10

G

B

Connections - relay 

                                            

Terminal types                                                      Screw-type (fixed)

Wire cross-section (min and max)                       0.2...4 mm

2

(26...10 AWG)

Tightening torque                                                  0.8 Nm (7 lbin)

Type of conductor                                                 Use copper conductors only, 75°C

Connections – fan and digital inputs

                  

Terminal types                                                      Screw-type (fixed)

Wire cross-section (min and max)                       0.2 - 2.5 mm

2

(24 - 12 AWG)

Tightening torque                                                  0.44 Nm (4 lbin)

Type of conductor                                                 Use copper conductors only, 75°C

Power connections for DCTL size 1 and 2

          

Terminal types                                                      Fixed – double lock clamp

Wire cross-section (min and max)                       2 x 2,5-35mm

2

                                                                             2 x 18-2 AWG

Imprint                                                                  Hexagon socket head screw 4mm

Tightening torque for                                            4-5 Nm / 2.95-3.69 lbft
DCTLA 400 0075… DCTLA 400 0300, 
DCTLA 480 0090… DCTLA 480 0360                  

Tightening torque for                                            5.5-6.5 Nm / 4.06-4.79 lbft
DCTLA 400 0500, DCTLA 480 0600,                    
DCTLA 690 0300, DCTLA 690 0500                     

Type of conductor                                                 Use copper conductors only, 75°C

Power connections for DCTL size 3

                    

Type of bars                                                          25x5mm, hole diam. 11mm

Type of conductor                                                 Use copper conductors only, 75°C

Conductor section                                                 Max. 50mm

2

                                                                             1xAWG3/0 (for cULus compliance you must install 
                                                                             n°2 lugs kit code EXA01
                                                                             + n°2 terminal shrouds kit code EXA 02)

Imprint                                                                  Socket wrench 17mm

Tightening torque for                                            35 Nm / 310 in-lbs
DCTLA 400 1000, DCTLA 480 1200, 
DCTLA 690 1000                                                  

Tightening torque for lugs EXA01                         42 Nm / 375 in-lbs

Housing

                                                                

Installation                                                            Internal panel version

Material                                                                 Polycarbonate RAL 7035

Degree of protection                                             IP00

Mounting                                                              Screw fixing or DIN-rail (IEC/EN60715) via optional 

                                                                             accessory EXP8003 (only for mechanical sizes 1 and 2)

Weight

DCTLA 400 0075, DCTLA 400 0150,                    1.74kg
DCTLA 400 0300, DCTLA 480 0090, 
DCTLA 480 0180, DCTLA 480 0360

DCTLA 400 0500, DCTLA 480 0600,                    2.84Kg
DCTLA 690 0300, DCTLA 690 0500

DCTLA 400 1000, DCTLA 480 1200,                    6.68kg
DCTLA 690 1000                                                  

Approvals and conformity

                                   

Pending approvals                                                cULus for DCTLA 480… and DCTLA 600…

                                                                             EAC for all DCTL… codes

Conformity to standards                                       IEC/EN 60947-4-3, IEC/EN 61000-6-2, 

                                                                             IEC/EN 61000-6-4

TECHNICAL CHARACTERISTICS

Auxiliary supply: terminals A1-A2

Us rated voltage                                                    100 - 240VAC

Operating range                                                    90 - 264VAC

Frequency                                                             45 - 66 Hz

Drawn/dissipated power                         Size 1     100-240VAC 4,6W 11,8VA

                                                              Size 2     100-240VAC 5,8W 14,1VA

                                                              Size 3     100-240VAC 5,8W 14,1VA

Capacitor bank supply voltage: terminals L1 – L2 – L3

Us rated voltage                                                    400VAC for DCTLA 400...

                                                                             400...480VAC for DCTLA 480...
                                                                             600…690VAC for DCTLA 690...

Operating range                                                    340…440VAC for DCTLA 400..

                                                                             340…528VAC for DCTLA 480…
                                                                             340…759VAC for DCTLA 690…

Frequency range                                                   45-65Hz

Rated current and power                                      (see table POWER RATINGS)

Control input: terminals C/-                

Us rated voltage                                                    12-24VDC

Operating range                                                    8...30VDC

Digital input: terminals C - IN1

Input type                                                             Negative

Applied voltage at contact                                     5VDC (provided by DCTL)

Input current                                                         

10mA

Low input signal                                                   

0,8V

High input signal                                                   

3,2V

Input signal delay                                                  

50ms

NTC probe input: terminals NTC - NTC

Type of sensor                                                      NTC (Lovato code NTC01)

Measuring range                                                   -25…+85°C

Maximum connection length                                3mt

Fan power supply: terminals FAN + / -

Voltage supply                                                      5VDC (provided by DCTL)

                                                                             Don’t apply any voltage on the terminals FAN +/-!

Fan type                                                                The fans are integrated as standard (one on 

                                                                             mechanical size 1, two on size 2 and 3). 
                                                                             In case of replacement use exclusively EXP8004 
                                                                             accessory

Output OUT1: terminals 11-12-14

Contact type                                                          1 NO/NC changeover contact

Operating voltage                                                  250VAC

Rating                                                                   NO contact AC1 5A-250VAC 5A 30VDC

                                                                             NC contact AC1 3A-250VAC 3A 30VDC

UL use data                                                           D300

Maximum usage voltage                                       250VAC

Electrical life                                                         NC contact – 10x10

3

operations

                                                                             NO contact – 20x10

3

operations

Mechanical life                                                      10

7

operations

Insulation voltage

                                                

Rated insulation voltage Ui                                   480VAC for DCTLA 400... and DCTLA 480...

                                                                             690VAC for DCTLA 690...

Rated impulse withstand voltage Uimp                4kV for DCTLA 400... and DCTLA 480...

                                                                             6kV for DCTLA 690...

Ambient operating conditions

                             

Operating temperature                                          -20...+45°C without derating

Storage temperature                                             -30...+80°C

Relative humidity                                                  <80% (IEC/EN 60068-2-78)

Pollution degree                                                    2

Overvoltage category                                            III

Maximum altitude                                                 2000m without derating

Climate sequence                                                  Z/ABDM (IEC/EN 60068-2-61)

Shock resistance                                                   15g (IEC/EN 60068-2-27)

Vibration resistance                                              0.7g (IEC/EN 60068-2-6)

GB

I580 

GB 

07 

19

                                               31100419

MANUAL REVISION HISTORY

 Rev                              Date                             Notes

 00                                28/09/2018                  – First release

Summary of Contents for DCTL Series

Page 1: ...zugänglich sein Er muss als Trennvorrichtung für das Gerät gekennzeichnet sein IEC EN 61010 1 6 11 3 1 Das Gerät mit einem weichen Tuch reinigen keine Scheuermittel Flüssigreiniger oder Lösungsmittel verwenden ADVERTENCIA Leer atentamente el manual antes de instalar y utilizar el regulador Este dispositivo debe ser instalado por personal cualificado conforme a la normativa de instalación vigente a...

Page 2: ...he built in infrared port and or NFC communication using the same hardware and software tools used for other Lovato devices CX01 CX02 dongles Xpress software LOVATO SAM1 App or LOVATO NFC App DESCRIPTION 3 status LEDs for the signalling of presence of power operating and fault 2 phase controlled switching Monitoring of the current flowing into the capacitor bank through built in current transforme...

Page 3: ...SAM1 App available for tablet and smartphone Android or iOS and the CX02 Wi Fi adapter to connect to the DCTL via its front optical port The App can be used to view alarms send commands read measurements set parameters download events and send collected data via e mail PARAMETER SETTING FROM SMARTPHONE OR TABLET WITH NFC You can use the LOVATO NFC App available for Android tablets and smartphones ...

Page 4: ...ontrol relay energized when the heatsink temperature is rising Activation of the relay follows the activation of internal fan P01 06 Normal status of the relay output Allows to reverse the logic of the output function Available from firmware version 2 M02 PROTECTIONS Cod Description UoM Default Range P02 01 Max current threshold In 120 OFF 100 150 P02 02 Max voltage threshold Un OFF OFF 100 150 P0...

Page 5: ...inside the panel clean filters and check cooling fan A02 External sensor overtemperature The temperature read by external NTC sensor has rised above the value set in parameter P02 04 A03 Cooling fan failure The integrated cooling fan is not working properly either not connected not drawing current or jammed too high current Check fan wiring and functioning Replace fan if necessary use EXP8004 acce...

Page 6: ...n chocked and unchoked capacitor banks It is important to keep in mind in unchoked capacitor banks that the modules can be destroyed by current transients caused by fast voltage fluctuations Also in chocked bank it is imperative to control that the current values do not exceed the maximum current rating of each module Thyristor modules switch without inrush current and provide smooth disconnection...

Page 7: ...tion is possible to monitor from the display of DCRG8F controller the status and the measures of each DCTL thyristor module For information about the programming refer to the technical manual of DCRG8F instruction I564 downloadable from the website www LovatoElectric com Note The EXP1012 mounted on DCRG8F controller is dedicated for the command of DCTL thyristor modules If necessary to connect the...

Page 8: ...171 5 56 206 SIZE 2 DCTLA 400 0500 DCTLA 480 0600 DCTLA 690 0300 DCTLA 690 0500 SIZE 3 DCTLA 400 1000 DCTLA 480 1200 DCTLA 690 1000 212 195 90 25 Ø10 60 216 97 154 275 301 DCTLA 400 1000 DCTLA 480 1200 DCTLA 690 1000 complete with terminal lugs kit for cULus EXA01 2pcs and terminals shrouds kit EXA02 2pcs 95 71 Ø5 40 182 214 226 468 301 128 175 212 216 80 137 148 ...

Page 9: ...00 480 480 480 480 480 690 690 690 0075 0150 0300 0500 1000 0090 0180 0360 0600 1200 0300 0500 1000 Rated operating voltage Us 400VAC 50 60Hz 400 480VAC 50 60Hz 600 690VAC 50 60Hz Rated current Ie 11A 22A 43A 72A 144A 11A 22A 43A 72A 144A 29A 48A 96A Step power 400VAC 7 5kvar 15kvar 30kvar 50kvar 100kvar 7 5kvar 15kvar 30kvar 50kvar 100kvar 20kvar 33kvar 67kvar 440VAC 8kvar 16 5kvar 33kvar 55kvar ...

Page 10: ...als A1 A2 Us rated voltage 100 240VAC Operating range 90 264VAC Frequency 45 66 Hz Drawn dissipated power Size 1 100 240VAC 4 6W 11 8VA Size 2 100 240VAC 5 8W 14 1VA Size 3 100 240VAC 5 8W 14 1VA Capacitor bank supply voltage terminals L1 L2 L3 Us rated voltage 400VAC for DCTLA 400 400 480VAC for DCTLA 480 600 690VAC for DCTLA 690 Operating range 340 440VAC for DCTLA 400 340 528VAC for DCTLA 480 3...

Page 11: ...ugänglich sein Er muss als Trennvorrichtung für das Gerät gekennzeichnet sein IEC EN 61010 1 6 11 3 1 Das Gerät mit einem weichen Tuch reinigen keine Scheuermittel Flüssigreiniger oder Lösungsmittel verwenden ADVERTENCIA Leer atentamente el manual antes de instalar y utilizar el regulador Este dispositivo debe ser instalado por personal cualificado conforme a la normativa de instalación vigente a ...

Page 12: ...orta ottica a infrarossi integrata e o tramite connettività NFC utilizzando gli stessi strumenti hardware e software utilizzati per gli altri dispositivi Lovato Electric connettori CX01 CX02 software Xpress App LOVATO SAM1 o App LOVATO NFC DESCRIZIONE 3 LED di stato per segnalazione presenza di alimentazione comando attivo intervento di una protezione 2 fasi controllate Monitoraggio della corrente...

Page 13: ...hone Android o iOS e l adattatore Wi Fi CX02 è possibile collegarsi al DCTL attraverso la porta ottica frontale L App permette di visualizzare allarmi inviare comandi leggere misure impostare parametri scaricare gli eventi e inviare i dati raccolti via e mail IMPOSTAZIONE PARAMETRIC DA SMARTPHONE O TABLET CON NFC Mediante l App LOVATO NFC disponibile per smart devices Android smartphone e tablet è...

Page 14: ...uando un allarme è attivo Comando ventola relè eccitato quando la temperatura del dissipatore sta crescendo L attivazione del relè segue l attivazione della ventola integrata P01 06 Stato a riposo dell uscita Permette di invertire la logica di funzionamento dell uscita Disponibile da versione firmware 2 M02 PROTEZIONI Cod Descrizione UdM Default Range P02 01 Soglia di massima corrente In 120 OFF 1...

Page 15: ...temperatura sensore esterno La temperatura letta dalla sonda NTC esterna ha superato il limite programmato in P02 04 A03 Guasto ventola di raffreddamento La ventola di raffreddamento integrata non funziona correttamente potrebbe non essere connessa non passa corrente o bloccata corrente troppo alta Verificare il collegamento della ventola e il funzionamento Se necessario sostituire la ventola codi...

Page 16: ...se in batterie di condensatori con oppure senza induttanze di filtro È importante tenere in considerazione che con i condensatori senza induttanze di filtro i moduli possono essere distrutti dai transitori di corrente dovuti alle variazioni rapide di tensione Anche nei condensatori con induttanze di filtro è indispensabile controllare che la corrente non superi il valore massimo di corrente di cia...

Page 17: ...igurazione è possibile monitorare dal display del regolatore DCR8GF lo stato e misure di ogni modulo a tiristori DCTL Per informazioni relative alla programmazione fare riferimento al manuale tecnico del regolatore DCRG8F istruzione I564 scaricabile dal sito web www LovatoElectric com Nota Il modulo EXP1012 montato sul regolatore DCRG8F è dedicato al comando dei moduli a tiristori DCTL Se necessar...

Page 18: ... 56 206 TAGLIA 2 DCTLA 400 0500 DCTLA 480 0600 DCTLA 690 0300 DCTLA 690 0500 TAGLIA 3 DCTLA 400 1000 DCTLA 480 1200 DCTLA 690 1000 212 195 90 25 Ø10 60 216 97 154 275 301 DCTLA 400 1000 DCTLA 480 1200 DCTLA 690 1000 completi con kit terminali per omologazione cULus EXA01 2pz e kit protezione terminali EXA02 2pz 95 71 Ø5 40 182 214 226 468 301 128 175 212 216 80 137 148 ...

Page 19: ...144A 11A 22A 43A 72A 144A 29A 48A 96A Potenza gradino 400VAC 7 5kvar 15kvar 30kvar 50kvar 100kvar 7 5kvar 15kvar 30kvar 50kvar 100kvar 20kvar 33kvar 67kvar 440VAC 8kvar 16 5kvar 33kvar 55kvar 110kvar 22kvar 37kvar 73kvar 480VAC 9kvar 18kvar 36kvar 60kvar 120kvar 24kvar 40kvar 80kvar 525VAC 26kvar 44kvar 87kvar 600VAC 30kvar 50kvar 100kvar 690VAC 30kvar 50kvar 100kvar Tensione inversa massima 1800V...

Page 20: ... dissipata Taglia 1 100 240VAC 4 6W 11 8VA Taglia 2 100 240VAC 5 8W 14 1VA Taglia 3 100 240VAC 5 8W 14 1VA Tensione di alimentazione del banco di condensatori terminali L1 L2 L3 Tensione nominale Us 400VAC per DCTLA 400 400 480VAC per DCTLA 480 600 690VAC per DCTLA 690 Limiti di funzionamento 340 440VAC per DCTLA 400 340 528VAC per DCTLA 480 340 759VAC per DCTLA 690 Frequenza 45 65Hz Corrente e po...

Reviews: