Chapter 2 System Configuration
2-4
Items
Part Names
Descriptions
⑥
USB Interface
1) USB Memory Connection: Backup of data such as alarm/logging/recipe
and storage of screen data
2) USB Memory Connection: Send/Receive project data, Send XP-Runtime
3) User’s Interface Connection: Using mouse/keyboard
4) Printer connection: Printing function
⑦
Battery Cover
Reset Switch
Backup Battery
Setting Switch
<Setting Switch>
No.1
A Side.
Backup Battery On
B Side.
Backup Battery Off
No.2 / 3
A Side.
RS-422/485 Terminating Resistance On
B Side.
RS-422/485 Terminating Resistance Off
No. 4
A Side.
O/S Download Mode
B Side.
Operating Mode
⑧
Ethernet Terminal
Ethernet: 10Base-T/ 100Base-TX
1) Send Project Data
2) Receive backup data and project file
3) Send XP-Runtime
4) PLC/Control Device Communication
⑨
RS-232C, RS-
422/485 Connector
RS-232C (COM2): PLC/ Control Device Communication
RS-422/485 (COM3): PLC/ Control Device Communication
※
COM1 is not used.