LOVATO ELECTRIC ADXN Series Instruction Manual Download Page 6

I651 

GB 

03 

22

                                                 31100488

6

7.      PROTECTIONS

All the soft starters ADXN integrate the protection against overtemperature, measured by an integrated temperature sensor. 

The versions provided with NFC connectivity (ADXNF and ADXNP) provides additional functions dedicated to the protection of the motor and the soft starter itself, some of which are programmable.

The following table summarizes the protections available in the different versions and their associated parameters and alarms.

For information about the configuration of the protection thresholds and tripping delays of the soft starters type ADXNF and ADXNP please refer to the menu M03 PROTECTIONS.

7.1    ENABLING THE PHASE SEQUENCE CONTROL (ADXNB)

To enable phase sequence control on basic soft starters type ADXNB follow the procedure below.

Enabling of the phase sequence control:

as soon as the soft starter is powered up, when the LEDs have stopped flashing, turn quickly the central potentiometer (acceleration ramp) to the maximum value of its

scale (20), then turn it to the minimum value (1) and then again to the maximum value (20) and then to minimum value (1).

After this operation, the activation of the phase sequence control is signaled by a short flash of the green LED RUN (~1 second). Now set the desired acceleration ramp time with the dedicated potentiometer

‘acceleration ramp’.

Disabling of the phase sequence control:

repeat the same procedure followed for the activation of the phase sequence control: as soon as the soft starter is powered up, when the LEDs have stopped flashing,

turn quickly the central potentiometer (acceleration ramp) to the maximum value of its scale (20), then turn it to the minimum value (1) and then again to the maximum value (20) and then to minimum value (1).

After this operation, the de-activation of the phase sequence control is signaled by a short flash of the red LED ALARM (~1 second). Now set the desired acceleration ramp time with the dedicated potentiometer

‘acceleration ramp’.

7.2    MOTOR THERMAL OVERLOAD PROTECTION

The advanced soft starter type ADXNP is provided with electronic current thermal overload protection of the motor, programmable with the menu M03 PROTECTIONS.

– The electronic thermal overload protection (if enabled with parameter P03.09=ON) trips when the motor thermal status overcomes the limit of the set thermal overload class, with consequent trip of the alarm   A10

Motor thermal overload protection.

– The tripping delays may vary according to the overload current and are defined in the charts illustrated below. 

– The curves for the various charts refer to the thermal protection class selected with parameters P03.10 (starting thermal protection class) and P03.11 (running thermal protection class), configurable between the

class 10, 15, 20 and 25. 

– The cold trip curves indicate the trip delay starting from thermal status 0%, while the hot trip curves start from thermal status 100% (motor running stably at rated current and voltage).

– With the motor stopped, the motor thermal status will tend to zero in a set time which depends on the configured thermal protection class.

– The motor thermal overload protection alarm can be reset when the motor thermal status falls to or below the value of P03.12 (motor thermal overload protection reset), which has a default value of 120%. This

value can be modified for specific needs, without changing the trip delay in any way. 

 PROTECTION                                                               MOTOR (MOT) /         PARAMETERS                                                                     ALARM                        ADXNB                         ADXNF                         ADXNP

                                                                                 SOFT STARTER (STA)

 Line voltage not present                                                       MOT                  –                                                                                            A01                               

                                

                                 

 Phase loss                                                                            MOT                  –                                                                                            A02                               

                                

                                 

 Wrong phase sequence                                                        MOT                  P03.01                                                                                   A03                            

(*)                              

                                 

 Frequency out of limits                                                         MOT                  –                                                                                            A04                               

                                

                                 

 Voltage out of limits                                                              MOT                  P03.02-P03.03-P03.04-P03.05                                             A05                                –                                  

                                 

 Soft starter thermal protection (overtemperature)                 STA                   –                                                                                            A06                               

                                

                                 

 Temperature sensor fault                                                       STA                   –                                                                                            A07                               

                                

                                 

 Bypass relay fault                                                                  STA                   –                                                                                            A08                               

                                

                                 

 System error                                                                          STA                   –                                                                                            A09                               

                                

                                 

 Motor current thermal overload protection                           MOT                  P03.09-P03.10-P03.11-P03.12                                             A10                                –                                  –                                  

 Overcurrent                                                                       MOT-STA              –                                                                                            A11                                –                                  –                                  

 Locked rotor                                                                      MOT-STA              –                                                                                            A12                                –                                  –                                  

 Load too low                                                                         MOT                  P03.13-P03.14                                                                      A13                                –                                  –                                  

 Current asymmetry                                                               MOT                  P03.18-P03.19                                                                      A14                                –                                  –                                  

 Starting time too long                                                           MOT                  P03.17                                                                                   A15                                –                                  –                                  

 Phase shorted                                                                        STA                   –                                                                                            A16                                –                                  –                                  

For information about the meaning and causes of the alarms see the chapter 10 ALARMS. 

(*) To enable the phase sequence control (disabled as default) on the basic version ADXNB see the chapter 7.1.

7.3    SOFT STARTER THERMAL PROTECTION

The soft starter thermal protection is realized by monitoring the temperature of the internal thyristors with a built-in analog sensor. At the reaching of the maximum temperature there is the trip of the alarm A06 Soft

starter thermal protection. The alarm resets automatically when the soft starter returns to an acceptable temperature.

Cold trip curves

Hot trip curves

G

B

Summary of Contents for ADXN Series

Page 1: ...nagement of the starting and stopping ramps 4 5 2 Management of starting ramps with current limit only for ADXNP 5 6 Functional diagram 5 7 Protections 6 7 1 Enabling the phase sequence control ADXNB...

Page 2: ...Fi CX02 for programming data download and diagnostic from a PC or App The following table shows the main differences between the functions of the three versions 2 GENERAL CHARACTERISTICS 2 phase cont...

Page 3: ...tatus LEDs Relay outputs 2 x 1NO 3 potentiometers for basic settings starting voltage 30 80 Ue acceleration ramp 1 20s deceleration ramp 0 20s Auxiliary supply voltage A1 A2 and start input ST Status...

Page 4: ...For instance setting a deceleration ramp time of 10 seconds and an end of deceleration step of 20 the actual deceleration time will be 10 seconds minus the contribution of the end of deceleration step...

Page 5: ...en setting this parameter If this situation occurs it will trip the protection for starting time too long or the motor thermal overload protection 6 FUNCTIONAL DIAGRAM Here below it is represented the...

Page 6: ...abled with parameter P03 09 ON trips when the motor thermal status overcomes the limit of the set thermal overload class with consequent trip of the alarm A10 Motor thermal overload protection The tri...

Page 7: ...e against the ADXN front panel it is possible to read or write the parameters Conditions for the operation The smart device must be provided with NFC connectivity which must be activated and the smart...

Page 8: ...ew seconds will be heard a beep 6 At the device recognition the Home Page of the LOVATO NFC App shows the information about the detected device 7 Press the button to access to the ADXN parameters menu...

Page 9: ...hic widgets view live charts to monitor the trends of the electric measures in real time With the Wi Fi device CX02 it is also possible to connect the soft starter ADXNP to the LOVATO SAM1 App freely...

Page 10: ...d V OFF OFF 170 760 P03 03 Minimum voltage trip delay s 5 0 600 P03 04 Maximum voltage threshold V OFF 170 760 OFF P03 05 Maximum voltage trip delay s 5 0 600 P03 06 Alarm reset mode STOP STOP START P...

Page 11: ...against pumps dry running or to detect failure of transmission chains or belts When the torque is lower than this setting after the delay set in P03 14 the alarm A13 Load too low is generated The trip...

Page 12: ...that the current limitation remains active for a time too long a symptom of a mechanical problem A starting time longer than this setting cause the alarm A15 Starting time too long P03 18 P03 19 Contr...

Page 13: ...start input ST is closed after the delay P03 08 the alarm is reset and the soft starter performs a restart attempt This operation is repeated up to a maximum number of attempts specified in P03 07 Wit...

Page 14: ...ont for the connection of the optional RS485 communication module code CX04 compatible with both type ADXNP auxiliary supply voltage 100 240VAC and ADXNP 24 auxiliary supply voltage 24VAC DC With this...

Page 15: ...imum instantaneous current 10 Unsigned long F94h 2 Status Unsigned integer FB0h 2 Motor thermal status Unsigned long FB2h 2 Thyristors temperature C 10 Signed long 2100h 1 ST start input status bool U...

Page 16: ...e capacitors connection can be controlled with a relay output of the soft starter programmed with function TOR Top Of Ramp Do not perform high potential dielectric test on the soft starter In case of...

Page 17: ...6 26 149 5 87 128 4 5 05 45 1 77 35 1 38 2 3 0 09 6 7 0 26 ADXN 025 ADXN 045 31 1 22 23 7 0 93 CX04 45 1 77 35 1 38 2 3 0 09 139 5 47 129 5 08 113 4 4 46 6 7 0 26 ADXNP006 ADXNP018 with CX04 RS485 com...

Page 18: ...elation 1HP kW 1 36 19 CHOOSING THE SOFT STARTER Number of starts hour WITHOUT FAN In 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 3A ADXN006 6A ADXN006 ADXN012 9A ADXN012 ADXN018 12A A...

Page 19: ...OORDINATION WITH THERMAL OVERLOAD RELAY ADXNB AND ADXNF The soft starter type ADXNB and ADXNF don t integrated the function of motor thermal overload protection which is present instead in the advance...

Page 20: ...he drillings Soft starter Motor protection MPCB thermal trip Maximum voltage circuit breaker MPCB adjustment range VAC ADXN 006 SM1R0650 4 6 5 600 ADXN 012 SM1R1400 9 14 600 ADXN 018 SM1R1800 13 18 60...

Page 21: ...C 15 10 Rated frequency 50 60Hz 5 Drawn dissipated power ADXN 100VAC 45mA 1 70W 6 18A 240VAC 27mA 2 40W w o fan 24VAC 135mA 1 85W 24VDC 75mA 1 80W ADXN 100VAC 55mA 2 55W 25 30A 240VAC 33mA 3 20W w o f...

Reviews: