Function 

The mixing group GM 1192 is a regulation group which combines a 
number of components in a single device able to maintain a pre-set 
temperature in the radiant panels circuit of mixed heating systems. The 
temperature in the panels is kept constant by a regulating valve which 
mixes hot water coming from the boiler with the low temperature one 
circulating in the panels. The GM 1192 can be connected directly to 
Luxor manifolds for radiant panels by means of a G 1” male fitting with 
soft seal. This makes the GM 1192 particularly convenient, since 

it can be kept in stock as a modular component.  

Moreover, the GM 1192 makes mixed heating systems extremely 
flexible, since the regulation group can be adjusted to meet the future 
requirements of the secondary circuit. It is therefore possible to expand 
the radiant panels system simply by adding outlets, without temperature 
or pressure issues downstream of the group. 

The GM 1192 can be set both to increase the heating capacity 

and to balance pressure drops. 

Finally, thanks to its great regulation capacity, the GM 1192 allows to 
make the secondary circuit independent from the primary in case of 
replacement of important parts of the system, for example when a new 
boiler with a different operating principle is installed. By means of the 
bypass circuit, the circulation pump can keep on operating at design 
conditions. 

This type of system can supply a max thermal power of 20 kW with a 
temperature of the primary circuit of ≥ 70°C. 

 

Technical data  

 

Max. working pressure: 

6 bar 

Max. differential pressure: 

1 bar 

Regulation range on the bypass: 

0.2 ÷ 0.7 bar 

Max. temperature on primary circuit: 

80 °C 

Max. working temperature on 
secondary circuit: 

70 °C 

Temperature adjustment range on 
secondary circuit: 

20 ÷ 65 °C 

Thermometer range: 

0 ÷ 80 °C 

Connections on primary circuit (to 
boiler): 

G 1” female 

Connections to secondary manifold: 

G 1” male 

Adjustment range of therm. head: 

20 ÷ 65 °C 

Length of capillary: 

2 m 

 
 
 
 
 
 
 
 

Summary of Contents for GM 1192

Page 1: ...y by adding outlets without temperature or pressure issues downstream of the group The GM 1192 can be set both to increase the heating capacity and to balance pressure drops Finally thanks to its great regulation capacity the GM 1192 allows to make the secondary circuit independent from the primary in case of replacement of important parts of the system for example when a new boiler with a differe...

Page 2: ...l plated annealed copper Accessories Brass parts CW 617 N DW UNI EN 12165 2016 CW 614 N DW UNI EN 12164 2016 Steel parts Stainless steel Gaskets Peroxide cured EPDM Safety valve Acetal Thermostatic head Head RAL9016 white ABS Sensor Liquid Thermometer Case and stem Galvanised steel Cover Transparent plastic material Thermometric element Bimetallic spiral spring Surface treatment Nickel plating ...

Page 3: ... 72000052 G1 x130mm G1 1 2 G1 M30x1 5 85 32 72000055 G1 x180mm G1 1 2 G1 M30x1 5 85 32 72000057 G1 x180mm G1 1 2 G1 M30x1 5 85 32 Construction 1 Thermostatic regulating valve boiler delivery controlled by thermostatic head with remote probe 0 10V electrothermal head or 3 point or 0 10V electric motor 2 Pump shut off valve 3 Ball valve for pump interception and balancing of the secondary circuit 4 ...

Page 4: ...Flow Rate Diagram Curve Adjustment Kv 1 ΔT 2 K 0 9 2 QM MAX 3 88 ...

Page 5: ...Flow Rate Diagram Curve Adjustment Kv 1 1 2 0 09 2 1 0 27 3 1 1 2 0 76 4 2 0 98 5 2 1 2 1 20 6 3 1 46 7 3 1 2 1 70 8 4 1 93 9 4 1 2 2 19 10 5 2 47 11 5 1 2 2 75 12 All open 3 01 ...

Page 6: ...p protecting the control stem of the adjustment valve Remove the protection cap To ease the installation set the thermostatic head to the maximum value and screw it onto the valve Set the head to the desired temperature Place the bulb of the head into the fastening device Loosen the union fittings marked with 12 in the picture to ease the installation of the pump Assemble the pump taking care to p...

Page 7: ... adjust the valve unscrew the brass plug and act on the obturator by means of a 5 mm hex wrench The value shown by the thermostatic head is indicative the temperature of the water entering the radiant panels circuit can be read on the thermometer of the upper group To avoid excessive noise in the system do not use the thermostatic valve with ΔP values higher than 0 5 bar Coupled with the pump PCE ...

Reviews: