S p e c i f i c at i o n   S u b m i t ta l

page

Job Name:

Job Number:

Model Numbers:

QS System

QSE-IO

Control Interface

369374a   2   08.07.12

Specifications

Power

• IEC PELV/NEC

®

 Class 2

• Operating voltage: 12–24 V   100 mA

Regulatory Approvals

• UL Listed

• cUL Listed

• CE compliant

QS Link Limits

• The QS wired communications link is limited to 

100 devices and 100 zones. Each QSE-IO control 

interface counts as 1 device and 2 zones.

• Each QSE-IO control interface consumes 3 power 

draw units (PDU) on the QS link. Refer to the QS 

Link Power Draw Units Specification Submittal 

(Lutron PN 369405, at www.lutron.com) for more 

information.

• The maximum wiring length for the QS link is 

 

2000 ft (610 m).

Environment

• 32 to 104 °F (0 to 40 °C). 

• Relative humidity less than 90% non-condensing.

Functionality and Operating Modes

• Using the inputs, contact closures in other 

equipment can operate control units to:

 

– Select scenes

  – Adjust scenes to reflect status of movable walls

 

–  Toggle any combination of zones in the system 

between Off and a configurable preset value

  –  Turn lights on or off and/or move shades based on 

room occupancy

  –  Perform special functions such as sequencing, 

panic, control lockout, or timeclock disable

• Using the outputs, scene and/or zone changes in 

control units can:

 

– Trigger outputs to control other equipment.

 

– Provide status feedback to other equipment.

• Using the inputs, contact closures in other 

equipment can operate Sivoia

®

 QS window 

treatments to:

 

– Open or close.

  – Raise, lower, or stop.

 

– Select one of three adjustable presets.

• Using the outputs, key presses on QS window 

treatment keypads or GRAFIK Eye

®

 QS window 

treatment buttons can:

 

–  Trigger outputs to other motorized window treatment 

equipment.

• Scene selection 

 

• Occupancy sensor

• Zone toggle   

 

• Shade input

• Special functions 

 

• Shade output

• Partitioning

Five Input Terminals

• Accept maintained inputs and momentary inputs with 

40 msec minimum pulse times.

• Off-state leakage current must be less than 100 µA.

• Open circuit voltage: 24 V  maximum.

• Inputs must be dry contact closure, solid state, open 

collector, or active-low (NPN)/active high (PNP) output.

  -  Open collector NPN or active-low on-state voltage 

must be less than 2 V  and sink 3.0 mA.

  -  Open collector PNP or active-high on-state voltage 

must be greater than 12 V  and source 3.0 mA.

Five Output Terminals

• Provide selectable maintained or momentary 

(

1

-second) outputs (IEC PELV/NEC

®

 Class 2 rated 

only).

• The QSE-IO is not rated to control unclamped, 

inductive loads. Inductive loads include, but are not 

limited to, relays, solenoids, and motors. To control 

these types of equipment, a flyback diode must be 

used (DC voltages only). See "Terminal Locations".

• Output relays are non-latching (if relays are closed and 

power is lost, relays will open).

Status LEDs

• Five Status LEDs light when associated output is 

active (on).

Summary of Contents for QSE-IO

Page 1: ...ure I O Provides five inputs and five dry contact closure outputs Provides both normally open NO and normally closed NC contacts May be programmed to control or be controlled by any combination of GRA...

Page 2: ...rovide status feedback to other equipment Using the inputs contact closures in other equipment can operate Sivoia QS window treatments to Open or close Raise lower or stop Select one of three adjustab...

Page 3: ...terminal will accept up to two 18 AWG 1 0 mm2 wires Connect wiring as shown in the Wiring Diagram Choose from the following mounting methods 1 Direct Wall Mounting Mount the control interface directly...

Page 4: ...CCO 4 NO CCO 5 NC CCO 5 NO 5 COM CCI 1 CCI 2 CCI 3 CCI 4 CCI 5 COM QSE IO Program button 1 2 3 4 5 6 7 DIP switches LED 1 CCO 1 LED 2 CCO 2 LED 3 CCO 3 LED 4 CCO 4 LED 5 CCO 5 LED 6 Unused LED 7 Stat...

Page 5: ...wiring Follow all local and national electrical codes when installing IEC PELV NEC Class 2 wiring with line voltage mains wiring Each terminal accepts up to two 18 AWG 1 0 mm wires Total length of con...

Page 6: ...ls Occupancy Sensors Hot Neutral Red 20 24 V Blue signal Black common Black White Red Red 120 277 347 V 60 Hz 230 V 50 60 Hz CCI1 CCI2 CCI3 CCI4 CCI5 COM Note Occupancy sensors will not participate in...

Page 7: ...Hot Neutral 120 277 347 V 60 Hz 230 V 50 60 Hz Occupancy Sensors Power Pack Neutral 120 277 347 V 60 Hz 230 V 50 60 Hz Hot Occupancy Sensor Power Pack Neutral 120 277 347 V 60 Hz 230 V 50 60 Hz Hot B...

Page 8: ...up raise lower Raise Stop Group 1 Lower Stop Group 1 Raise Stop Group 2 Lower Stop Group 2 Momentary Momentary Shade input toggle stop if moving open stop close stop Toggle Group 1 Toggle Group 2 Togg...

Page 9: ...acy do not disturb Doorbell Start end afterhours mode Toggle Scene 1 Off 1 3 Maintained or Momentary 4 5 Maintained Maintained except 3 Hotel configuration 2 Service make up room Privacy do not distur...

Reviews: