Working Instructions 

 

 

The circulation of water through the  secondary circuit radiant panels is activated by the 
pump featured in the GM 1192, while the thermostatic head mounted on the 
adjustment valve keeps the temperature of the water to be sent to the radiant panels 
constant by acting on the quantity of hot water which is integrated into the secondary 
circuit. 
The water returning to the primary circuit flows through the lockshield valve upon which 
it is possible to act in order to balance pressure drops. It is advisable to install a 
security thermostat on the pump inlet valve in order to avoid damages caused by a 
sudden temperature rise. The intervention of the thermostat must block the functioning 
of the pump.  

 

How to install the fixed point thermostatic head: 

  The GM 1192 system is supplied with a plastic cap protecting the control stem of the 

adjustment valve. Remove the protection cap.  

  To ease the installation, set the thermostatic head to the maximum value and screw 

it onto the valve. 

  Set the head to the desired temperature. 

 

 

  Place the bulb of the head into the fastening device. 

 

 

Loosen the union fittings marked with “12” in the picture to ease the installation of 
the pump. 

  Assemble the pump taking care to place it in the correct direction, which is upwards.  

 

After the installation, tighten back the fittings “12” 

 

 

The balancing ball valve “3” is adjusted by aligning the reference mark on the control 
stem with the scale by means of a 4 mm hex wrench. 

 

 

The bypass valve “6” is simply adjusted by turning the knob until the desired value. 

 

  To substitute the whole tightening device of the thermostatic screw while the group 

is operating, proceed as follows: 

o

  Remove the protection cap, manual knob, thermostatic head or thermoelectric 

head;  

o

  Hold the screw body with a 19 mm wrench and unscrew the tightening device 

by means of a 9 mm wrench; 

Summary of Contents for GM 1192

Page 1: ...y by adding outlets without temperature or pressure issues downstream of the group The GM 1192 can be set both to increase the heating capacity and to balance pressure drops Finally thanks to its great regulation capacity the GM 1192 allows to make the secondary circuit independent from the primary in case of replacement of important parts of the system for example when a new boiler with a differe...

Page 2: ...l plated annealed copper Accessories Brass parts CW 617 N DW UNI EN 12165 2016 CW 614 N DW UNI EN 12164 2016 Steel parts Stainless steel Gaskets Peroxide cured EPDM Safety valve Acetal Thermostatic head Head RAL9016 white ABS Sensor Liquid Thermometer Case and stem Galvanised steel Cover Transparent plastic material Thermometric element Bimetallic spiral spring Surface treatment Nickel plating ...

Page 3: ... 72000052 G1 x130mm G1 1 2 G1 M30x1 5 85 32 72000055 G1 x180mm G1 1 2 G1 M30x1 5 85 32 72000057 G1 x180mm G1 1 2 G1 M30x1 5 85 32 Construction 1 Thermostatic regulating valve boiler delivery controlled by thermostatic head with remote probe 0 10V electrothermal head or 3 point or 0 10V electric motor 2 Pump shut off valve 3 Ball valve for pump interception and balancing of the secondary circuit 4 ...

Page 4: ...Flow Rate Diagram Curve Adjustment Kv 1 ΔT 2 K 0 9 2 QM MAX 3 88 ...

Page 5: ...Flow Rate Diagram Curve Adjustment Kv 1 1 2 0 09 2 1 0 27 3 1 1 2 0 76 4 2 0 98 5 2 1 2 1 20 6 3 1 46 7 3 1 2 1 70 8 4 1 93 9 4 1 2 2 19 10 5 2 47 11 5 1 2 2 75 12 All open 3 01 ...

Page 6: ...p protecting the control stem of the adjustment valve Remove the protection cap To ease the installation set the thermostatic head to the maximum value and screw it onto the valve Set the head to the desired temperature Place the bulb of the head into the fastening device Loosen the union fittings marked with 12 in the picture to ease the installation of the pump Assemble the pump taking care to p...

Page 7: ... adjust the valve unscrew the brass plug and act on the obturator by means of a 5 mm hex wrench The value shown by the thermostatic head is indicative the temperature of the water entering the radiant panels circuit can be read on the thermometer of the upper group To avoid excessive noise in the system do not use the thermostatic valve with ΔP values higher than 0 5 bar Coupled with the pump PCE ...

Reviews: