S p e c i f i c at i o n   S u b m i t ta l

page

Job Name:

Job Number:

Model Numbers:

QS System

QSE-IO

Control Interface

369374a   1   08.07.12

QSE-IO Control Interface

The QSE-IO contact closure interface provides 

integration with third-party equipment requiring 

contact closure input/output, including occupancy 

and vacancy sensors; motorized projection screens, 

skylights, and window shades; AV equipment; security 

systems; movable partition walls; and timeclocks. One 

QSE-IO interface provides five (5) dry contact closure 

outputs.

For complete functionality, programming 

instructions, and detailed DIP switch settings, see 

the QSE-IO Programming Guide, PN 040391,  

at www.lutron.com/qs.

Key Features

• Integrates a GRAFIK Eye

®

 QS control system 

with equipment that has contact-closure I/O

• Provides five inputs and five dry contact closure 

outputs.

• Provides both normally open (NO) and normally closed 

(NC) contacts.

• May be programmed to control or be controlled by 

any combination of GRAFIK Eye

®

 QS control units or 

control any combination of Sivoia

®

 QS window 

treatments on the QS link.

Compatible Components

The following devices are compatible with the QS link. 

For more information on each, refer to 

 

www.lutron.com/qs.

• GRAFIK Eye

®

 QS control units

• seeTouch

®

 QS wallstations

• Sivoia

®

 QS shades

• QS Interfaces (contact closure, Ethernet/RS232)

• Quantum

®

 system

• Energi Savr Node

TM

 units

• QS Sensor Module

• QS Keyswitch

For Programming, see the  

QSE-IO Control Interface Programming Guide: 

PN 040391 at www.lutron.com/qs

Requirements

• QS Link Power Supply, such as a: 

  - GRAFIK Eye

®

 QS

  - QS Link power supply, such as the QSPS-P1-1-50 

  - Energi Savr Node

TM

 QS

  - Quantum

® 

light management hub

• QS Communication Link (IEC PELV/NEC

®

 Class 2)

 

(see QS Link Wire Sizes table)

 

Summary of Contents for QSE-IO

Page 1: ...ure I O Provides five inputs and five dry contact closure outputs Provides both normally open NO and normally closed NC contacts May be programmed to control or be controlled by any combination of GRA...

Page 2: ...rovide status feedback to other equipment Using the inputs contact closures in other equipment can operate Sivoia QS window treatments to Open or close Raise lower or stop Select one of three adjustab...

Page 3: ...terminal will accept up to two 18 AWG 1 0 mm2 wires Connect wiring as shown in the Wiring Diagram Choose from the following mounting methods 1 Direct Wall Mounting Mount the control interface directly...

Page 4: ...CCO 4 NO CCO 5 NC CCO 5 NO 5 COM CCI 1 CCI 2 CCI 3 CCI 4 CCI 5 COM QSE IO Program button 1 2 3 4 5 6 7 DIP switches LED 1 CCO 1 LED 2 CCO 2 LED 3 CCO 3 LED 4 CCO 4 LED 5 CCO 5 LED 6 Unused LED 7 Stat...

Page 5: ...wiring Follow all local and national electrical codes when installing IEC PELV NEC Class 2 wiring with line voltage mains wiring Each terminal accepts up to two 18 AWG 1 0 mm wires Total length of con...

Page 6: ...ls Occupancy Sensors Hot Neutral Red 20 24 V Blue signal Black common Black White Red Red 120 277 347 V 60 Hz 230 V 50 60 Hz CCI1 CCI2 CCI3 CCI4 CCI5 COM Note Occupancy sensors will not participate in...

Page 7: ...Hot Neutral 120 277 347 V 60 Hz 230 V 50 60 Hz Occupancy Sensors Power Pack Neutral 120 277 347 V 60 Hz 230 V 50 60 Hz Hot Occupancy Sensor Power Pack Neutral 120 277 347 V 60 Hz 230 V 50 60 Hz Hot B...

Page 8: ...up raise lower Raise Stop Group 1 Lower Stop Group 1 Raise Stop Group 2 Lower Stop Group 2 Momentary Momentary Shade input toggle stop if moving open stop close stop Toggle Group 1 Toggle Group 2 Togg...

Page 9: ...acy do not disturb Doorbell Start end afterhours mode Toggle Scene 1 Off 1 3 Maintained or Momentary 4 5 Maintained Maintained except 3 Hotel configuration 2 Service make up room Privacy do not distur...

Reviews: