EN
23
4. TECHNICAL DATA
Measuring Ranges.
Table 1
Kind of inputs
Indication range
Class
Number of pulses
Cntr1, Cntr2
-19 999..99 999
1)
±1 pulse
Frequency <10 kHz
0.05...99 999 Hz
2)
0.01
Frequency >10 kHz
1...99 999 kHz
0.01
Rotational speed
0.05...99 999 [Rev/min]
1)
0.01
Period t < 10s
0.0001...11 [s]
1)
0.01
Period t > 10s
0.0001...3600 [s]
1)
0.01
Worktime counter
0...99 999 [h]
0.5 sec/24 hours
Current time
00.00...23.59
0.5 sec/24 hours
Encoder
-19 999...99 999
1)
-
1)
maximal frequency of input signal with filter :2 kHz ; without filter for Cntr1 input
10 kHz, for Cntr2 input 8 kHz (table 8).
2)
maximal frequency of input signal: 100 kHz; measuring range without filter:10
kHz,
with filter 100Hz.
3)
maximal frequency of input signal: 1MHz,
Relay outputs
:
- relays, NOC voltageless contacts; load capacity 250 V~/0.5A~
- relays, switched voltageless contacts; load capacity 250 V~/0.5A~
Analog outputs (option):
- rogrammable, current 0/4..20 mA; load resistance
£
500
W
- programmable, voltage 0...10 V; load resistance
³
500
W
Output of auxiliary supply
: 24 V d.c./30 mA
Alarm output OC (option)
: output of OC type, passive npn,
30 V d.c./30 mA.
Input signals
: voltage 5...36 V d.c., galvanically separated
Duration of control signals
: higher than 10 ms
Serial interface RS 485
: address: 1...247; mode: 8N2, 8E1, 8O1, 8N1
baud rate: 4.8, 9.6, 19.2, 38.4, 57.6, 115.2 [kb/s].; maximal response
time 100 ms