background image

7

6

G O Y2 Y1 RC C RH W1 W2 E B

TYPICAL 24VAC 4 WIRE HOOKUP

SINGLE STAGE HEATING AND COOLING

FAN

XFMR

COMPRESSOR

GAS

VALVE

AC LINE

TYPICAL INSTALLER SETUP:

JUMPER

PROVIDED

SYSTEM COMMON

SYSTEM TYPE = FURNACE

[01]

HEAT STAGES =1

[02]

COMPRESSOR STAGES = 1

[03]

MODES = Ht-Off-Cl-Auto

[04]

HEAT FAN CONTROL
= GAS

[09]

OPTIONAL COMMON
ALLOWS USE OF
SYSTEM POWER

[1]

NOTES:

G O Y2 Y1 RC C RH W1 W2 E B

TYPICAL 5 WIRE HOOKUP

SINGLE STAGE HEATING AND COOLING

COOLING

XFMR 1

FAN

GAS

VALVE

HEATING

XFMR 2

AC LINE

AC LINE

COOL

COMMON

COMPRESSOR

TYPICAL INSTALLER SETUP:

SYSTEM TYPE = FURNACE

[01]

HEAT STAGES =1

[02]

COMPRESSOR STAGES = 1

[03]

MODES = Ht-Off-Cl-Auto

[04]

HEAT FAN CONTROL
= GAS

[09]

OPTIONAL COMMON
ALLOWS USE OF
SYSTEM POWER

[1]

NOTES:

G O Y2 Y1 RC C RH W1 W2 E B

TYPICAL SINGLE-STAGE HEAT PUMP WITH

(2 STAGES HEAT AND 1 STAGE COOL)

OPTIONAL AUX AND EMERGENCY HEAT

FAN

SYSTEM

XFMR

COMPRESSOR

AUX/EM

HEAT

REVERSING

VALVE

AC LINE

OPTIONAL COMMON
ALLOWS USE OF
SYSTEM POWER
USE "B" OR "O" BUT
NOT BOTH

AUX HEAT AND
EMERGENCY HEAT
ARE OPTIONAL

[1]

[2]

[3]

NOTES:

JUMPER

PROVIDED

SYSTEM COMMON

TYPICAL INSTALLER SETUP:

SYSTEM TYPE = HEAT PUMP

[01]

HEAT STAGES =1

[02]

COMPRESSOR STAGES = 1

[03]

MODES = Ht-Off-Cl-

 EmHt-Auto

[04]

HEAT FAN CONTROL
= ELECTRIC

[09]

G O Y2 Y1 RC C RH W1 W2 E B

USE 2 SEPARATE SINGLE STAGE HEATERS

AS A 2 STAGE HEAT SYSTEM

SYSTEM

XFMR 1

HEATER

1

HEATER

2

SYSTEM

XFMR 2

AC LINE

AC LINE

SYSTEM 1

COMMON

SYSTEM 2

COMMON

OPTIONAL COMMON
ALLOWS USE OF
SYSTEM POWER

[1]

NOTES:

TYPICAL INSTALLER SETUP:

SYSTEM TYPE = HEAT PUMP

[01]

HEAT STAGES =1

[02]

COMPRESSOR STAGES = 1

[03]

MODES = Heat-Off

[04]

HEAT FAN CONTROL
= ELECTRIC

[09]

Summary of Contents for LuxPro EVERYTHING'STAT PSP722E

Page 1: ... 4 2 USER SETUP MENU 12 4 2 1 ACCESS AND NAVIGATE USER SETUP MENU 12 4 2 2 KEYBOARD LOCK 12 4 2 3 BEEP 12 4 2 4 TEMPERATURE DISPLAY FORMAT F C DISPLAY 13 4 2 5 CLOCK FORMAT 13 4 2 6 CALIBRATION OFFSET 13 4 2 7 MAXIMUM HEAT SETTING 13 4 2 8 MINIMUM COOL SETTING 13 4 2 9 SMART RECOVERY 13 4 2 10 FILTER LIMIT 13 4 2 11 USER SETUP MENU 13 4 3 ADVANCED FEATURES AND OPERATION 13 4 3 1 EMERGENCY HEAT 13 ...

Page 2: ...Differential Cycle Rate Programmable Length Minimum Run Time Programmable Auto Changeover Dead Band Programmable Fan Delays For Heat Cool In Both On And Off 2 COMPATIBILITY Your PSP722E is compatible with most 24 volt gas oil or electrical Heating and or Cooling systems It cannot be used with 120 volt heating systems Ask your dealer for other LUXPRO thermostats to control those systems 2 1 HEAT ST...

Page 3: ...zing the tabs into the body Separate the unit from its base plate by pulling the body outward from the bottom NOTE If you are mounting the base to a soft material like plasterboard or if you are using the old mounting holes the screws may not hold Drill a 3 16 in 4 8mm hole at each screw location and insert the plastic anchors provided Then mount the base as described below Route the wires through...

Page 4: ...RING OPTIONS Though not shown here additional second stages may be used where applicable Be sure to enable them properly in the Installer Setup menu W2 is second stage heat E is emergency heat and freeze protection Y2 is second stage cool or second stage heat pump OPTIONAL O or B terminals may be used to power heat ing dampers or changeover valves in any system config uration OPTIONAL C terminal m...

Page 5: ...CAL 2 WIRE HEAT HOOKUP 24 VAC AND MILLIVOLT SYSTEMS XFMR GAS VALVE ACLINE SYSTEMTYPE FURNACE 01 HEATSTAGES 1 02 COMPRESSORSTAGES 0 03 MODES Heat Off 04 HEATFANCONTROL GAS 09 TYPICALINSTALLERSETUP OPTIONALCOMMON ALLOWSUSEOF SYSTEMPOWER 1 NOTES JUMPER PROVIDED SYSTEM COMMON G O Y2 Y1 RC C RH W1 W2 E B TYPICAL 24VAC 3 WIRE HEAT HOOKUP WHERE 3RD WIRE IS FAN WIRE FAN XFMR GAS VALVE ACLINE TYPICALINSTAL...

Page 6: ... 1 03 MODES Ht Off Cl Auto 04 HEATFANCONTROL GAS 09 OPTIONALCOMMON ALLOWSUSEOF SYSTEMPOWER 1 NOTES G O Y2 Y1 RC C RH W1 W2 E B TYPICAL 5 WIRE HOOKUP SINGLE STAGE HEATING AND COOLING COOLING XFMR1 FAN GAS VALVE HEATING XFMR2 ACLINE ACLINE COOL COMMON COMPRESSOR TYPICALINSTALLERSETUP SYSTEMTYPE FURNACE 01 HEATSTAGES 1 02 COMPRESSORSTAGES 1 03 MODES Ht Off Cl Auto 04 HEATFANCONTROL GAS 09 OPTIONALCOM...

Page 7: ...ROVIDED SYSTEMCOMMON TYPICALINSTALLERSETUP SYSTEMTYPE HEATPUMP 01 HEATSTAGES 1 02 COMPRESSORSTAGES 1 03 MODES Ht Off Cl EmHt Auto 04 HEATFANCONTROL ELECTRIC 09 G O Y2 Y1 RC C RH W1 W2 E B USE 2 SEPARATE SINGLE STAGE HEATERS AS A 2 STAGE HEAT SYSTEM SYSTEM XFMR1 HEATER 1 HEATER 2 SYSTEM XFMR2 ACLINE ACLINE SYSTEM1 COMMON SYSTEM2 COMMON OPTIONALCOMMON ALLOWSUSEOF SYSTEMPOWER 1 NOTES TYPICALINSTALLER...

Page 8: ...ERSETUP SYSTEMTYPE FURNACE 01 HEATSTAGES MATCHSYSTEM 02 COMPRESSORSTAGES MATCHSYSTEM 03 MODES Ht Off Cl Auto 04 HEATFANCONTROL ELECTRIC 09 G O Y2 Y1 RC C RH W1 W2 E B TYPICAL MULTI STAGE STAGE HEAT PUMP WITH OPTIONAL AUX AND EMERGENCY HEAT 2 OR 3 STAGES HEAT 2 STAGES COOL FAN SYSTEM XFMR AUX EM HEAT REVERSING VALVE HEAT PUMP STAGE2 COMPRESSOR STAGE1 COMPRESSOR ACLINE JUMPER PROVIDED SYSTEMCOMMON O...

Page 9: ... cooling In this mode an additional stage of Aux Heat may also be activated through the W1 terminal 3 7 1 2 HEAT STAGES Set this to the number of non compressor driven heat stages to use for temperature control by this system 3 7 1 3 COMPRESSOR STAGES COOL HEAT PUMP STAGES Set the number of compressor driven system stages to use for temperature control These stages include all cooling or heat pump...

Page 10: ...perature will be displayed alter nately with time The word OUT will be visible to the right of the temperature while the outside temperature is dis played 3 7 1 17 INTERNAL TEMPERATURE SENSOR This setting enables and disables the thermostats internal temperature sensor It may only be disabled if there are indoor remote sensors present and enabled 3 7 1 18 FUTURE INDOOR REMOTE SENSOR 1 2 3 Used to ...

Page 11: ...s supplied from the factory the following ENERGY STAR approved program will be used for temperature control This program and all other settings maybe restored to their default values via a SOFTWARE RESET Default Daily Temperature Program Period HeatMode CoolMode Morning 6 00AM70 F 6 00AM78 F Day 8 00AM62 F 8 00AM85 F Evening 6 00PM70 F 6 00PM78 F Night 10 00PM62 F 10 00PM82 F 4 1 4 MODES Because o...

Page 12: ...e momentarily press Setup Button Selections can be changed by pressing the UP DOWN button Moving from one menu item to the next and accept ance of changes is done by pressing the NEXT button All changes become effective when the unit exits the User Setup mode The User Setup mode will be exited when the Setup button is pressed again or if no other keys are pressed for 20 seconds 4 2 2 KEYBOARD LOCK...

Page 13: ...ta necessary to predict a Smart recovery time 4 2 10 FILTER LIMIT Your thermostat will warn you that your HVAC systems air filter should be changed after the systems fan has run the number of hours that this setting has been pro grammed for A general rule of thumb is to assume that the fan will run at 1 3 duty cycle A 90 day filter will then be good for 90 24 3 720 hours This is the default value ...

Page 14: ...mer To exit the AIR FILTER mode rotate the dial to another position 4 3 6 ENERGY USAGE Your thermostat records the total number of hours the thermostat has activated heating and cooling with six separate timers They measure Today s cumulative heating time Today s cumulative cooling time Yesterdays cumulative heating time Yesterdays cumulative cooling time Total cumulative heating time Total cumula...

Page 15: ...cating that it is under edit When all the periods for a day have been set the start time for the next weekday will be displayed to begin edit ing the settings for that day Rotate the dial back to RUN to and accept all current values and end the programming session 4 4 2 WEEKDAY FAN PROGRAMMING Programming fan operation is similar to programming the temperature periods and set points Fan periods ar...

Page 16: ...bove the temperature set point Stage one of a cooling system will be deactivated at the value of swing 1 below the temperature set point Stage two of a heating system will be activated at the value of swing 1 swing 2 below the temperature set point The auxiliary heat indicator AUX HT will be visible when a second stage of heat is activated Stage two of cooling will be activated at the value of swi...

Reviews: