The TSS2
is an electronic temperature controller designed for ON/OFF
control or Neutral Area Control. They can be provided with 1 or 2 probes
(both PTC range -58 to 302ºF) according to parameter P5 and it
provides with two output relays plus an alarm buzzer. The unit controls
cooling, heating or both, since its relays can be setup for direct or
reverse operation. The user is able to program 34 different parameters
including set points, hysteresis, configuration of alarms and probe
adjustment using the silicone front keypad. The unit features error
warning and password protection.
Each suffix can take the following values:
NOTE:
Unit must be mounted away from vibration, impacts, water and
corrosive gases.
• Cut hole in panel 71 x 29 mm (2.80 x 1.14 inches).
• Apply silicone (or rubber gasket) around the perimeter of the hole to
prevent leakage.
• Insert unit into hole of panel.
• Slide removable fitting clips onto unit from the back until secure to
panel.
• Wiring diagram is displayed on the top of the unit.
• Note:
DO NOT INSTALL PROBE CABLE NEAR POWER CABLES.
Series TSS2 Dual Stage Temperature Switch
Specifications - Installation and Operating Instructions
Bulletin E-90-TSS2
SPECIFICATIONS
Probe Range:
-58 to 302°F (-50 to 150°C).
Input:
PTC thermistor (1000Ω @ 25°C).
Outputs:
One 16A SPDT relay @ 250 VAC, resistive; One 8A SPDT
relay @ 250 VAC resistive.
Horsepower Rating (HP):
1 HP.
Power Requirements:
12 VAC/DC, 24 VAC/DC, 115 VAC, 230 VAC
depending on model.
Accuracy:
1% of full scale.
Display:
3-digit and sign, red LED.
Resolution:
0.1° (<100°); 1° (≥100°).
Memory Backup:
Nonvolatile memory.
Temperature Limit:
Ambient: 32 to 158°F (0 to 70°C).
Storage Temperature:
-4 to 176°F (-20 to 80°C).
Dimensions:
3 x 1-27/64 x 2-7/16 in.
Front Panel Rating:
IP64.
Weight:
2.3 oz (65 g).
Agency Approvals:
CE, UR.
Maintenance, cleaning and repair
After final installation of the unit, no routine maintenance is required.
Clean the surface of the display controller with a soft and damp cloth.
Never use abrasive detergents, petrol, alcohol or solvents. All repairs
must be made by authorized personnel.
LOVE CONTROLS DIVISION
Phone: 219/879-8000 www.love-controls.com
DWYER INSTRUMENTS INC.
Fax: 219/872-9057 e-mail:[email protected]
P.O. BOX 338 - MICHIGAN CITY, INDIANA 46361, U.S.A.
°C
WIRING DIAGRAM
BLUE BUTTONS
3
[76.2]
1-27/64
[36.12]
1-9/64
[28.97]
2-7/16
[61.91]
MODEL CODE
DISPLAY COLOR
0=RED
UNITS
0 = °F
1 = °C
SUPPLY VOLTAGE
1 = 115 VAC
2 = 230 VAC
3 = 12 VAC/DC
4 = 23 VAC/DC
OUTPUTS
2 = 2 OUTPUTS
TSS2 –