![LOVATO ELECTRIC TMM1 NFC User Manual Download Page 5](http://html1.mh-extra.com/html/lovato-electric/tmm1-nfc/tmm1-nfc_user-manual_1942185005.webp)
Doc: I562EGB07_18 ok.docx 13/09/2018
p. 5 / 17
Funciones
A
Activación retardada del relé
Parámetro
Descripción
Modo de reinicio
P01.06
No produce efecto (con independencia de que se configure en INP o PWR; para reanudar la
función es preciso apagar y volver a encender el temporizador).
Contador predefinido
P02.01
No produce efecto (tras T1, la salida permanece activa hasta que se desconecta la
alimentación del temporizador).
Functions
A
On delay
Parameter
Description
Reset mode
P01.06
This parameter has no effect (independently from the setting INP or PWR, to restart the
function is necessary to turn off and on the power supply of the timer).
Preset counter
P02.01
This parameter has no effect (after the time T1 the output remains energised until you remove
the power supply to the timer).
At
Activación retardada del relé con opción de pausa mediante
contacto
Parámetro
Descripción
Modo de reinicio
P01.06
No produce efecto (con independencia de que se configure en INP o PWR; para reanudar la
función es preciso apagar y volver a encender el temporizador).
Contador predefinido
P02.01
No produce efecto (tras T1, la salida permanece activa hasta que se desconecta la
alimentación del temporizador).
At
On delay with optional pause with contact
Parameter
Description
Reset mode
P01.06
This parameter has no effect (independently from the setting INP or PWR, to restart the
function is necessary to turn off and on the power supply of the timer).
Preset counter
P02.01
This parameter has no effect (after the time T1 the output remains energised until you remove
the power supply to the timer).
Ac
Activación retardada del relé cuando se cierra un contacto
Parámetro
Descripción
Modo de reinicio
P01.06
INP = la función se ejecuta cada vez que se cierra la entrada de comando (S).
PWR = la función se ejecuta una sola vez y cuando termina de realizarse, se ignoran los
nuevos cierres de la entrada de comando (S). Para reanudar la función es necesario apagar
y encender de nuevo el temporizador.
Contador predefinido
P02.01
Cuando la salida de relé se cierra tantas veces como se ha configurado en P02.01, el
temporizador permanece "bloqueado" (se ignoran los nuevos cierres de la entrada de
comando S). Para realizar de nuevo la función hay que apagar y volver a encender el
temporizador.
Ac
On delay, start from contact
Parameter
Description
Reset mode
P01.06
INP = every time you close the command input S the function is performed.
PWR = the function is performed just one time, after that, new closures of the command input
S are ignored and to perform again the function is necessary to turn off and on the power
supply of the timer.
Preset counter
P02.01
When the number of the closures of the relay output reaches the value set in P02.01, the
timer goes into a “lock” status and is no longer possible to perform the function (new closures
of the command input S are ignored). To restart to perform the function is necessary to turn
off and on the power supply of the timer.
Al
Activación retardada del relé cuando se cierra un contacto,
rearmable
Parámetro
Descripción
Modo de reinicio
P01.06
INP = la función se ejecuta cada vez que se cierra la entrada de comando (S).
PWR = la función se ejecuta una sola vez y cuando termina de realizarse, se ignoran los
nuevos cierres de la entrada de comando (S). Para reanudar la función es necesario apagar
y encender de nuevo el temporizador.
Preselección del
contador
P02.01
Cuando la salida de relé se cierra tantas veces como se ha configurado en P02.01, el
temporizador permanece "bloqueado" (se ignoran los nuevos cierres de la entrada de
comando S). Para realizar de nuevo la función hay que apagar y volver a encender el
temporizador.
Al
On delay, start from contact, reloadable
Parameter
Description
Reset mode
P01.06
INP = every time you close the command input S the function is performed.
PWR = the function is performed just one time, after that, new closures of the command input
S are ignored and to perform again the function is necessary to turn off and on the power
supply of the timer.
Preset counter
P02.01
When the number of the closures of the relay output reaches the value set in P02.01, the
timer goes into a “lock” status and is no longer possible to perform the function (new closures
of the command input S are ignored). To restart to perform the function is necessary to turn
off and on the power supply of the timer.