MODEL EPC-2-D-FM INSTALLATION INSTRUCTIONS

1

LVS

LVS, Inc. 2555 Nicholson Street, San Leandro, CA 94577-4216
Phone: 510-352-9600     1-800-982-4587    Fax: 510-352-6707
Web:  WWW.LVSCONTROLS.COM

LVS, Inc. warrants to the original purchaser/user for the published warranty period from the date of shipment that should LVS instruments or 

equipment prove defective by reason of improper workmanship or material, LVS will repair or replace the same equipment without charge.  

This warranty does not cover defects or malfunctions arising from improper installation, operation or repair, or neglect, accident, or abuse.  LVS 

will honor its warranty provided the equipment has not been physically damaged or improperly installed or connected.  To obtain warranty/re-

pair, the defective product should be shipped freight prepaid within the warranty period to the address below.  To the extent permitted by 

applicable law, all warranties extending beyond repair or replacement as described above are disclaimed, including the implied warranties of 

merchantability and fitness for a particular purpose.  Where applicable law prohibits disclaimers or the implied warranties of merchantability 

and fitness; those warranties are limited to 12 months from date of shipment.  LVS provides a 90 day money back guarantee if equipment 

does not perform in accordance with LVS published specifications.  The liability of LVS and its agents under all warranties is limited to repair and 

replacement as described herein and under no circumstances shall there be liability for any other kind of loss, damage, or labor, either conse

-

quential or for injury to person or property or otherwise.

5-Year Limited Warranty

1. This product can be used with LED, ballast, tungsten, and general use loads.
2. Make sure all connections are in accordance with the National Electrical Code and local regulations.
3. To reduce the risk of electric shock, disconnect both normal and emergency power supplies before servicing.
4. This product is intended to be used to control indoor and outdoor located loads.
5. An unswitched AC power source is required (120-240VAC/277VAC).
6. Do not install near gas or electric heaters.
7. Do not attempt to service a sealed Emergency Power Control.  When malfunctioning, return to the                  
manufacturer: LVS, Inc. 2555 Nicholson Street, San Leandro, CA 94577.
8. The use of accessory equipment is not recommended by the manufacturer and may cause unsafe condition.
9. Do not use this product for other than its intended use.
10. Servicing should be performed by qualified service personnel.
11. Equipment should be mounted in locations and at heights where it will not readily be subjected to            
tampering by unauthorized personnel.

! IMPORTANT SAFEGUARDS !

SAVE THESE INSTRUCTIONS

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS 

SHOULD ALWAYS BE FOLLOWED, INCLUDING THE FOLLOWING:

Electrical Specfications

120-240/277V Sensing Input
N.C. Output Contact
3 Amp Electronic/LED Load Rating (120-277V)
5 Amp Ballast Load Rating (120-277V)
5 Amp General Use Rating (120-277V)
360W Incandescent Load Rating (120V)
600W Incandescent Load Rating (277V)
Auxiliary N.O.+N.C. Contact (1A/30VDC)
UL924 Listed (usUL/cUL)

Mechanical Specifications

Fixture or Panel Mount
Damp Location Rated
Shipping Weight:  6 oz  Color : Black

Temperature: -40˚C-60˚C (-40˚F - 140˚F)

Body Size:  5”x1”x1.25” (125mmx25.4mmx30mm)

UL

®

UL924 LISTED

C

US

Summary of Contents for EPC-2-D-FM

Page 1: ... be used with LED ballast tungsten and general use loads 2 Make sure all connections are in accordance with the National Electrical Code and local regulations 3 To reduce the risk of electric shock disconnect both normal and emergency power supplies before servicing 4 This product is intended to be used to control indoor and outdoor located loads 5 An unswitched AC power source is required 120 240...

Page 2: ...gh inrush electronic ballasts or drivers highbay or 347V applications use EPC 1 D HV Patented Automatic Diagnostic When the room switch is turned off EPC 2 D FM tests itself for 2 5 seconds testing that an emergency power source is available and that the EPC 2 D FM ballast and lamp s are functioning correctly This feature eliminates the need for manual monthly testing and is approved for this purp...

Page 3: ...t breaker is connected utility power is available Green LED should be lit If green LED is not lit check connections continuity to branch circuit breaker 2 Check that emergency branch circuit breaker is connected emergency power is available Red LED should be lit If red LED is not lit check connections continuity to branch circuit breaker 3 Normal Operation Test Turn dimmer or other control device ...

Page 4: ...last driver Can I use the EPC 2 D FM with 3 way dimmers YES Why is my EPC 2 D FM buzzing humming chattering This can occur with some dimmers when they do not have enough load on them Changing to Wiring Diagram 2 should eliminate this issue contact LVS for further assistance How do I wire the EPC 2 D FM with DALI EcoSystem loads Please check this link http www lvscontrols com assets EPC2DDALI pdf W...