I352
GB
I
10
14
31100171
6
GB
SSR output OUT3 - OUT 4 (+ battery voltage output)
Type of output 4 x 1 NO + one common terminal
Rated voltage 12-24V= from battery
Rated current 2A DC1 each
Protection Overload, short circuit and reverse polarity
Relay output OUT 8 (voltage free)
Type of contact 1 changeover
UL Rating B300 / 30V= 1A Pilot Duty
Rated voltage 250V~
Rated current at 250VAC 8A AC1 (1,5A AC15)
Relay output OUT 9 (voltage free)
Type of contact 1 NC (mains contactor)
UL Rating B300 / 30V= 1A Pilot Duty
Rated voltage 250V~ (400V~ max)
Rated current at 250VAC 8A AC1 (1,5A AC15)
Relay output OUT 10 (voltage free)
Type of contact 1 NO (generator contactor)
UL Rating B300 / 30V= 1A Pilot Duty
Rated voltage 250V~ (400V~ max)
Rated current at 250VAC 8A AC1 (1,5A AC15)
Communication Lines
RS232 Serial interface Not isolated
Baud-rate programmable 1200…115200 bps
CAN bus interface Not isolated …...
Insulation
Rated insulation voltage Ui 600V~
Rated impulse withstand voltage Uimp 9.5kV
Power frequency withstand voltage 5,2kV
Ambient conditions
Operating temperature -30 - +70°C
Storage temperature -30 - +80°C
Relative humidity <80% (IEC/EN 60068-2-78)
Maximum pollution degree 2
Overvoltage category 3
Measurement category III
Climatic sequence Z/ABDM (IEC/EN 60068-2-61)
Shock resistance 15g (IEC/EN 60068-2-27)
Vibration resistance 0.7g (IEC/EN 60068-2-6)
Connections
Terminal type Plug-in / removable
Conductor cross section (min… max) 0.2…2.5 mm² (24…12 AWG)
UL Rating
Conductor cross section (min… max) 0,75…2.5 mm² (18…12 AWG)
Tightening torque 0.56 Nm (5 lbin)
Housing
Version Flush mount
Material Polycarbonate
Degree of protection IP65 on front – IP20 terminals
Weight 880g for RGK700;
900g for RGK700SA
Certifications and compliance
Certifications obtained cULus
UL Marking Use 60°C/75°C copper (CU) conductor only
AWG Range: 24 - 12 AWG stranded or solid
Field Wiring Terminals Tightening Torque: 5lb.in
For use on a flat surface of a type 4X enclosure
Tighting torque used for fixing screw =0.5Nm
Comply with standards IEC/EN 61010-1, IEC/EN 61000-6-2,
IEC/ EN 61000-6-3, UL508, CSA C22.2 N°14
TECHNICAL CHARACTERISTICS
Supply
Battery rated voltage 12 or 24V= indifferently
Maximum current consumption 400mA at 12V= and 200mA at 24V=
Maximum power consumption/dissipation 4.8W
Voltage range 7…33V=
Minimum voltage at the starting 5.5V=
Stand-by current 70mA at 12V= and 40mA at 24V=
Micro interruption immunity 150ms
Digital inputs
Input type Negative
Current input
≤
10mA
Input “low” voltage
≤
1.5V (typical 2.9V)
Input “high” voltage
≥
5.3V (typical 4.3V)
Input delay see P18.n.04 - P18.n.05 parameters
Analog inputs
Pressure sensor Current 10mA = max
Measuring range 0 - 450
Ω
Temperature sensor Current 10mA = max
Measuring range 0 - 1350
Ω
Fuel level sensor Current 10mA = max
Measuring range 0 - 1350
Ω
Speed input “W”
Input type AC coupling
Voltage range 2.4…75Vpp
Frequency range 40…2000Hz
Pick-up input
Input type AC coupling
Voltage range High sensitivity: 1.6...60Vpp – 0.6...21VRMS
Low sensitivity: 4.8...150Vpp – 1.7...53VRMS
Frequency range 20Hz...10000Hz
Measuring input impedance >100k
Ω
Engine running input (500rpm) for permanent magnet alternator
Input type AC coupling
Voltage range 0…44V~
Engine running input (500rpm) for pre-excited alternator
Voltage range 0…44V=
Maximum input current 12mA
Maximum voltage at +D terminal 12 or 24V= (battery voltage)
Pre-excitation current ( 42 terminal) 230mA 12V= – 130mA 24V=
Mains and generator voltage inputs
Maximum rated voltage Ue 600V~ L-L (346V~ L-N)
Measuring range 50…720V L-L (415V~ L-N)
Frequency range 45…65Hz – 360…440Hz
Measuring method True RMS
Measuring input impedance > 0.55M
Ω
L-N
> 1,10M
Ω
L-L
Wiring mode Single-phase, two-phase, three-phase with or without
neutral or balanced three-phase system.
Current inputs
Rated current Ie 1A~ or 5A~
Measuring range for 5A scale: 0.010 - 6A~
for 1A scale: 0.010 – 1.2A~
Type of input Shunt supplied by an external current
transformer (low voltage). Max. 5A
Measuring method True RMS
Overload capacity +20% Ie
Overload peak 50A for 1 second
Power consumption <0.6VA
Measuring accuracy
Mains and generator voltage ±0.25% f.s. ±1digit
SSR output OUT1 and OUT 2 (+ battery voltage output)
Type of output 2 x 1 NO + one common terminal
Rated voltage 12-24V= from battery
Rated current 2A DC1 each
Protection Overload, short circuit and reverse polarity