S p e c i f i c at i o n   S u b m i t ta l

page

Job Name:

Job Number:

Model Numbers:

QS System

QSE-IO

Control Interface

369374a   4   08.07.12

Terminal Locations

4 3 2 1

Relay 1 NC Relay 1 NO Relay 1 & 2 Common Relay 2 NC Relay 2 NO Relay 3 NC Relay 3 NO Relay 3 & 4 Common Relay 4 NC Relay 4 NO Relay 5 NC Relay 5 NO Relay 5 Common Input 1 Input 2 Input 3 Input 4 Input 5 Common

CCI and CCO terminals each  hold one 

28–16 AWG (0.08–1.5 mm

2

) wire

QS Data Link (to control 

units, window treatments, 

and wallstations) 

 

1: Common

 

2: 24 V

 

3: MUX

4: MUX

CCO 1 NC CCO 1 NO 1-2 COM CCO

 2 

NC

CCO 2 NO

CCO

 3 

NC

CCO 3 NO 3-4 COM CCO

 4 

NC

CCO 4 NO

CCO

 5 

NC

CCO 5 NO 5 COM

CCI 1 CCI 2 CCI 3 CCI 4 CCI

 5

COM

QSE-IO

Program 

button

1 2 3 4 5 6 7

DIP switches

LED 1: CCO 1

LED 2: CCO 2

LED 3: CCO 3

LED 4: CCO 4

LED 5: CCO 5

LED 6: Unused

LED 7: Status

Note: LED is ON when CCO NO 

(normally open contact) is closed.

}

Contact Closure Outputs

Contact 

Closure 

Inputs

LED and DIP Switch Locations

QS Link Wire Sizes (check compatibility in your area)

QS Link Wiring Length

Wire Gauge

Lutron Cable Part Number

< 500 ft (153 m)

Power (terminals 1 and 2)
1 pair 18 AWG (1.0 mm

2

)

GRX-CBL-346S (non-plenum)
GRX-PCBL-346S (plenum)

Data (terminals 3 and 4)
1 twisted, shielded pair 22 AWG (0.5 mm

2

)

500 – 2000 ft
(153 – 610 m)

Power (terminals 1 and 2)
1 pair 12 AWG (4.0 mm

2

)

GRX-CBL-46L (non-plenum)
GRX-PCBL-46L (plenum)

Data (terminals 3 and 4)
1 twisted, shielded pair 22 AWG (0.5 mm

2

)

Summary of Contents for QSE-IO

Page 1: ...ure I O Provides five inputs and five dry contact closure outputs Provides both normally open NO and normally closed NC contacts May be programmed to control or be controlled by any combination of GRA...

Page 2: ...rovide status feedback to other equipment Using the inputs contact closures in other equipment can operate Sivoia QS window treatments to Open or close Raise lower or stop Select one of three adjustab...

Page 3: ...terminal will accept up to two 18 AWG 1 0 mm2 wires Connect wiring as shown in the Wiring Diagram Choose from the following mounting methods 1 Direct Wall Mounting Mount the control interface directly...

Page 4: ...CCO 4 NO CCO 5 NC CCO 5 NO 5 COM CCI 1 CCI 2 CCI 3 CCI 4 CCI 5 COM QSE IO Program button 1 2 3 4 5 6 7 DIP switches LED 1 CCO 1 LED 2 CCO 2 LED 3 CCO 3 LED 4 CCO 4 LED 5 CCO 5 LED 6 Unused LED 7 Stat...

Page 5: ...wiring Follow all local and national electrical codes when installing IEC PELV NEC Class 2 wiring with line voltage mains wiring Each terminal accepts up to two 18 AWG 1 0 mm wires Total length of con...

Page 6: ...ls Occupancy Sensors Hot Neutral Red 20 24 V Blue signal Black common Black White Red Red 120 277 347 V 60 Hz 230 V 50 60 Hz CCI1 CCI2 CCI3 CCI4 CCI5 COM Note Occupancy sensors will not participate in...

Page 7: ...Hot Neutral 120 277 347 V 60 Hz 230 V 50 60 Hz Occupancy Sensors Power Pack Neutral 120 277 347 V 60 Hz 230 V 50 60 Hz Hot Occupancy Sensor Power Pack Neutral 120 277 347 V 60 Hz 230 V 50 60 Hz Hot B...

Page 8: ...up raise lower Raise Stop Group 1 Lower Stop Group 1 Raise Stop Group 2 Lower Stop Group 2 Momentary Momentary Shade input toggle stop if moving open stop close stop Toggle Group 1 Toggle Group 2 Togg...

Page 9: ...acy do not disturb Doorbell Start end afterhours mode Toggle Scene 1 Off 1 3 Maintained or Momentary 4 5 Maintained Maintained except 3 Hotel configuration 2 Service make up room Privacy do not distur...