100
Electronic Motor Protection Relays
CT
(Current Transformer)
Rated specifications
Classification
Code
Model name
Primary
current
Secondary
current
Load(VA)
Penetrating
hole [mm]
Upper installation
EMPR
Remarks
3CT type
76012116026
3CT-23
50A
5A
1.5
21×21
GMP22/40/60T
1) Error class: Class 1.0
2) Insulation voltage: 690V
3) Withstanding voltage:
4kV/min
4) Overcurrent strength:
40 x 1n
5) Insulation resistance:
10MΩ (DC 500V Megger)
6) Frequency: 50/60Hz
76012116011
3CT-23
80A
76012116012
3CT-23
100A
76012116013
3CT-23
150A
76012116014
3CT-23
180A
76012116015
3CT-23
200A
76012116016
3CT-43
100A
27×27
DMP/IMP/DMPi
entire series
GMP60-3T/3TN/3TZ
GMP22/40/60T
76012116017
3CT-43
150A
76012116018
3CT-43
200A
76012116019
3CT-43
250A
76012116020
3CT-43
300A
76012116021
3CT-43
350A
76012116022
3CT-43
400A
76012116023
3CT-63
400A
45×30
76012116024
3CT-63
500A
76012116025
3CT-63
600A
2CT type
76012116001
DCT-100
100A
5A
5
28.5×33.5
GMP22/40/60T
76012116002
DCT-150
150A
76012116003
DCT-200
200A
76012116004
DCT-300
300A
76012116005
DCT-400
400A
1CT type
76012116006
SCT-100
100A
5A
5
27.5×32.5
DMP/IMP/DMPi
entire series
GMP60-3T/3TN/3TZ
GMP22/40/60T
76012116007
SCT-150
150A
76012116008
SCT-200
200A
76012116009
SCT-300
300A
76012116010
SCT-400
400A
*Note: If the CT secondary cable thickness is 2.5mm2, the load of 3m is 0.52VA.
Dimensions
Dimensions
3CT type (3CT-
)
u
K
K
v
K
w
w
u
B
A
B
C
D
E
F
3CT-23
Type
119
35
9
21.5
89
76
3CT-43
149
44
12
27
117
91
3CT-63
218
70
20
45/30
183
94
5
E
D
A
C
D
38 53±1
F
B
2CT type (DCT-
)
65
33.
5
55
28.5
120
60
80
69.6
2- 5
EMPR Optional accessories