700678-LTG-E-0415
Johnson Controls Unitary Products
23
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
TCJD42S4(3,4)S4(E)
INDOOR COIL MODEL NO.
FC/MC/PC43
AIR TEMP.
ENTERING
OUTDOOR UNIT (°F)
ID CFM
1200
1400
1600
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
41.8
43.9
43.7
47.2
49.9
43.3
45.0
44.7
47.9
50.9
44.7
46.0
45.7
48.5
51.9
S.C.
41.6
36.4
30.9
29.8
23.8
43.0
38.5
32.5
31.0
24.2
44.3
40.7
34.0
32.2
24.5
KW
2.79
2.81
2.82
2.82
2.85
2.80
2.82
2.82
2.83
2.85
2.80
2.83
2.82
2.84
2.86
75
T.C.
39.8
41.2
41.3
45.1
48.2
41.4
42.3
42.2
45.7
49.0
42.9
43.3
43.2
46.4
49.8
S.C.
39.5
35.2
29.8
29.1
23.1
41.0
37.4
31.6
30.6
23.8
42.5
39.7
33.5
32.1
24.5
KW
3.08
3.10
3.10
3.13
3.17
3.10
3.11
3.11
3.14
3.18
3.12
3.13
3.12
3.15
3.19
85
T.C.
37.8
38.6
38.8
43.0
46.5
39.4
39.6
39.7
43.6
47.1
41.0
40.6
40.7
44.3
47.7
S.C.
37.5
34.1
28.7
28.4
22.4
39.1
36.4
30.8
30.2
23.4
40.7
38.7
32.9
32.0
24.5
KW
3.38
3.39
3.39
3.44
3.50
3.41
3.41
3.41
3.46
3.51
3.43
3.42
3.42
3.47
3.52
95
T.C.
35.8
35.9
36.3
40.9
44.8
37.5
36.9
37.3
41.5
45.2
39.2
37.9
38.2
42.1
45.6
S.C.
35.4
33.0
27.6
27.7
21.7
37.1
35.3
30.0
29.8
23.0
38.8
37.6
32.3
31.9
24.4
KW
3.67
3.68
3.68
3.76
3.82
3.71
3.70
3.70
3.77
3.83
3.75
3.72
3.72
3.79
3.84
105
T.C.
33.1
33.1
32.6
37.0
41.6
34.7
34.2
33.5
37.6
42.0
36.3
35.4
34.4
38.2
42.4
S.C.
32.7
31.0
26.3
26.4
20.7
34.3
33.1
28.4
28.6
22.1
35.9
35.2
30.5
30.8
23.5
KW
3.98
3.98
3.96
4.05
4.14
4.02
4.01
3.98
4.07
4.16
4.06
4.05
4.01
4.09
4.18
115
T.C.
30.5
30.2
28.9
33.3
38.4
32.0
31.6
29.8
33.8
38.8
33.4
33.0
30.8
34.4
39.3
S.C.
30.2
29.1
25.0
25.1
19.8
31.6
30.9
26.8
27.4
21.3
33.1
32.7
28.7
29.6
22.7
KW
4.27
4.27
4.22
4.33
4.45
4.32
4.31
4.26
4.36
4.48
4.37
4.36
4.29
4.39
4.51
125
T.C.
27.9
27.4
25.2
29.5
35.2
29.2
29.0
26.2
30.0
35.7
30.6
30.5
27.1
30.5
36.2
S.C.
27.6
27.3
23.7
23.8
18.9
28.9
28.8
25.3
26.2
20.4
30.3
30.3
26.9
28.5
21.8
KW
4.57
4.56
4.49
4.62
4.77
4.62
4.62
4.53
4.65
4.80
4.67
4.67
4.57
4.68
4.84
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (O INDOOR).
Air Handlers
Coils
T.C.
S.C.
KW
–
FC/MC/PC43
1.00
1.00
1.00
–
FC/MC/PC48
1.01
1.01
1.01
–
FC/MC/PC60
1.00
0.99
1.00
–
FC/MC62
1.01
1.02
1.01
–
FC64
1.01
1.03
0.99
–
UC48
1.01
1.01
1.01
AHE42D
–
1.01
1.03
0.93
AHE48D
–
1.01
1.02
0.93
AHE60D
–
1.01
1.04
0.93
AHR42C
–
1.01
1.03
1.01
AHR48D
–
0.99
0.97
0.99
AHR60D
–
1.01
1.01
1.01
AHV42D
–
1.01
1.01
0.95
AHV48D
–
1.00
0.98
0.92
AHV60D
–
1.01
1.01
0.93
MV16C
FC/MC43C
1.01
1.01
0.93
MV16C
FC/MC48C
1.01
1.02
0.95
MV16C
FC60C
1.01
1.01
0.97
MV20D
FC/MC48D
1.01
1.04
0.93
MV20D
FC/MC60D
1.01
1.01
0.95
MV20D
FC/MC62D
1.01
1.03
0.93
MV20D
FC64D
1.01
1.03
0.91
MX16CN21
FC/MC43C
1.00
1.01
0.94
MX16CN21
FC/MC48C
1.01
1.01
0.94
MX16CN21
FC60C
1.01
1.01
0.94
MX20DN21
FC/MC48D
1.02
1.02
0.94
MX20DN21
FC/MC60D
1.01
1.01
0.93
MX20DN21
FC/MC62D
1.02
1.04
0.92
MX20DN21
FC64D
1.06
1.07
0.93
Furnaces
Coils
T.C.
S.C.
KW
T*(8,L)V*B12
FC/MC/PC43B
0.99
0.97
0.97
T*(8,L)V*C16
FC/MC/PC43C
1.01
1.01
0.97
T*(8,L)V*C16
FC/MC/PC48C
1.01
1.00
0.97
T*(8,L)V*C16
FC/MC/PC48D
1.01
1.00
0.97
T*(8,L)V*C16
FC/MC/PC60D
1.01
1.01
0.97
T*(8,L)V*C16
FC/MC62D
1.01
1.03
0.97
T*(8,L)V*C16
FC/PC60C
1.01
1.01
0.97
T*(8,L)V*C16
FC64D
1.01
1.03
0.93
T*(8,L)V*C16
UC48C
1.01
1.01
0.97
T*(8,L)V*C16
UC60C
1.01
1.01
0.97
T*(8,L)V*C20
FC/MC/PC43C
1.01
1.03
0.99
T*(8,L)V*C20
FC/MC/PC48C
1.01
1.01
0.97
T*(8,L)V*C20
FC/MC/PC48D
1.01
1.01
0.97
T*(8,L)V*C20
FC/MC/PC60D
1.01
1.01
0.95
Continued on next page.
Air Handlers
Coils
T.C.
S.C.
KW