A

Building Safety. Building Security.

Specifi cations

Mains voltage 

10/-20%, 47...63Hz

Output/nominal voltage 

typ. 27.6VDC

Output current 

max. 2.2A

Output current siren outputs

   output 1 

max. 1A

   output 2 

max. 0.5A

   (the sum of the currents of the signalling devices that are connected to the two outputs must not exceed 1A!)

Own current consumption at 24V 

typ. 70mA (without optional componentries, line termination 5.6k

Ω

)

 

typ. 55mA (without optional componentries, line termination 47µF)

Line voltage 

typ. 20V (line termination 5.6k

Ω

)

 

typ. 23V (line termination 47µF)

Line current without fi re detectors 

typ. 3.7mA (line termination 5.6k

Ω

)

 

typ. 0mA (line termination 47µF)

Line termination 

5.6k

Ω

 or 47µF

Line resistance 

max. 50

Ω

 per core

Ambient temperature 

-5°C to +50°C

Relative humidity 

max. 95% (no condensation)

Dimensions W × H × D 

330 × 330 × 90 (mm)

Colour 

grey-white, RAL 9002

Weight without batteries 

approx. 3kg

Approval 

tested according to EN 54-2, EN54-4

 

VdS approval pending

Fire Detection Control Panel BC06-1

Order number 

210205

Order name 

Fire Detection Control Panel BC06-1/INT1

Fire Detection Control Panel BC06-2

Order number 

210209

Order name 

Fire Detection Control Panel BC06-2/INT1