Symptom
Lights do not come on.
Lights turn on/off
unexpectedly.
Troubleshooting Guide
PB
ELVI
FDBI
4 1/2 in. (11 cm) MINIMUM
4 1/2 in. (11 cm) MINIMUM
Panel Mounting
■
The enclosure must be in accordance with all local and national electrical
codes.
■
Lutron does not recommend using a door to enclose the front of a panel, since
this restricts airflow to the
GRAFIK Eye
Control Units and Interfaces.
■
If mounting multiple Control Units or Interfaces in an enclosure:
1.
Ambient temperature within an enclosure
must remain between
32°—104° F (0°—40° C)
.
2.
If not mounting in a metal enclosure, all units
must
be mounted in a
wallbox.
■
To improve heat dissipation of Power Interfaces, remove the faceplate from the
unit.
GRAFIK Eye
Control Units and Interface Units dissipate heat when
operating. Obstructing these units can cause malfunction to both the
Control Unit and the Interface if ambient temperature does not remain
between 32°—104° F (0°—40° C).
Causes
Power is off
Miswire
Bulb(s)/lamp(s) burned out
GRAFIK Eye
3000 Control
Unit
Interface is overloaded
Load Type
GRAFIK Eye
3000 Control
Unit
Solution
Restore power to the
PB/ELVI/FDBI
.
Restore power to the Control Unit.
Confirm wiring per wiring diagrams.
Replace bulb(s)/lamp(s).
Refer to troubleshooting section of
GRAFIK Eye
Control Unit Installer’s
Guide.
Check for excess load, proper mounting, and adequate air convection.
Allow unit to cool.
Confirm that the load type being switched/dimmed is compatible with
the
PB/ELVI/FDBI
.
Refer to the troubleshooting section of
GRAFIK Eye
Control Unit
Installation Guide.
7
030-739 8/1/02 2:22 PM Page 7