P30P-09A 45 User's manual
Fig. 18 Conditional
archiving
types
A
r_L - Archiving lower limit → OverLoAr → Register 7608
Ar_H – Archiving upper limit → OverHiAr → Register 7609
Example:
Transducer configured for monitoring voltage, current, active power, THD U, THD I.
Conditional archiving of five displayed values triggered by active power coefficient level – if PF falls
below 0,9, transducer archives the values displayed every 10 seconds:
Table 22
Figure
description
Register no.
Parameter
symbol in the
menu
Register
value
Parameter value symbol
in the menu
4064
Arch.Val
12295
U, I, P, THD U,
THD I
4065
Param.Ar
5
PF
4066
Ar. Mode
1
n-off
Ar_L
7608
OverLoAr
0.9
0.9
Ar_H
7609
OverHiAr
0.9
0.9
4067
Ar. Time
10
10
4068
Ar.Erase
0
No
4069
Rec.ToSD
0
No
7614
Param.SD
10
95.0
5.8.4 Memory card or internal memory file system (optional)
Transducers P30 in P30P-XX1XXXXXXX versions use memory card compatible with SD and
SDHC standard. Transducers P30 in P30P-XX2XXXXXXX versions are equipped with file system
internal memory – memory size 8GB. It is compatible with both FAT and FA32 file systems. If the