5.    Cut the incoming DC power supply cable to less than 1 meter away from 

        the equipment.

6.    Strip about 50mm of cable jacket to expose wires.

7.    Strip about 6mm of wire insulator to expose conductor.

8.    Connect the + and - of the incoming DC power supply to the 

        corresp and - of LINE terminal of the SPD.

9.    Connect the + and - of the equipment DC power cable to the 

        corresp and - of EQUIPMENT terminal of the SPD following the

        same procedure used in step 6 & 7.   

10.  Apply power to the now protected equipment.

Trouble - shooting  

1.   Check to see if your equipment is turned on.

2.   Inspect  all connections.

3.   Remove and by - pass SPD and verify proper operation. If  the system

       comes back on line without the SPD installed, chances are the SPD

       has been damaged by excessive surge. Replace  the  SPD as soon as

       possible with a new SPD. It is not advisable to run the system  

       without  SPD. 

v

Equipment

to be 

Protected

AC 

Ground

Equipment Data Line

< 1 meter

Incoming Data Line

(overhead cable/underground cable/

indoor equipment > 30 meters)

G

Note:

Both + (Positive) and - (Negative) are connected internally inside the SPD.

 +   G    -

 +   G    -

 LINE

 EQUIP