The TSS2 

is an electronic temperature controller designed for ON/OFF

control or Neutral Area Control. They can be provided with 1 or 2 probes
(both  PTC  range  -58  to  302ºF)  according  to  parameter  P5  and  it
provides with two output relays plus an alarm buzzer. The unit controls
cooling,  heating  or  both,  since  its  relays  can  be  setup  for  direct  or
reverse operation. The user is able to program 34 different parameters
including  set  points,  hysteresis,  configuration  of  alarms  and  probe
adjustment  using  the  silicone  front  keypad.  The  unit  features  error
warning and password protection.

Each suffix can take the following values:

NOTE: 

Unit must be mounted away from vibration, impacts, water and

corrosive gases.

• Cut hole in panel 71 x 29 mm (2.80 x 1.14 inches). 
• Apply silicone (or rubber gasket) around the perimeter of the hole to 

prevent leakage. 

• Insert unit into hole of panel. 
• Slide removable fitting clips onto unit from the back until secure to 

panel. 

• Wiring diagram is displayed on the top of the unit. 

• Note: 

DO NOT INSTALL PROBE CABLE NEAR POWER CABLES.

Series TSS2 Dual Stage Temperature Switch 

Specifications - Installation and Operating Instructions

Bulletin E-90-TSS2

SPECIFICATIONS
Probe Range:

-58 to 302°F (-50 to 150°C).

Input:

PTC thermistor (1000Ω @ 25°C).

Outputs:

One 16A SPDT relay @ 250 VAC, resistive; One 8A SPDT

relay @ 250 VAC resistive.

Horsepower Rating (HP):

1 HP.

Power Requirements:

12 VAC/DC, 24 VAC/DC, 115 VAC, 230 VAC

depending on model.

Accuracy:

1% of full scale.

Display:

3-digit and sign, red LED. 

Resolution:

0.1° (<100°); 1° (≥100°).

Memory Backup:

Nonvolatile memory.

Temperature Limit:

Ambient: 32 to 158°F (0 to 70°C).

Storage Temperature:

-4 to 176°F (-20 to 80°C).

Dimensions:

3 x 1-27/64 x 2-7/16 in.

Front Panel Rating:

IP64.

Weight:

2.3 oz (65 g).

Agency Approvals:

CE, UR.

Maintenance, cleaning and repair

After  final  installation  of  the  unit,  no  routine  maintenance  is  required.
Clean the surface of the display controller with a soft and damp cloth.
Never  use  abrasive  detergents,  petrol,  alcohol  or  solvents. All  repairs
must be made by authorized personnel.

LOVE CONTROLS DIVISION

Phone: 219/879-8000 www.love-controls.com

DWYER INSTRUMENTS INC. 

Fax: 219/872-9057 e-mail:[email protected]

P.O. BOX 338 - MICHIGAN CITY, INDIANA 46361, U.S.A.