Installation and Handling
6. Installation of accessories and handling
■
Internal Accessories.
Auxiliary Switch (AX) / Alarm Switch (AL) / Shunt Trip (SHT) / Under voltage Trip (UVT)
/ Fault and SHT/UVT Trip Alarm Switch (FUAL)
FUAL
①
②
③
SCREW
(+)PH M3X10, 2ea
0.8Nm
(8.2kgf cm)
.
②
①
Figure. Example of Lock up Circuit for FUAL
:
Please use
“
Lock up Circuit
”
following under figure
“
Example of lock up circuit for FUAL
”
: When MCCB is tripped by SHT or UVT,
the FAL signal appears for 20ms that
is time of being transferred from
“
b
”
contact to
“
a
”
contact of control relay.
Shunt Trip (SHT) / Under Voltage Trip (UVT)
: Don
’
t operate MCCB unless Under Voltage Trip is energized.
①
②
③
④
Please check that MCCB is trip state before installing UVT.
Install
Uninstall
Uninstall
* In case of
assembling
UVT
①
②
Install
④
③
1. In case of disassembling and assembling the main cover, screw should be tightened in specific torque of1.5N.m (15.3kgf.cm)
2. In case of disassembling and assembling the main cover by over tightening torque, the parts of MCCB can be damaged.
Summary of Contents for TS1000H
Page 1: ...0 ...
Page 8: ...7 C Structure and Operation 1 Internal structure and Components System Overview ...
Page 13: ...12 E Weight Dimension 1 Weight Dimension 3 Overall Dimension Front connection type ...
Page 14: ...13 E Weight Dimension 1 Weight Dimension 4 Overall Dimension Rear connection type ...
Page 36: ...35 4 온도 센서 1 Protection A Type J TRIP RELAY Setting ...
Page 37: ...36 4 온도 센서 1 Protection P S Type J TRIP RELAY Setting ...
Page 45: ...44 4 온도 센서 1 Long time Delay L Characteristic Curves of TRIP RELAY ...
Page 46: ...45 4 온도 센서 2 Short time Delay L Characteristic curves of TRIP RELAY ...
Page 47: ...46 4 온도 센서 3 Instantaneous Ground Fault L Characteristic curves of TRIP RELAY ...
Page 48: ...47 4 온도 센서 4 IDMTL L Characteristic curves of TRIP RELAY ...
Page 49: ...48 4 온도 센서 5 Pre Trip Alarm L Characteristic curves of TRIP RELAY ...
Page 55: ...54 ...