MMP Series
D-group
Group
Menu
Description
Setting range
Default
D
Total running time
0~9999day / 0~23h / 0~59m
-
Running time
0~9999h /
-
0~59m
Running time setting
Off/10~8760
Off
Contactor check
Off/On
Off
Date
note 1)
2013~2100y
2014.01.01.
/ 1~12 (Mon), 1~31 (Day)
0:00
/ 0~23h, 0~59m
Contactor counter
note 1)
-
-
Fault cause check
note 3)
1. The most recent
-
2. The 2nd. recent
3. The 3rd. recent
4. The 4th. recent
5. The 5th. recent
Automatic reset time
OFF / 1~20m
Off
Automatic reset number
Off/1~5
Off
Set number of times
Communication address
note 4)
1~247
247
Communication speed
note 4)
9.6/19.2/38.4K
9.6K
Swap
note 4)
On/Off
Off
Parity setting
note 4)
nonE/odd/EUEn
nonE
20mA setting
note 4)
0.5~10/5~100
10/100
Stored data deletion
All : for all subparameters
-
A-P : active energy
rA-P : reactive energy
trt : total running time
CCC : contactor counter
CALo : calories
FALt : fault events
Operation test
o-L : overcurrent test
-
o-U : overvoltage test
g-F : ground fault test
I-C : instantaneous test
Note) 1. The contactor operation is counted up to 65000cycles and then initialized.
2. The date setting can be stored after filling up month, day, hour and minute.
3. The trip cause can be stored up to 5 recent events and then the oldest event is deleted first.
4. 10.Ad, 11.bs, 12.SP, 13.Pr, 14.td are available for communication type products.
5. Data clear and test can be inputted in the normal state, and test items can be viewed while a motor is switched on.
LSIS Co.,Ltd.
87