Lucent Technologies Lineage
®
2000 50A Ferroresonant Rectifier J85502B-1
Issue 6 May 1999
Product Description 2 - 7
•
The digital output meter is optional on the J85502B-1
rectifier. The meter displays (1) the rectifier output current
when the selector switch is in the AMPS position, (2) the
rectifier output voltage when the selector switch is in the
RECT V position, and (3) the plant battery voltage when
the selector switch is in the BATT V position. The default
display is rectifier output current. Table 2-A gives the
accuracy of this meter in the various positions. The
Figure 2-1: Control Panel of J85502B-1 Rectifier
OUTPUT
RECT V
BATT V
AMPS
OUTPUT
VOLTS ADJ
DC
OUTPUT
REG
POWER
ON
RFA
ALARM
RECT
TEST
FL
NL
OFF
1/2 AMP
+
–
Table 2-A: Digital Meter Accuracy
Meter
Position
Accuracy
RECT V
±0.5 volt for Series 1 or 2 CM3 digital
meter boards
±0.02 volt for Series 3 CM3 digital meter
boards*
BATT V
±0.02 volt for any CM3 digital meter board
AMPS
±2.5 percent of rectifier rating
*Series 3 CM3 boards can be identified by the designation
“AM3” stamped on the wiring (noncomponent) side of the
board. See Figure 7-1 for a partial sketch of CM3 boards.