L-INX User Manual
256
LOYTEC
Version 4.0
LOYTEC electronics GmbH
The L-logiCAD installer installs the IEC61131 programming environment logiCAD and all
L-INX related software packages. These packages include the template project for the
LINX, the required software to build IEC61131 programs for the L-INX device, and
required extensions to interface to CEA709 networks. Follow the instructions of the installer
to install logiCAD for the LINX-110.
The language for the logiCAD user interfaces can be set to German or English using the
administration folder of the logiCAD control center. The logiCAD control center can be
started from the Windows start menu.
The license to run a copy of logiCAD on any PC can be stored on a USB hardlock of type
‗Aladdin‘. If no driver for this type of hardlock is already installed on the PC, install the
driver provided on the LOYTEC website. If the driver installation failed, or the USB key
was not detected or connected, the window shown in Figure 201 will be shown when
logiCAD is started. The USB key was correctly detected if it is listened in the Microsoft
Windows device manager as shown in Figure 202.
If a softlock license should be used instead of the USB key, press the button
Download
Softlock License
, enter the license data provided with the product into the web site form,
download the license file (.lic file) and install it using the
Install Softlock License
button.
Figure 201: logiCAD Product Activation
Figure 202: USB key driver
Note:
logiCAD checks frequently if the USB key is present. When unplugging the USB key, even if
logiCAD was successfully started, all major features are automatically disabled. But there
is no additional message for the user!
12.3 IEC61131 Project Files
In the L-INX Configurator select the
Project Files
tab to attach an IEC61131 program and
a logiCAD project to the L-INX project. The tab is shown in Figure 203.