4.2
INTRODUCTION
PowerPoint is a simple-to-use power distribution unit with a 3-phase mains input (single-
phase input available) and either 6 or 12 single-phase outputs depending on the model.
Designed for applications wherever fixed or mobile power distribution is required, the
PowerPoint distribution rack offers a 4-pole mains input isolator switch with Neutral
Disconnect as standard and individual RCBO (RCD+MCB) per output channel. There are also
3 neon phase indicators to show power input to the rack.
Output circuit rating can be specified as either 10A, 16A or 25A and back-panel options
include either Australian GPO, Socapex, powerCON, Schuko, Wieland or terminal outputs.
4.3
FEATURES
•
Twelve 10A, 16A or six 25A output circuits
•
Individual RCD (30mA) protection for each output circuit
–
protection for users
•
Individual circuit breaker for each output circuit
•
Master isolator switch that also disconnects Neutral from output circuits
•
Three neon indicators show state of input phase power
•
Three-phase operation
•
Single-phase operation possible
4.4
FRONT PANEL
12-Channel PowerPoint
5
Setting Up and Connecting
5.1
SAFETY
All electrical work must be carried out by suitably qualified persons.
5.2
UNPACKING
Your PowerPoint is fully tested and inspected before leaving the factory. Upon delivery, inspect
the PowerPoint for signs of damage or mishandling. In the event of any damage, contact your
LSC agent.
5.3
CONNECTIONS
5.3.1
Input Power Supply
Always ensure that the Input Isolator is in the OFF position before connecting or
disconnecting the input power.
PowerPoint must be fed from a suitable external circuit breaker. The nominal input voltage is
110-240V, 3-phase Star (380-415V), 50-60Hz. Single-phase operation is possible but input
current must be limited to 63A in total.
Output Load RCBOs
Input Isolator
Input Phase
Presence Indicators
Input Phase Labels