5.14 Auto Restart Settings
When inverter operation stops due to a fault and a fault trip is activated, the inverter
automatically restarts based on the parameter settings.
Group
Cod
e
Name
Setting
Setting
Range
Unit
Pr
08 Selection of startup on trip reset
0 No
0
–1
-
09 Number of automatic restarts
0
0
–10
-
10 Auto restart delay time
1.0
0.0
–60.0
sec
Cn
71 Speed search operation selection
-
0000*
–1111
bit
72 Speed search reference current
150
80
–200
%
73 Speed search proportional gain
100
0
–9999
74 Speed search integral gain
200
0
–9999
75
Output block time before speed
search
1.0
0.0
–60.0
sec
*Displayed as
on the Keypad.
Auto Restart Setting Details
Code and
Features
Description
Pr.08 RST
Restart, Pr.09
Retry Number,
Pr.10 Retry
Delay
Only operates when Pr.08 (RST Restart) is set to 1 (Yes). The
number of attempts to try the auto restart is set at Pr.09 (Auto Restart
Count). If a fault trip occurs during operation, the inverter
automatically restarts after the set time programmed at Pr.10 (Retry
Delay). At each restart, the inverter counts the number of tries and
subtracts it from the number set. Once the retry number count
reaches 0, the automatic restart is not conducted. After an auto
restart, if a fault trip does not occur within 60 sec, it will increase the
restart count number. The maximum number of increase is limited by
the number set for Auto Restart Count.
If the inverter stops due to low voltage, emergency stop (Bx), inverter
overheating, or hardware diagnosis, an auto restart is not activated.
At auto restart, the acceleration options are identical to those of
speed search operation. Codes Cn.72
–75 can be set based on the
load. Information about the speed search function can be found at
on page
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...