Control
Operator controls of the control unit
25
© Lutz-Jesco GmbH 2017
Subject to technical changes.
170502
BA-10010-02-V01
Solenoid-diaphragm dosing pump
MAGDOS LA / LD
Operating instructions
10 Control
10.1 Operator controls of the control unit
Fig. 20: Operator controls of the control unit
No.
Explanation
1
Graphic display
2
Four multifunction keys
Table 20: Operator controls of the control unit
You operate the dosing pump using the four keys below the display. The
system shows the respective functions of the keys at the bottom of the
display.
The
+
and
-
selection keys as well as the and keys have a repeat
function, i.e. if you keep them pressed down, the system automatically
repeats the key function.
The display brightness reduces 45 seconds after your last input.
i
The dosing pump does not have an ON/OFF switch. After being
disconnected from the power supply, the dosing pump starts
in the operating mode and configuration that you selected last.
10.2 Explanation of the menu icons
10.2.1 Level monitoring
Symbol
Meaning
Dosing tank full
Dosing tank at minimum (alert)
Dosing tank empty (main alarm)
Table 21: Explanation of the menu symbols – Level monitoring
10.2.2 Operating modes
Symbol
Meaning
Manual mode
Analogue input (only LA)
Pulse input (only LD)
Table 22: Explanation of the menu symbols – Operating modes
10.2.3 Release input
Symbol
Meaning
Contact open
Contact closed
Table 23: Explanation of the menu symbols – Release input
10.2.4 Release code
Symbol
Meaning
Release code active
Table 24: Explanation of the menu symbols – release code
10.2.5 Activating the password protection
If password protection is activated, the dosing pump is protected against
unauthorized access. You can only perform settings after entry of the
correct password.
WARNING
Caustic burns or other burns through dosing media!
If the password protection is activated, operation of the dosing pump
is blocked. The only way to stop a dosing pump without entry of the
password is via the power supply. In unfavourable cases, if the
password protection has been inadvertently activated or the user has
forgotten the password, the dosing pump cannot be stopped in time.
This can result in injury.
ð
Install an emergency stop switch or integrate the dosing pump into
the plant safety concept.
You can set any password you like from 0001 to 9999.
1.
Press
+
and
-
simultaneously.
4
The dosing pump displays the password protection menu.
Fig. 21:
4 3 2 1
OK - +
Release code
b
a