background image

SAFETY INSTRUCTION

1. Safety instruction

Please, observe the following instructions:

• 

The router must be used in compliance with all applicable international and national laws and 

in   compliance   with   any   special   restrictions   regulating   the   utilization   of   the   router   in 
prescribed applications and environments. 

• 

To   prevent   possible   injury   to   health   and   damage   to   appliances   and   to   ensure   that   all 

the relevant  provisions   have   been   complied   with,   use   only   the   original   accessories. 
Unauthorised modifications or utilization of accessories that have not been approved may 
result in damage to the router and in a breach of applicable regulations.  Unauthorized 
modifications or utilization of accessories that have not been approved may result in the 
termination of the validity of the guarantee.

• 

The router can not be opened. 

• 

Caution!

 The SIM card could be swallowed by small children.

• 

It must not be exceeded by the maximum voltage 30V DC power connector on the router.

• 

Do not expose the  router to extreme ambient  conditions.  Protect  the router against  dust, 

moisture and high temperature.

• 

The router should not be used at petrol stations of  flammable  and explosive  materials. We 

remind the users of the duty to observe the restrictions concerning the utilization of radio 
devices at petrol stations, in chemical plants, or in the course of blasting works in which 
explosives are used.

• 

Switch   off   the  router   when   travelling   by   plane.   Utilization   of the router   in   a   plane   may 

endanger the operation of the plane or interfere with the mobile telephone network, and 
may be unlawful. Failure to observe these instructions may result in the suspension or 
cancellation   of   telephone   services   for the respective   client,   or,   it   may   result   in   legal 
sanctions; it may also result in both eventualities.

• 

When using the  router in the close proximity of personal medical devices, such as cardiac 

pacemakers or hearing aids, you must proceed with heightened caution.

• 

If it is in the proximity of TV sets, radio receivers and personal computers, the telephone may 

cause interference.

• 

It is recommended that you should create an appropriate copy or backup of all the important 

settings that are stored in the memory of the device.

1

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

  

LUCOM GmbH * Ansbacher Str. 2a * 90513 Zirndorf * Tel. 09127/59 460-10 * Fax. 09127/59 460-20 * www.lucom.de 

 

  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

  

LUCOM GmbH * Ansbacher Str. 2a * 90513 Zirndorf * Tel. 09127/59 460-10 * Fax. 09127/59 460-20 * www.lucom.de 

 

  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

  

LUCOM GmbH * Ansbacher Str. 2a * 90513 Zirndorf * Tel. 09127/59 460-10 * Fax. 09127/59 460-20 * www.lucom.de 

 

  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

  

LUCOM GmbH * Ansbacher Str. 2a * 90513 Zirndorf * Tel. 09127/59 460-10 * Fax. 09127/59 460-20 * www.lucom.de 

 

  

Summary of Contents for UR5 v2 SL

Page 1: ...UMTS router UR5 v2 and UR5 v2 SL USER S GUIDE LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 59 460 20 www lucom de ...

Page 2: ...ge by sending an email to info conel cz Conel s r o Sokolska 71 562 04 Usti nad Orlici Czech Republic Manual issued in CZ 2 19 2013 ii Declared quality system ISO 9001 LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 59 460 20 www lucom de LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 59 460 20 www lucom de LUCOM GmbH Ansbacher Str 2a 90513 Zirndo...

Page 3: ...ing the router before first use 20 6 2 Start router 21 6 3 Router configuration 21 6 3 1 Configuration over web browser 21 6 3 2 Configuration over Telnet 21 7 Technical parameters 22 7 1 Technical parameters of router 22 7 2 Technical parameters of module 22 7 3 Technical parameters of processor 23 7 4 Technical parameters of I O port 23 7 5 Technical parameters of expansion port 23 8 Recommended...

Page 4: ... antenna 13 Fig 22 Connecting the antenna 13 Fig 23 Ejected the SIM card 14 Fig 24 Ethernet connector 14 Fig 25 Connection Ethernet cable 15 Fig 26 Example of router connection 15 Fig 27 Connection PORT1 cable 16 Fig 28 Connection PORT2 cable 16 Fig 29 USB connector 17 Fig 30 Connection PLC to the router 17 Fig 31 Connection flash memory to the router 17 Fig 32 I O connector 18 Fig 33 Connection I...

Page 5: ...I O port 18 Table 12 Description of reset and restart router 19 Table 13 Technical parameters of router 22 Table 14 Technical parameters of module 22 Table 15 Technical parameters of processor 23 Table 16 Technical parameters of I O 23 v LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 59 460 20 www lucom de LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax...

Page 6: ...he duty to observe the restrictions concerning the utilization of radio devices at petrol stations in chemical plants or in the course of blasting works in which explosives are used Switch off the router when travelling by plane Utilization of the router in a plane may endanger the operation of the plane or interfere with the mobile telephone network and may be unlawful Failure to observe these in...

Page 7: ...an be recycled At the end of it s life this product MUST NOT be mixed with other commercial waste for disposal Check the terms and conditions of your supplier for disposal information 2 LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 59 460 20 www lucom de LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 59 460 20 www lucom de LUCOM GmbH Ansbacher S...

Page 8: ...es detail statistics about the 3G router activities signal strength detailed log etc Cellular router supports functions DHCP NAT NAT T DynDNS NTP VRRP control by SMS and many other functions Other diagnostic functions ensuring continuous communication include automatic inspection of PPP connection offering an automatic restart feature in case of connection losses or hardware watchdog which monitor...

Page 9: ...r WMBUS Separation columns for mounting expansion boards are included Module can be connected only as follows PORT1 RS232 RS485 422 ETHERNET M BUS CNT XC SW together with PORT2 PORT2 RS232 RS485 422 M BUS XC SW together with PORT1 WIFI WMBUS Table 1 Expansion port possibilities 4 LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 59 460 20 www lucom de LUCOM GmbH Ansbacher St...

Page 10: ...n UR5 v2B SL UR 5 v2 Basic version in the metal box UR5 v2F UR 5 v2 Full version UR5 v2F SL UR 5 v2 Full version in the metal box Table 3 Delivery identification Fig 6 Label UR5 v2B Fig 7 Label UR5 v2F 5 LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 59 460 20 www lucom de LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 59 460 20 www lucom de LUCO...

Page 11: ...ional MBUS port PORT1 a PORT2 UR5 v2F MBUS set Version with optional CNT port PORT1 UR5 v2F CNT set Version with optional XC SW port PORT1 PORT2 UR5 v2F SWITCH set Version with optional WIFI port PORT2 UR5 v2F WIFI set Version with optional WMBUS port PORT2 UR5 v2F WMBUS set Table 5 Ordering code of full version Second optional port is written after first optional port in the ordering code Example...

Page 12: ...bacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 59 460 20 www lucom de LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 59 460 20 www lucom de LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 59 460 20 www lucom de LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 59 460 20 www lucom de ...

Page 13: ...00 A1 04 specification it is necessary to observe next assembly of the router to the switch board for whip antennas we recommend to observe a distance of 6 cm from cables and metal surfaces on every side according to the next picture due to the elimination of interference while using an external antenna except for the switch board it is necessary to fit a lightening conductor before mounting a rou...

Page 14: ... routing for SL version sufficient space must be left before individual connectors for handling of cables Fig 14 Space in front connectors Fig 15 Space in front connectors SL version for correct function of the router we recommend to use in the switch board earth bonding distribution frame for grounding of power supply of router data cables and antenna 9 LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf ...

Page 15: ...ion the devices with the router USB supports equipments with PL 2303 and FTDI USB RS232 converter I O 3 pin Connector for connection of the binary input and output SIM1 Holder for first SIM card SIM2 Holder for second SIM card only FULL version Table 6 Front panel description Fig 16 Front panel UR5 v2F Fig 17 Front panel UR5 v2F SL 10 LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 ...

Page 16: ...ary output active IN Green On Binary input active ETH Green On Off Selected 100 Mbit s Selected 10 Mbit s ETH Yellow On Blinking Off The network cable is connected Data transmission The network cable is not connected PORT Green Description by port viz Technical specification of expansion port PORT Yellow Description by port viz Technical specification of expansion port SIM1 Yellow On SIM card 1 is...

Page 17: ...sary that the power source is able to supply a peak current of 1 A Connector on the power cable connects into the power connector on the router head and tightens locking screws see figure bellow Fig 19 Connection of power supply connector Circuit example Fig 20 Connection of power supply The positive pole VCC is marked by a red socket on the power 12 LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel ...

Page 18: ...o screw the antenna connector SMA to SMA connector on the router head see figure below Fig 22 Connecting the antenna 13 LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 59 460 20 www lucom de LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 59 460 20 www lucom de LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 59 460 20 www l...

Page 19: ...umber Signal mark Description Data flow direction 1 TXD Transmit Data positive pole Input Output 2 TXD Transmit Data negative pole Input Output 3 RXD Receive Data positive pole Input Output 4 5 6 RXD Receive Data negative pole Input Output 7 8 Table 9 Connection of Ethernet connector Fig 24 Ethernet connector ATTENTION Port ETH is not POE Power Over Ethernet compatible 14 LUCOM GmbH Ansbacher Str ...

Page 20: ...ion 15 LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 59 460 20 www lucom de LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 59 460 20 www lucom de LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 59 460 20 www lucom de LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 59 460 20 www lucom de ...

Page 21: ...ace PORT2 RS232 RS485 422 M BUS XC SW together with PORT1 WIFI WMBUS PORT2 is fitted only in the FULL version of the router Description connection and examples of optional connection ports can be found in separate manuals expansion ports PORT2 cable plug into the RJ45 connector labeled as ETH see figure bellow Fig 28 Connection PORT2 cable 16 LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59...

Page 22: ...ing devices with serial interface to the USB router Fig 30 Connection PLC to the router Example of connecting of USB flash disk to the USB router Fig 31 Connection flash memory to the router 17 LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 59 460 20 www lucom de LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 59 460 20 www lucom de LUCOM GmbH Ans...

Page 23: ...pplied by the binary input is 3 mA Connector I O cable connect into the I O connector on the router head and tighten locking screws See bellow picture Fig 33 Connection I O cable Circuit example of a binary input or output equipment with router Fig 34 Connection input and output of router 18 LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 59 460 20 www lucom de LUCOM GmbH ...

Page 24: ...nel After press button RST it is restoration of default configuration and reboot green LED will be on For pressing the RST button could be used a narrow screwdriver Fig 35 Router reset We recommend to backup your router configuration see Configuration manual because after reset router set configuration to the initial state 19 LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127...

Page 25: ...power supply In operation the router must be connected to the antenna otherwise damage to the router Fig 36 Router connection 20 LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 59 460 20 www lucom de LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 59 460 20 www lucom de LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 59 460...

Page 26: ...router into the web browser The default IP address of the router is 192 168 1 1 Configuration may be performed only by the user root with initial password root A detailed description of the router settings via the Web interface can be found in the configuration manual 6 3 2 Configuration over Telnet Monitoring of status configuration and administration of the router can be performed by means of th...

Page 27: ...uter 7 2 Technical parameters of module UMTS module HSDPA parameters 3GPP rel 5 standard bitrate 3 6 Mbps 384 kbps UE CAT 1 to 6 11 12 Data compress 3GPP TS25 212 UMTS parameters W CDMA FDD standard PS bitrate 384 384 kbps CS bitrate 64 64 kbps GPRS parameters GPRS multislot class 10 CS 1 to 4 EGPRS multislot class 10 CS 1 to 4 MCS 1 to 9 Transmit power GSM900 class 4 GSM1800 class 1 EDGE class E2...

Page 28: ...t 120 mA max 30 V Table 16 Technical parameters of I O 7 5 Technical parameters of expansion port Technical parameters of the expansion ports are to be found in separate manuals for expansion ports 23 LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 59 460 20 www lucom de LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 59 460 20 www lucom de LUCOM G...

Page 29: ...r guide 9 Possible problems Some network cards are able to be set in situation when it is not possible to connect the router It is possible to solve this problem in the following steps hand by selection communication rates 10 MB s in property network cards connect router over switch start computer only after finalizing the start of the router 24 LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127...

Page 30: ...e router it is possible to switch auto negotiation off and set a rate and duplex by hand DynDNS not function In private APN not functional If the same IP address is recorded in your canonic name as dynamically assign address it means that the operator is using NAT or firewall NAT is possible to verify by the help of the ping on address of your server with static IP address and by the help of the r...

Page 31: ...ol SMS message doesn t change the router configuration If the router is switched to offline mode by the SMS message the router will be in this mode up to next restart This behaviour is the same for next all control SMS messages 26 LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 59 460 20 www lucom de LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 ...

Page 32: ...ds of directive 1999 5 EC R TTE Router fits values of coefficient SAR defined by association ICNIRP and values of About protection of health before non ionized radiation Declaration about consistency was issued and is possible get it in accompanying CD or at producer 27 LUCOM GmbH Ansbacher Str 2a 90513 Zirndorf Tel 09127 59 460 10 Fax 09127 59 460 20 www lucom de LUCOM GmbH Ansbacher Str 2a 90513...

Reviews: