I N S T R U C T I O N S
Power Panel
Installation Instructions
S P E C I F I C A T I O N S U B M I T T A L
Job Name:
Model Numbers:
Job Number:
I-114
1221 Admiral Street Richmond VA 23220 800-817-1204 LuXoutShades.com
LSPP-12V-29A-18S
4). Low Voltage Wiring
A.
SHOCK HAZARD. Risk of serious injury or death. Locate and lock the supply
breaker in the OFF position before wiring to the terminal blocks.
Note: Note: All secondary wiring must be of type CL2, CL2P, CL2R, CL2X or other cable with
equivalent or better electrical, mechanical, and flammability ratings in accordance with local and
national electric code.
1. Unplug panel.
2. Remove as many knockout tabs as necessary from the top of the enclosure and insert
0.50 in strain reliefs (not included) into the open knockout holes.
3. Route the wire through the strain reliefs and to the output terminal blocks.
4. Strip the wire insulation so that 0.25 in of bare wire is exposed. Insert the Common leads
into the (-) Terminal screw and the +12 V leads into the (+) Terminal screw. Tighten the
terminal blocks to 3.5 - 5 in•lb (0,4, -0,6 N•m). Make sure the wire insulation is not
pinched.
5. Close metal cover securely back onto the enclosure and tighten the screws.
6. Restore power to the panel by plugging into outlet.
7. IMPORTANT NOTE: No more than 5, 35mm or 45mm motors can be wired to each of the
sections. Do not overload section. For 25mm & 28mm motors the maximum number is 9
per section.
B.
Wire Length Chart
Use this chart to determine the maximum wire length, from panel to shade, based on the gauge
of the wire that is used.
Distance to
shade
16 AWG
(1.5 mm²)
18 AWG
(1 mm²)
125 ft (35 m)
200 ft (60 m)