User Guide for SpeedControl 1047
• LS Control A/S
• Industrivej 12
• DK –
4160 Herlufmagle
Page 12
• Tel: +45
5550 5550
• Fax:+45
5550 2265
FAQ
No LEDs are on and the motor will not start.
1.)
Check if the frequency converter is connected to mains
2.)
Check if fuse is blown.
The motor will not start and LED7 is on
If hardware stop switch is not in use, terminals 16 and 17 must be shortened.
The motor will not start and LED3 flashes (11
times)
If LSC input is detecting an error. By default, LSC input is setup for connection of a thermal
switch, and if it is not used, terminals 1 and 2 must be shortened.