 Dimensioni meccaniche 

 Mechanical dimensions

 

 

45.0

mm

90.0

mm

98.3

mm

104.7

mm

53.5mm

4.2mm

 
 

 

 

 

 

 

 

 

 
 

 

 

 
 

CARATTERISTICHE TECNICHE

 

Circuito di alimentazione e controllo 

Tensione nominale Ue 

400V

~

 

230V

~

 

Frequenza nominale 

50Hz  

Limiti di funzionamento 

0,7...1,3 Ue 

Potenza assorbita  

27 VA max 

Potenza dissipata  

1,9 W max 

Ripristino Automatico 
Tempo di ripristino all’alimentazione 

 500ms 

Soglie di intervento di tensione 

Intervento di MAX tensione  

113 [%Ue] 

Intervento di MIN tensione  

82,5 [%Ue] 

Isteresi sulle soglie di tensione 

5%  

Ritardo intervento per V MAX  

 0,1 sec 

Ritardo intervento per V MIN 

 0,2 sec 

Soglie di intervento di frequenza 

Intervento soglia frequenza  

+/-0,3Hz o +/-1Hz 

Isteresi sulle soglie di frequenza 

0,2%  

Ritardo intervento  

 100ms 

 

Tempo immunità ai transitori 

 40ms 

Soglia derivata di frequenza

 

 0,5 Hz/s 

Isteresi sulla derivata di frequenza 

25mHz/s 

Ritardo intervento per derivata di 
frequenza 

 200ms 

Ritardi regolabili 

Ritardo ripristino per intervento di 
tensione e frequenza  

0,1…30 sec 

Relè di uscita 

Numero di relè 

Tipo di uscita 

 contatto in scambio 

Tensione nominale  

250V

~

 

Tensione max d’interruzione 

400V

~

 

Designazione secondo IEC/EN 

60947-5-1 

AC1 8A-250V

~

 / 

B300  

Durata elettrica 

10

5

 operazioni 

Vita meccanica 

30x10

6

 operazioni 

Tensione di isolamento  

Tipo di prova 

Uimp 

AC 50Hz 

Fra alimentazione/misura e contatti 
relè

 

7,3kV 2kV 

Fra contatti relè  

7,3kV 

2kV 

Fra i circuiti e le parti accessibili del 
contenitore 

9,8kV 4kV 

Tensione nominale d’isolamento Ui 

400V

~

 

Condizioni ambientali  

Temperatura ambiente di 

funzionamento 

-20…+60°C 

Temperatura ambiente di 
stoccaggio 

-30 …+80°C 

Umidità relativa 

<

90%  

(IEC/EN 60068-2-70)

 

Inquinamento ambientale massimo 

Grado 3 

Categoria dì sovratensione 

Sequenza climatica 

Z/ABDM  

(IEC/EN 60068-2-61)

 

Resistenza agli urti 

 (IEC/EN 60068-2-27)

 

Resistenza alle vibrazioni 

 (IEC/EN 60068-2-6)

 

Connessioni  

Tipo di terminali 

Fissi 

Sezione conduttori 

0.2 – 4.0 mm

(24 – 12 AWG) 

Coppia di serraggio 

0,8Nm   (7Lbin) 

 

TECHNICAL CHACTERISTICS 

Control and power supply circuit 

Rated operational voltage Ue  

400V

~

 

230V

~

 

Rated frequency 

50Hz  

Operating range 

0.7...1.3 Ue 

Power consumption 

27 VA max 

Power dissipation 

1,9 W max 

Resetting Automatic 
Resetting time at power on 

 500ms 

Voltage tripping thresholds 

Tripping for MAX voltage 

113 [%Ue] 

Tripping for MIN voltage 

82,5 [%Ue] 

Hysteresis  for voltage thresholds 

5% 

V MAX tripping delay 

 0,1 sec 

V MIN tripping delay 

 0,2 sec 

Frequency  tripping thresholds 

Frequency  tripping thresholds 

+/-0,3Hz or +/-1Hz 

Hysteresis for frequency  thresholds 

0,2% 

 

Thresholds tripping delay 

 

 100ms 

Transient immunity time 

 40ms 

ROCOF threshold 

 0,5 Hz/s 

ROCOF hysteresis 

25mHz/s 

 

ROCOF tripping delay 

 

 200ms 

Adjustable timers 

Reset delay for voltage and 
frequency thresholds 

0.1…30 sec 

Output relay 

Number of outputs 

Type of output 

 changeover contact 

Rated operating voltage  

250V

~

 

Maximum switching voltage 

400V

~

 

IEC/EN 60947-5-1  

designation 

AC1 8A-250V

~

 / 

B300    

Electrical life 

10

5

 ops 

Mechanical life 

30x10

6

 ops 

Insulation voltage 

Type of test 

Uimp 

AC 50Hz 

Between supply/measure and relay 
contacts 

7.3kV 2kV 

Between relay contact groups 

7.3kV 

2kV 

between all circuits and accessible 
parts of the enclosure 

9.8kV 4kV 

Rated insulation voltage Ui 

400V

~

 

Ambient conditions  

Operating temperature 

 

-20...+60°C 

Storage temperature 
 

-30 ...+80°C 

Relative humidity 

<

90%  

(IEC/EN 60068-2-70) 

Maximum  pollution 

Degree 3 

Overvoltage category 

Climatic sequence 

Z/ABDM  

(IEC/EN 60068-2-61)

 

Shock resistance  

 (IEC/EN 60068-2-27)

 

Vibration resistance 

 (IEC/EN 60068-2-6)

 

Connections  

Type of terminals 

Fixed 

Conductor cross section 

0.2 - 4.0 mm

(24 - 12 AWG) 

Tightening torque 

0.8Nm   (7lbin) 

 

 

 

 

 

43.7mm

58.0mm

59.9mm

5.0mm

Summary of Contents for PMVF 10

Page 1: ... with a changeover contact According to reference standard requirements the PMVF 10 has the following protections o Overvoltage o Undervoltage o Overfrequency o Underfrequency o ROCOF Rate Of Change Of Frequency deactivable Dispone di soglie fisse d intervento di tensione Max e Min rispettivamente 1 13 Ue e 0 825 Ue E possibile selezionare il controllo delle tensioni fase fase oppure fase neutro T...

Page 2: ...e di impostare il funzionamento dell apparecchio secondo la seguente tabella NOTA La posizione A è quella che determina le impostazioni di default suggerite dalla guida ENEL Attenzione Lo spostamento del selettore 5 durante l operatività dello strumento potrebbe provocare interventi non desiderati Il potenziometro 6 permette l impostazione del tempo di ripristino per tutte le soglie Il tempo di de...

Page 3: ...remote trip contact in series with the PMVF 10 outputs Diagrammi di funzionamento Operating diagrams Tensione Voltage Frequenza Frequency Derivata di frequenza ROCOF 14 24 Relè Ue 12 22 11 21 ON Hz 500ms all alimentazione Ritardo ripristino Isteresi Hysteresis Isteresi Hysteresis Frequenza massima Frequenza minima Hz Ritardo MAX t 40ms Ritardo ripristino Ritardo ripristino Ritardo MIN ON Relè 11 2...

Page 4: ...Rete di distribuzione in bassa tensione Low voltage utility Generazione Power source Contact available for signalling auxiliary contactor or inverter stop Remote disconnection command L 11 14 12 TRMS 21 24 22 N L1 L2 L3 N K1 1 2 1 Contatto libero per utilizzo come segnalazione secondo contattore o blocco inverter 2 Dispositivo di interruzione remoto Rete di distribuzione in bassa tensione Low volt...

Page 5: ...sione 4 Sequenza climatica Z ABDM IEC EN 60068 2 61 Resistenza agli urti IEC EN 60068 2 27 Resistenza alle vibrazioni IEC EN 60068 2 6 Connessioni Tipo di terminali Fissi Sezione conduttori 0 2 4 0 mm2 24 12 AWG Coppia di serraggio 0 8Nm 7Lbin TECHNICAL CHACTERISTICS Control and power supply circuit Rated operational voltage Ue 400V 230V Rated frequency 50Hz Operating range 0 7 1 3 Ue Power consum...

Page 6: ...ologazioni Guida ENEL edizione 2 1 Dicembre 2010 Conformi alle norme IEC EN60255 5 IEC EN 61000 6 2 IEC EN 61000 6 3 Housing Version 3 modules DIN43880 Material Polyamide Mounting On 35mm DIN rail IEC EN60715 or by screws using extractible clips Degree of protection IP40 on front IP20 at terminals Weight 130g Certifications ENEL guide edition 2 1 December 2010 Compliant with standards IEC EN60255 ...

Reviews: