DMX CABLES 

Only use specific DMX data cable. The data cable must conform to the EIA485 cable 
requirements by providing the following specifications: 

 

Low capacitance 

 

One or more twisted pairs 

 

Foil and braid shielded 

 

Impedance of 85-150 ohms, nominally 120 ohms 

 

22AWG gauge for continuous lengths over 300 metres 

If  you  want  to  make  your  own  cables  LSC  recommends  using  Beldon  9842  (or 
equivalent). Never use audio cable. 
The end of the DMX line must be terminated (120 

Ω

) to prevent the signal reflecting 

back up the line and causing possible errors. 

1.6

 

PUSH-FIT TERMINALS 

The following cables are suitable for use with the push-fit terminals: 

 

2.5mm² stranded wire 

 

4.0mm² solid wire 

Stripping length is 8mm. 
Insert a small screwdriver into the slot adjacent to the cable hole. This releases the 
spring inside the connector. Insert the cable into the round hole then remove the 
screwdriver. Solid wires or wires fitted with ferrules can often be pushed directly 
into the connector without the use of the screwdriver. When connecting multiple 
cables  to  a  single  terminal  the  wires  must  be  twisted  together  to  ensure  a  good 
connection  to  both  legs.  Non-insulated  bootlace  ferrules  can  also  be  used  for 
stranded cables. Ferrules are not recommended for solid cables. Insulated bootlace 
ferrules can also be used allowing stranded cables to be easily inserted without the 
need of a tool to actuate the spring release. The maximum ferrule outer diameter is 
4mm. 

1.7

 

RJ45 DMX CONNECTOR PIN-OUTS 

RJ45 8-Pin Connector  Function 

Pin 1 

DMX +ve 

Pin 2 

DMX 

ve 

Pin 3 

Not Connected 

Pin 4 

Not Connected 

Pin 5 

Not Connected 

Pin 6 

Not Connected 

Pin 7 

Common 

Pin 8 

Common 

Page 2 

 

1.8

 

MDR-DIN SPECIFICATIONS 

Power Requirements

 

9-24V DC, 5W 

Power Input Connector

 

Quick Connect Terminals 

Reverse Polarity Protected

 

Yes 

Input and Thru Connectors

 

RJ45  or  Quick Connect Terminals 

Output Connectors

 

RJ45  or  Quick Connect Terminals 

Number of Buffered Outputs

 

DMX Protocol

 

ANSI DMX512A Standard E1.11:2008 (R2013) 

RDM Protocol

 

ANSI RDM Standard E1.20:2010 

RDM

 

Can be individually disabled on each output 

All Inputs and all Outputs Isolated

 

Yes 

Galvanic Isolation Barrier

 

1500V 

Short Circuit Protected

 

Yes 

DMX512 Data LED

 

Yes (Flashes when DMX data is present) 

RDM Data LED

 

Yes (Flashes when RDM data is present) 

Power LED

 

Yes (Flashes when RDM Identify is received) 

Conformity

 

CE, RCM 

 

Note:

 All outputs are individually isolated from each other as well as the input.  

Isolation  is  for  both  data  and  common  connections  and  provides  a  galvanic 
barrier to 1500V. Outputs are EMI-filtered and current-limited to protect against 
short circuits. 

1.9

 

DMX EXPLAINED 

DMX512-A is the industry standard for the transmission of digital control signals 
between  lighting  equipment.  It  utilises  just  a  single  pair  of  wires  on  which  is 
transmitted  the  level  information  for  the  control  of  up  to  512  DMX  slots 
(addresses or channels).   
The  information  for  each  slot  is  sent  sequentially.  The  level  of  slot  1  is 
transmitted, then the level of slot 2, then 3, etc., up to a maximum of 512 slots. 
This  stream  of  data  containing  the  levels  for  all  512  DMX  slots  is  repeated  a 
minimum (generally) of 44 times per second. This provides sufficient updates of 
channel information for smooth fade transitions. 
DMX  allows  a  controller  to  communicate  with  a  device.  It  does  not  allow  the 
device to communicate with the controller. 

1.10

 

RDM EXPLAINED 

RDM allows RDM-based controllers and devices to communicate with each other 
in bidirectional mode over the DMX cable, interleaved with the DMX512-A signal. 
 

 

Page 3 

 

 