P83541 G 

Sheet 1 of 6 

 

273 Branchport Avenue 
Long Branch, N.J.  07740 
(800) 

 

631-2148             

 

Thank you for using our products.

 

www.wheeelockinc.com 

INSTALLATION INSTRUCTIONS 

FOUR ZONE SPLITTER 

(FOR MULTI CIRCUIT SAFEPATH PANELS) 

 

Use this product according to this instruction manual.  Please keep this instruction manual for future reference. 

 
 

MODEL NUMBER: 

SPL 

   Four 

Zone 

Splitter

 

                   
 

GENERAL: 

The Four Zone Splitter is designed to be used with Wheelock’s multi circuit SAFEPATH panels and it provides a means for 
expanding a supervised audio output zone from one to four sub zones.  The Four Zone Splitters are UL Listed under Standard 864, 
Control Units for Fire Protective Signaling Systems.  They are listed for indoor use only.  Only 1 Four Zone Splitter can be connected 
to each SAFEPATH channel.  They are to be mounted inside the SAFEPATH panel enclosure onto the power supply printed circuit 
board (PCB) cover.  The splitter works with all of the Wheelock amplifier modules.  If the splitter is used with a power amplifier, the 
maximum power per sub zone cannot exceed what is listed in Table 1. 
 

NOTE:

  All 

CAUTIONS

 and 

WARNINGS

 are identified by the symbol

 

.  All warnings are printed in bold capital letters. 

 

SPECIFICATIONS: (Per UL 864) 
 

Table 1: 

 SAA-40S/80S/80SE 

SALL-15S 

Audio Output Voltage 

25.0V 

70.7V 

100.0V 

0.5V 

Maximum Output Power Per Sub Zone 

25.0W 

70.0W 

100.0W 

30 Speaker Inputs 

 
Power Input Voltage: 

24VDC 

Audio Input/Output Voltage: 

25.0VRMS, 70.7VRMS, 100.0VRMS, or 0.5VRMS 

Input Current: 

40mA Standby with no zones selected  

 

190mA with all zones selected 

Audio Power In: 

100.0 Watts Maximum 

Audio Power Out: 

100.0 Watts Maximum (See Table 1 for maximum watts per zone) 

 

MOUNTING INSTRUCTIONS: 
 
Four Circuit SAFEPATH 

 
1.  Attach the 4 PCB standoffs to the 4 mounting holes in the SAFEPATH Power Supply PCB cover (see Figure 1) by pushing 

standoff into the hole until it locks into place as shown in Figure 2. 

 

2.  Attach the Four Zone Splitter PCB on to the PCB standoffs so that the standoffs mate with the mounting holes on the PCB as 

shown in Figure 2.  Push the PCB until the board locks into the 4 standoffs 

 

3.  Remove the old hole cover on the SAFEPATH Panel’s Dead Front Panel that corresponds to the location of the new splitter 

module by removing the 4 hole plugs on the cover.  Save the 4 plugs to attach the new cover.  (See Figure 3) 

 

4. 

Attach the Four Zone Splitter cover to the Dead Front Panel using the 4 hole plugs. 

 
 

Copyright 2003, 2004 Wheelock, Inc.  All rights reserved. 

Summary of Contents for SPL

Page 1: ... the symbol All warnings are printed in bold capital letters SPECIFICATIONS Per UL 864 Table 1 SAA 40S 80S 80SE SALL 15S Audio Output Voltage 25 0V 70 7V 100 0V 0 5V Maximum Output Power Per Sub Zone 25 0W 70 0W 100 0W 30 Speaker Inputs Power Input Voltage 24VDC Audio Input Output Voltage 25 0VRMS 70 7VRMS 100 0VRMS or 0 5VRMS Input Current 40mA Standby with no zones selected 190mA with all zones ...

Page 2: ...P83541 F Sheet 2 of 6 4 MOUNTING HOLES FOR SPLITTER POWER SUPPLY PCB COVER Figure 1 4 ZONE SPLITTER 1 PCB STANDOFFS 4 POWER SUPPLY PCB COVER 1 Figure 2 ...

Page 3: ...ONE 1 Slide the zone disarrangement switch down to the 2 To override zone disarrangement slide the DISARRANGEMENT ACKNOWLEDGE DISARRANGEMENT DISARRANGEMENT DISARRANGEMENT ALL CALL press the push to talk switch on microphone deliver the message to all circuits DISARRANGEMENT position WARNING ZONE SELECT ALL CALL switch to ALL CALL MANUAL position NORMAL TROUBLE ZONE 4 ZONE 3 ZONE 2 ZONE 1 WARNING M...

Page 4: ...indicate to which zones audio is currently being broadcast The splitter will allow zone selection of live announcements only Automatic or manual alarm operation will be through all zones The splitter detects audio wiring faults opens and shorts in the non alarm mode only During alarm paging the splitter allows the selection of any or all zone outputs The ALL CALL switch overrides all zone selectio...

Page 5: ... for a specific installation must be obtained from the Fire Department d A priority voice message matrix must be submitted to the Fire Department for approval before the installation is performed and shall include the following information 1 The duration of each message 2 The content of each message 3 The duration of the audible and visual alarm signals prior to the initiation of the subsequent pr...

Page 6: ... SPECIFICATION ABUSE ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND WHEELOCK S CONTROL SOME WHEELOCK PRODUCTS CONTAIN SOFTWARE WITH RESPECT TO THOSE PRODUCTS WHEELOCK DOES NOT WARRANTY THAT THE OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR FREE OR THAT THE SOFTWARE WILL MEET ANY OTHER STANDARD OF PERFORMANCE OR THAT THE FUNCTIONS OR PERFORMANCE OF THE SOFTWARE WILL MEET THE USER S REQUIR...