background image

Application Note 4 Reliable Operation of LSProbe 1.2 Field Probes

4 Fiber Connector Cleaning Instructions

There are two methods for cleaning fiber-optic connectors: dry cleaning and wet-to-dry
cleaning. Dry cleaning is suitable for minor contamination. Wet-to-dry cleaning is suitable
for severe contamination caused by skin oils, skin flakes, dust particles, etc. Therefore,
LUMILOOP recommends the wet-to-dry cleaning method, detailed in this section.

Regardless of the method, the following sequence of steps should be observed:

1. Inspect the connector end-faces for contamination using a fiber microscope. Always

ensure that the Computer Interface is switched off and cannot be turned on inad-
vertently during fiber inspection. Note that the focal plane for for E2000 and ST/FC
connectors differ and must thus be adjusted.

2. Clean the connector end-face.
3. Reinspect the connector end-face, go back to step two, if there is any contamination.
4. Connect the fiber connectors, do not put the connector down. Do not apply dust caps

between cleaning and connecting.

LUMILOOP’s cleaning kit shown in Fig. includes:

• a 400x optical fiber microscope,
• two packs lint-free cassette cleaner wipes

(Chemtronics, Foccus QbE Pleaning Platform, part no. QBE),

• a fiber-optic cleaning pen

(Chemtronics, Foccus Fiber-Wash Precision Cleaner, part no. FW2170)

• an unfilled isopropyl alcohol (IPA) pipette/bottle,
• spare FC/ST dust caps and two E2000 locking caps.

Figure 7: LUMILOOP fiber-optic cleaning kit

Fig. shows how to clean the fiber connectr end-faces of ST/FC and E2000 connectors.

November 23, 2020

Page 6/9

Summary of Contents for LSProbe 1.2

Page 1: ... Probes LUMILOOP GmbH support lumiloop de November 23 2020 Contents 1 Introduction 2 2 Fiber Failure Mechanism 3 3 Sacrificial Cable Kits for LSProbe 1 2 Field Probe Systems 4 4 Fiber Connector Cleaning Instructions 6 5 Replacing Sacrificial Cables 8 6 Fiber Handling Recommendations 9 ...

Page 2: ...ectors of Field Probe Computer Interface and extension cable They provide two defined and convenient points for disconnecting the Field Probe from the Computer Interface using the E2000 con nectors of the sacrificial cable kits Due to the integrated shutters burn in defects at the E2000 connectors are significantly less frequent However in the case of a burn in defect at an E2000 connector the sacrifi...

Page 3: ...C fiber connector pair which carries the optical power for the field probe suffered a burn in defect a Field Probe FC before after cleaning b Field Probe ST before after cleaning c Extension cable FC before after cleaning d Extension cable ST before after cleaning Figure 2 Example for contaminated FC power and ST data fiber connectors As suggested by the name burn in defects are caused by excessive he...

Page 4: ...tors are significantly less prone to contamination and thus to burn in defects because of their integrated automatic shutters Consequently E2000 connectors may be plugged without cleaning consciously accepting that contamination will accumulate with each plugging cycle and lead to a burn in defect eventually Once a burn in defect has occurred the complete sacrificial cable kit must be replaced in cl...

Page 5: ...al link should always be disconnected using E2000 connec tors Do not disconnect any FC ST connectors unless absolutely necessary When plugging FC ST connectors make sure to observe the cleaning instructions in Section 4 FC ST Coupler Field Probe Use E2000 Connectors Two Sacrificial Cable Kits incl E2000 Connectors and Coupler E2000 Fiber Coupler FC ST Fiber Coupler FC ST Fiber Coupler E2000 Fiber ...

Page 6: ...n inad vertently during fiber inspection Note that the focal plane for for E2000 and ST FC connectors differ and must thus be adjusted 2 Clean the connector end face 3 Reinspect the connector end face go back to step two if there is any contamination 4 Connect the fiber connectors do not put the connector down Do not apply dust caps between cleaning and connecting LUMILOOP s cleaning kit shown in Fig...

Page 7: ...rm Step 3 Moisten one corner of the cleaning wipe us ing the fiber optic cleaning pen or IPA pipette Step 4 Press the fiber end face flatly against the moist area of the wipe and slide it into the dry area of the wipe Step 5 Only for E2000 connectors remove the E2000 locking cap re clip the connector pair after cleaning both connectors Figure 8 FC ST E2000 fiber optic connector wet to dry cleaning met...

Page 8: ...or and connect it to the coupler d Repeat steps a through c for the ST connectors 4 Repeat step three for the second end of the sacrificial cable kit 5 Consider ordering a new spare sacrificial cable kit Fixing burned in FC ST connectors In case of a burn in defect at a ST or FC connector due to improper handling replacement is required There are three destinct cases In case of a burn in defect at a...

Page 9: ...g Avoid tensile strain on fiber optic cables Fiber optic cables shall not carry the weight of the connectors Always use two sacrificial cable kits one between Computer Interface and extension cable and one between extension cable and Field Probe Always disconnect the optical fiber connection using the E2000 connectors of the sacrificial cable kits Do not open any FC ST fiber connectors unless absolutel...

Reviews: