1943969
V1.6
11 April 2022
Instruction Sheet Template - V1.3
–
Updated 20/01/2022
Installation:
The LP Cleverfit Pro can be installed either Ceiling or Wall Mounted. The LP Cleverfit
Pro uses a “slide
connect bracket base” that is mounted and wired into position first. The main body can be installed once
the base is wired or later to avoid damage during the construction phase. Please follow the steps below
to install the LP Cleverfit Pro Exit:
•
Disengage the slide connect bracket from the exit body. Position the base in the mounting position.
•
Using the bracket as a guide, mark 2 holes for mounting and one for mains access. Then install the
bracket using appropriate fixings (not supplied).
•
Configure all the mounting parts and cable entry points as below (if required) and engage the body
into the slide connect bracket. Connect mains and check that the LP Cleverfit Pro Exit is
Operational
.
•
If the CTP capabilities are activated, please affix the CTP Status Label to a visible surface.
Dimensions: Assembly:
Testing:
Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24
hours. Conduct the following tests:
•
For the first test, the emergency lamp must remain illuminated for at least 2 hours after
disconnection from the mains supply.
•
Subsequent tests require the unit to illuminate for at least 90 minutes. The results of all tests are
required to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails
to remain illuminated for the requisite time, remedial action must be taken to repair the situation
and once completed, the unit must pass a subsequent test. For more specific information, please
refer to the current edition of the AS 2293.3 Standard.
Trouble Shooting:
Below are a list of common problems and their possible causes.
Fault:
The Green LED Test Switch indicator is not illuminated.
Check: A.C. is connected and is turned on.
Battery is connected
Test Switch for damage.
Fault:
Lamp does not illuminate in emergency mode.
Check: A.C. is connected.
Lamp is correctly inserted.
Battery is connected
Fault:
Lamp illuminates in emergency mode, but only stays on for a short period.
Check:
Battery has been allowed to charge for at least 24 hours.
Battery for damage.
Rated Emergency Lumen Output in accordance with AS2293.1, not applicable
for
–TH (theatre) version (refer to spacing tables for installation positions):
Refer to the Technical Label for classification information.
Caution:
On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries
discharged or “cycled”. The battery in this fitting has been selected to give excellent long-life
performance in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-
life performance and may lead to premature battery failure. Battery warranty claims, as a result of such
abuse, are specifically EXCLUDED from Clevertronics warranty terms.
Warranty:
For Product Warranty information and Terms and Conditions of Sales please refer to our website
http://clevertronics.com.au/terms-conditions-sale-australia-nz/
Mounting Bracket - Top View
Ceiling Mount screw fixing points
Mounting Bracket - Front
View
Wall Mount screw
fixing points
Mounting Bracket - Bottom
View
Terminal Block
Cover
Terminal Block
Cable Entry Point
–
Inside of bracket for ceiling
mount, 20mm diameter, located in centre of
bracket. Bracket shown with the terminal block
cover removed.
Wall Mount Access
Holes with Cover
Plug
Cable Entry Point
–
Rear of bracket for wall
mount, 20mm diameter, located in centre of
bracket.
Cable Entry Point
–
Top of
bracket for ceiling mount,
20mm diameter, located
in centre of bracket