background image

I6

0

4

 G

B

 I

 0

9

 1

9

3

1

1

0

0

4

4

2

3

WIRING TEST

–    The wiring test allows to verify if the connection of the DMG5... device has been executed properly. 

–    To be able to execute the test, the device must be connected to an active plant, with the following conditions:

     • three-phase system with all phases presence (V > 50VAC PH-N)

     • current flowing in each phase > 1% of the CT primary.

     • positive flow of energies (that is a normal plant where the inductive load draws power from the supplier).

–    To launch test execution, enter command menu and select command C.16 as per Commands menu instructions.

–    The test allows to verify the following points:

     • reading of the three voltage phases.

     • phase sequence.

     • voltage unbalance.

     • reverse polarity of each CT. 

     • mismatch between voltage and current phases.

–    If the test does not succeed, the display shows the reason of the failure.

INSTALLATION

–    DMG5... is designed for flush-mount installation. With proper mounting, it guarantees IP40 front protection.

–    From inside the panel, for each four of the fixing clips, position the clip in one of the two sliding guide, then press on the clip corner until the second guide snaps in.

–    Push the clip forward pressing on its side and making it slide on the guides until it presses completely on the internal surface of the panel.

–    For the electrical connection see the wiring diagrams in the dedicated chapter and the requirements reported in the technical characteristics table.

Summary of Contents for DMG500

Page 1: ...f r die elektrische Sicherheit Die in dieser Brosch re beschriebenen Produkte k nnen jederzeit weiterentwickelt und ge ndert werden Die im Katalog enthaltenen Beschreibungen und Daten sind daher unver...

Page 2: ...n the alphanumeric disp lay scrolls a written description If you must enter the password the menu opens with the voice PAS already selected Press s t to select the desired item and then press to confi...

Page 3: ...g points reading of the three voltage phases phase sequence voltage unbalance reverse polarity of each CT mismatch between voltage and current phases If the test does not succeed the display shows the...

Page 4: ...l P01 07 L1 L2 L3 N BIL L1 L2 L3 BIL AUX SUPPLY A1 I1 S2 A2 VOLTAGE V1 VN V2 V3 S1 I3 I2 CURRENT 110 250VDC 100 440VAC L2 L3 L1 TA CT1 D TA CT2 O A L S2 S1 COM RS485 A B AUX SUPPLY A1 I1 S2 A2 VOLTAGE...

Page 5: ...485 I3 I2 I1 A VN V3 V2 V1 B A2 A1 Aux supply 100 240V 50 60Hz 1W 3VA V Input 100 480V 50 60Hz I Input 0 025 5A RS485 I3 I2 I1 A VN V3 V2 V1 B A2 A1 MECHANICAL DIMENSIONS AND FRONT PANEL CUTOUT mm 96...

Page 6: ...hase to neutral 0 5 50 415V 0 5 digit Voltage phase to phase 0 5 90 720V 0 5 digit Current 0 5 0 1 1 2In 0 5 digit Active Energy Class 1 IEC EN 62053 21 Reactive energy Class 2 IEC EN 62053 23 Additio...

Page 7: ...g f r die elektrische Sicherheit Die in dieser Brosch re beschriebenen Produkte k nnen jederzeit weiterentwickelt und ge ndert werden Die im Katalog enthaltenen Beschreibungen und Daten sind daher unv...

Page 8: ...La scelta selezionata lampeggia Nel display alfanumerico scorre una scritta descrittiva della scelta effettuata Se necessario impostare la password il menu si apre con la voce PAS gi selezionata Preme...

Page 9: ...a delle fasi sbilanciamento delle tensioni inversione della polarit di uno o pi TA scambio delle fasi fra tensioni correnti Se il test non viene superato il display visualizza la ragione dell errore I...

Page 10: ...L3 N BIL L1 L2 L3 BIL AUX SUPPLY A1 I1 S2 A2 VOLTAGE V1 VN V2 V3 S1 I3 I2 CURRENT 110 250VDC 100 440VAC L2 L3 L1 TA CT1 D TA CT2 O A L S2 S1 COM RS485 A B AUX SUPPLY A1 I1 S2 A2 VOLTAGE V1 VN V2 V3 S1...

Page 11: ...IA RS485 DMG5 n 1 Max 1200m DMG5 n 31 MASTER RS485 A B RS485 A B 120R RS485 A B 120R Aux supply 100 240V 50 60Hz 1W 3VA V Input 100 480V 50 60Hz I Input 0 025 5A RS485 I3 I2 I1 A VN V3 V2 V1 B A2 A1 A...

Page 12: ...Temperatura 23 C 2 C Tensione fase neutro 0 5 50 415V 0 5 digit Tensione fase fase 0 5 90 720V 0 5 digit Corrente 0 5 0 1 1 2In 0 5 digit Energia attiva Classe 1 IEC EN 62053 21 Energia reattiva Clas...

Reviews: