background image

To remove from the DIN rail, place a small slotted screwdriver in the slot
in the spring clip under the housing. Pry the slot downward to release the
SCU from the bottom of the rail.

Wiring

The wiring terminals for the SC4380 are compression type. To open the wiring ter-
minal, turn the screw for that terminal counterclockwise. Slide the wire into the ter-
minal space. While holding the wire in place, turn the screw clockwise to tighten.
Do not overtighten. The wire should be held snugly in place.

Wire the input, output, and power as shown on the wiring label. 

Do not run Class

2 signal wires adjacent to or in the same conduit as power wires.

Calibration

1. Apply the appropriate input for the low end of the scale.
2. Adjust the ZERO screw for the appropriate low end output.
3. Apply the appropriate input for the high end of the scale.
4. Adjust the SPAN screw for the appropriate high end output.
5. Repeat as necessary.

SPECIFICATIONS
Power Supply: 

SCL4380: 12 to 24 VDC/AC 40 to 400 Hz ±20%.
SC4380: 85 to 265 VDC/VAC 50 to 400 Hz.

Isolation: 

1500 VAC.

Ambient Temperature Range (operating): 

0 to 50°C (32 to 131°F).

Linearity: 

0.1%. 

Drift: 

±0.02% per °C typical, ±0.05% maximum.

Maximum Current Output Load:

600 ohms.

Maximum Voltage Output Load:

20 mA (500 ohms).

Input Impedence - Current:

10 ohms.

Input Impedence - Voltage: 

1 Megohm.

©Copyright 2010 Dwyer Instruments, Inc.                             Printed in U.S.A. 3/10

FR# 949-0527 Rev. 1

LOVE CONTROLS DIVISION

Phone: 219/879-8000

DWYER INSTRUMENTS, INC.

www.love-controls.com

P.O. BOX 373 • MICHIGAN CITY, 

Fax: 219/872-9057

INDIANA 46361, U.S.A. 

e-mail: [email protected]

949-0527:Layout 3  3/25/10  8:44 AM  Page 4

Reviews: