TROUBLESHOOTING
REFRIGERANT TROUBLESHOOTING
COMPLIANT
PROBLEM
SOLUTION
COMPRESSOR WILL NOT START
LINES DISCONNECTED / SWITCH OPEN
CLOSE START ON DISCONNECT SWITCH
FUSE REMOVED OR BLOWN
REPLACE FUSE
CONTROL STUCK IN OPEN POSITION
REPAIR OR REPLACE CONTROL
CONTROL OFF DUE TO COLD LOCATION
RELOCATE CONTROL
COMPRESSOR WILL NOT START, HUMS
BUT TRIPS OVERLOAD PROTECTOR
LOW VOLTAGE TO UNIT
CALL POWER SUPPLIER
STARTING CAPACITOR DEFECTIVE
REPLACE CAPACITOR
RELAY FAILING TO CLOSE
REPLACE RELAY
COMPRESSOR MOTOR HAS A WINDING
OPEN OR SHORTED
REPLACE COMPRESSOR
INTERNAL MECHANICAL TROUBLE IN
COMPRESSOR
REPLACE COMPRESSOR
COMPRESSOR STARTS AND RUNS, BUT
SHORT CYCLES ON OVERLOAD
PROTECTOR
LOW VOLTAGE TO UNIT
CALL POWER SUPPLIER
OVERLOAD PROTECTOR DEFECTIVE
CHECK CURRENT, REPLACE PROTECTOR
RUN CAPACTIOR DEFECTIVE
REPLACE CAPACITOR
EXCESSIVED DISCHARGE PRESSURE
CHECK VENTILATION, RESTRICTIONS IN
COOLING MEDIUM, RESTRICTIONS IN
REFRIGERANT SYSTEM
COMPRESSOR TOO HOT, RETURN GAS
HOT
CHECK REFRIGRANT CHARGE (FIX LEAK IF
NECESSARY)
COMPRESSOR MOTOR HAS A WINDING
SHORTED
REPLACE COMPRESSOR
UNIT RUNS OKAY, BUT SHORT CYCLE ON
OVERLOAD PROTECTOR
CHECK CURRENT, REPLACE PROTECTOR
THERMOSTAT
DIFFERENTIAL SET TO CLSE, WIDEN
HIGH PRESSURE CUT OUT DUE TO:
INSUFFICIENT AIR, OVERCHARGE, OR AIR
IN SYSTEM
REDUCE REFRIGERANT CHARGE, PURGE.
CHECK AIR SUPPLY TO CONDENSER,
REDUCE REFRIGERANT CHARGE, PURGE
UNIT OPERATES LONG OR
CONTINUOUSLY
SHORTAGE OF REFRIGERANT
FIX LEAK, ADD CHARGE
CONTROL
CONTACTS
STUCK
OR
FROZEN/CLOSED
CLEAN CONTACTS, OR REPLACE CONTROL
REFRIGERANT OR AIR CONDITIONED
SPACE HAS EXCESSIVE LOAD OR POOR
INSULATION
DETERMINE FAULT AND CORRECT
EVAPORATOR COIL ICED
DEFROST
RESTRICTION IN REFRIGERANT SYSTEM
DETERMINE LOCATION AND REMOVE
DIRTY CONDENSER
CLEAN CONDENSER
FILTER DIRTY
CLEAN OR REPLACE
START CAPACITOR OPEN
RELAY
CONTACTS
NOT
OPENING
PROPERLY
CLEAN CONTACTS OR REPLACE IF
NECESSARY
PROLONGED OPERATION ON CYCLE DUE
TO LOW VOLTAGE, IMPROPER RELAY
CALL POWER SUPPLIER, OR REPLACE
RUN CAPACITOR OPEN, SHORTED OR
BLOWN
EXCESSIVE SHORT CYCLE
DETERMINE REASON FOR SHORT CYCLE
IMPROPER CAPACITOR
DETERMINE CORRECT SIZE AND REPLACE
EXCESSIVELY HIGH LINE (100% OF RATED-
MAX)
CALL POWER SUPPLIER
SPACE TEMPERATURE TOO HIGH
CONTROL SETTING TO HIGH
RESET CONTROL
INADEQUATE AIR CIRCULATION
IMPROVE AIR MOVEMENT
SUCTION LINE FROSTED OR SWEATING
EXPANSION VALVE STUCK
CLEAN VALVE OFF FOREIGN PARTICLES,
REPLACE IF NECESSARY
EVAPORATOR FAN NOT RUNNING
DETERMINE REASON AND CORRECT
OVERCHARGE OF REFRIGERANT
CORRECT CHARGE