2.
Street Lamp
Function
When the load is set to Dusk to Dawn or Evening mode, the
voltage and the
Day/Night
delay t
can be set b the mobile phone APP, RS485 or
Wechat APP
, and the load can be
turned on or off by the test function during the day charging process.
2.1
Day/Night threshold
voltage
The controller recognizes day and night based on the solar array open circuit voltage.
This day/night threshold
voltage
can be modified according to local light conditions and the solar array
used.
Day/Night threshold
setting range: 3.0~20.0V(Lithium, default: 8.0V)
Day/Night threshold
setting range: 3.0~10/6.0~20V(Liquid/Gel/AGM,Default: 8/16V)
2.2 Day/Night delay time
In the evening, when the solar array open circuit voltage reaches the setting day/night
detect voltage
, you
can adjust the day/night delay time to make the load turn on a little bit later.
Day
/
Night delay time setting range: 0~30min(Default
:
0min)
2.3
Test Function
When the controller is working in
Dusk to Dawn or Evening
mode, press the
MENU
key for
3
s to turn on
the load. Press the
MENU
key again or the load turns off automatically after 1 minute.
If the controller is operating in
a
lways on mode, the test function does not work.
Day/Night threshold
ime
y
1.If the controller turns off the load due to low voltage protection
、
overcurrent
protection
、
short-circuit protection or over temperature protection, the load will turn on
automatically
when the controller recovers from protection state.
2.Please note: Pushing the MENU button can still activate the function of the key, even
during of the above four kinds protection states.
3.User-defind Mode
①
MENU
shortly.
②
The default switching state of the load in manual mode can be changed by mobile APP
Wechat APP. At the same time, the output to the load can be turned on or off.
If the load mode is selected
"
USE
"
, then you can switch on and off the load output manually by pressing
, RS485 or
Battery voltage is abnormal
at start-up
Faults
Reason
Troubleshooting
Battery voltage is too low
Reduce the load, the controller will resume work
after 1minute.
After the temperature decreases, the controller will
work normally.
Battery voltage is too high
Short Circuit
Over Current
Over temperature
Switch off all loads, remove short circuit, load will be
reconnected after 1 minute automatically
Charge or discharge the battery so that the battery
voltage is within the normal operating range(8.5~15.5V
or 20~30V).
Check if other sources overcharge the battery or battery
parameter is set correctly. If not, controller is damaged.
Load will be reconnected when battery is recharged.
7
.
1
T
rouble shooting
7, Troubleshooting,
and maintenance
Protections
14