Single-Feed Wiring for PB/ELVI
230V
The
PB/ELVI
may be on the same circuit as the Control
Unit
only if
the total load does not exceed the rating of
the breaker.
HOT/LIVE
ZONE
NEUTRAL
4
3
2
1
USA: Class 2
IEC: PEL
V
DO NOT USE
H/L
N
HOT/LIVE
EAR
TH/GROUND
ZONE OUT
ZONE IN
NEUTRAL N
H/L
N
HOT/LIVE
ZONE
NEUTRAL
4
3
2
1
USA: Class 2
IEC: PEL
V
DO NOT USE
H/L
N
HOT/LIVE
EAR
TH/GROUND
ZONE OUT
ZONE IN
NEUTRAL N
Dual-Feed Wiring for PB/ELVI
230V
The load breaker/MCB can be on a different phase than the control
breaker/MCB
.
LOAD NEUTRAL
LOAD NEUTRAL
4
■
When using a
PB
to control a Lutron
Tu-Wire
dimming bal-
last, the associated zone on the GRAFIK Eye
®
3000 Series
Control Unit must be set to the
Tu-Wire
load type. Please
see the
GRAFIK Eye
3000 Series Installer’s Guide for more
details.
■
The
PB 230V
must not be used with
Tu-Wire
ballasts
because the
Tu-Wire
load type is not available on 230V CE
models of the
GRAFIK Eye
Control Unit.
LOAD
LOAD
Tu-Wire
Dimming Ballast
HOT/LIVE
ZONE
NEUTRAL
4
3
2
1
USA: Class 2
IEC: PEL
V
DO NOT USE
H/L
N
HOT/LIVE
EAR
TH/GROUND
ZONE IN
NEUTRAL N
H/L
N
ZONE OUT
DO NOT USE
HOT/LIVE
EAR
TH/GROUND
ZONE IN
NEUTRAL N
ZONE OUT
H/L
N
Dual-Feed Wiring for Two (2) PB/ELVI Interfaces on One
Zone - 120V and 220-240V
The load breaker/MCB can be on a different phase than the control
breaker/MCB.
LOAD NEUTRAL
LOAD
LOAD NEUTRAL
LOAD
030-739 8/1/02 2:22 PM Page 4