: