Installation & Operating Instructions

Installation & Operating Instructions

From inverter

Dimmable driver

New wire - N

New wire from 

connector

E

L

N

Dim N

Dim L

3

261

96

40

216

Ø4

TECHNICAL INFORMATION

Code

LED3EP80

Dimensions

245mm x 95mm x 40mm

Total Weight

0.9Kg

Supply Voltage

230/240 Volts AC 50/60 Hz

Power Rating

4 Watts

Power Factor

0.8

Duration

3 hours

Ambient Temp

0°C to + 55°C

Max Case Temperature *

70°C

Max Battery Temperature

55°C

Battery Fuse

Internal

Battery Pack

3.6V/4.5Ah Ni-Cd

Charge Current

170mA

Recharge Period

36 Hours

•  From initial installation the integral batteries will require 

36 hours to reach full charge status.

•  Following a full discharge, 24 hours should be allowed for 

the batteries to re-charge.

•  The green LED charge indicator signifies that the batteries 

are charging and will remain illuminated when the 

luminaire is switched off.

•  The batteries have a rated service life of 4 years and should 

be checked and considered for replacement at that point.

•  A record of routine testing should be kept to ensure 

emergency luminaires are maintained and operated 

correctly.

•  The battery has a 4 year service life provided it is operated 

and maintained by regular testing, as detailed in this 

document. Failure to maintain or change the battery may 

result in reduced duration in emergency mode.

ENVIRONMENTAL PROTECTION W.E.E.E

This symbol is known as the “crossed-out wheelie Bin Symbol”. When this symbol is marked on a product or battery, It 

means that it should not be disposed of with your general household waste. Some chemicals contained within electrical/

electronic products or batteries can be harmful to health and the environment. Only dispose of electrical/electronic/battery 

items in separate collection schemes, which cater for the recovery and recycling of materials contained within. Your co-

operation is vital to ensure the success of these schemes and for the protection of the environment.

TESTING/COMMISSIONING

•  Ensure the load is connected.

•  Connect the battery. 

•  Switch on the unswitched supply - Check the charge LED 

illuminates.

•  Switch on the maintained supply - Check the LED 

illuminates as normal.

•  Switch off the maintained supply. 

•  Switch off the unswitched supply - Check the charge 

LED extinguishes and the load LED illuminates at a 

reduced output.

•  Enter the commissioning date on the battery pack. 

Switch on the unswitched supply

•  From Initial installation the intergral batteries will 

require 36 hours to reach full charge status

SL

E

N

L

SL

E

N

L

Old

New

Connector block

New wire

1

2

Page 3

Page 2

DIMMABLE DRIVER CONNECTION (DALI)

For use with DALI drivers, Please connect DALI leads direct to Driver DALI in, as per Standard installation. 

Please Note - This is not a DALI Emergency Pack and has no further DALI functionality.

FOR USE WITH DIMMABLE DRIVERS, AN ADDITION SINGLE CORE CABLE IS REQUIRED

For Use with Dimmable Drivers, An additional single core cable is required

Dimming is only suitable with retractive switches and/or DALI 

1. Open Connection Block, Move existing Switched Live from SL to L(Permanent Live)

2. Add Additional Single Core cable (400-600mm) into SL terminal, 

3. Connect New Switched Live to Switch Dim L on Driver. A small bridge cable is required from main Neutral to Dim N. 

4. Connect L/N from Emergency pack to Driver, and follow instructions as normal. 

Turn OFF Power Supply

NOTE – To comply with regulations, Installation must be carried out by suitably qualified competent person and in accordance 

with the current IEE Wiring Regulations (BS7671) and Building Regulations.

The Emergency pack requires 2 Live feeds, 1 to charge the battery pack and 1 for switching of the product.

ENSURE ELECTRICAL SUPPLY AND BATTERY CONNECTION IS DISCONNECTED/ISOLATED BEFORE COMMENCING 

INSTALLATION OR ANY MAINTENANCE WORK. HIGH VOLTAGE COULD BE PRESENT AT THE OUTPUT CONNECTION IF THE 

BATTERY IS NOT DISCONNECTED.

  3

GUARANTEE

year

 1

WARRANTY

year

on site

WARNING - AVOID RUNNING THE LED MAINS DRIVER AND 

EMERGENCY PACK WITHOUT THE LOAD CONNECTED. 

FAILURE TO DO SO MAY RESULT IN DAMAGE TO THE LED 

EMERGENCY PACK.

NOTE - This Emergency Pack is only suitable and 

guaranteed for use with Luceco luminaires.

SPECIFICATIONS

•  Suitable for use with Mains voltage of 230/240V AC

•  This product must be disconnected before insulation resistance testing of the lighting circuit

•  Check for electrical cables and pipes before installation 