Installation & Operating Instructions
Installation & Operating Instructions
From inverter
Dimmable driver
New wire - N
New wire from
connector
E
L
N
Dim N
Dim L
3
261
96
40
216
Ø4
TECHNICAL INFORMATION
Code
LED3EP80
Dimensions
245mm x 95mm x 40mm
Total Weight
0.9Kg
Supply Voltage
230/240 Volts AC 50/60 Hz
Power Rating
4 Watts
Power Factor
0.8
Duration
3 hours
Ambient Temp
0°C to + 55°C
Max Case Temperature *
70°C
Max Battery Temperature
55°C
Battery Fuse
Internal
Battery Pack
3.6V/4.5Ah Ni-Cd
Charge Current
170mA
Recharge Period
36 Hours
• From initial installation the integral batteries will require
36 hours to reach full charge status.
• Following a full discharge, 24 hours should be allowed for
the batteries to re-charge.
• The green LED charge indicator signifies that the batteries
are charging and will remain illuminated when the
luminaire is switched off.
• The batteries have a rated service life of 4 years and should
be checked and considered for replacement at that point.
• A record of routine testing should be kept to ensure
emergency luminaires are maintained and operated
correctly.
• The battery has a 4 year service life provided it is operated
and maintained by regular testing, as detailed in this
document. Failure to maintain or change the battery may
result in reduced duration in emergency mode.
ENVIRONMENTAL PROTECTION W.E.E.E
This symbol is known as the “crossed-out wheelie Bin Symbol”. When this symbol is marked on a product or battery, It
means that it should not be disposed of with your general household waste. Some chemicals contained within electrical/
electronic products or batteries can be harmful to health and the environment. Only dispose of electrical/electronic/battery
items in separate collection schemes, which cater for the recovery and recycling of materials contained within. Your co-
operation is vital to ensure the success of these schemes and for the protection of the environment.
TESTING/COMMISSIONING
• Ensure the load is connected.
• Connect the battery.
• Switch on the unswitched supply - Check the charge LED
illuminates.
• Switch on the maintained supply - Check the LED
illuminates as normal.
• Switch off the maintained supply.
• Switch off the unswitched supply - Check the charge
LED extinguishes and the load LED illuminates at a
reduced output.
• Enter the commissioning date on the battery pack.
Switch on the unswitched supply
• From Initial installation the intergral batteries will
require 36 hours to reach full charge status
SL
E
N
L
SL
E
N
L
Old
New
Connector block
New wire
1
2
Page 3
Page 2
DIMMABLE DRIVER CONNECTION (DALI)
For use with DALI drivers, Please connect DALI leads direct to Driver DALI in, as per Standard installation.
Please Note - This is not a DALI Emergency Pack and has no further DALI functionality.
FOR USE WITH DIMMABLE DRIVERS, AN ADDITION SINGLE CORE CABLE IS REQUIRED
For Use with Dimmable Drivers, An additional single core cable is required
Dimming is only suitable with retractive switches and/or DALI
1. Open Connection Block, Move existing Switched Live from SL to L(Permanent Live)
2. Add Additional Single Core cable (400-600mm) into SL terminal,
3. Connect New Switched Live to Switch Dim L on Driver. A small bridge cable is required from main Neutral to Dim N.
4. Connect L/N from Emergency pack to Driver, and follow instructions as normal.
Turn OFF Power Supply
NOTE – To comply with regulations, Installation must be carried out by suitably qualified competent person and in accordance
with the current IEE Wiring Regulations (BS7671) and Building Regulations.
The Emergency pack requires 2 Live feeds, 1 to charge the battery pack and 1 for switching of the product.
ENSURE ELECTRICAL SUPPLY AND BATTERY CONNECTION IS DISCONNECTED/ISOLATED BEFORE COMMENCING
INSTALLATION OR ANY MAINTENANCE WORK. HIGH VOLTAGE COULD BE PRESENT AT THE OUTPUT CONNECTION IF THE
BATTERY IS NOT DISCONNECTED.
3
GUARANTEE
year
1
WARRANTY
year
on site
WARNING - AVOID RUNNING THE LED MAINS DRIVER AND
EMERGENCY PACK WITHOUT THE LOAD CONNECTED.
FAILURE TO DO SO MAY RESULT IN DAMAGE TO THE LED
EMERGENCY PACK.
NOTE - This Emergency Pack is only suitable and
guaranteed for use with Luceco luminaires.
SPECIFICATIONS
• Suitable for use with Mains voltage of 230/240V AC
• This product must be disconnected before insulation resistance testing of the lighting circuit
• Check for electrical cables and pipes before installation