background image

I651 

GB 

03 

22

                                                 31100488

13

10     ALARMS

–    When an alarm occurs, the red ALARM LED on the front will blink for as long as an alarm is active. The number of the flashes identify the type of alarm in progress (i.e. 1 flash = alarm A01, 2 flashes = alarm A02,

3 flashes = alarm A03, and so on). The meaning of the alarm is described in the Alarm table.

–    As default, most of the protections are set to OFF. To enable them, it is necessary to set the relative parameter (see menu M03 PROTECTIONS).

–    Some alarms cause the stop of the motor, while others are just signaled but the motor continues to run.

–    The alarms reset can be configured independently as automatic or manual. In case of manual reset, the reset of the alarm must be performed by the user according to the reset mode set in P03.06. 

–    In automatic mode, the reset of the alarm is performed when the alarm conditions cease, according with the settings of the menu M03 PROTECTIONS.

The meaning of the properties that can be associated with the alarms is described below

–    

enabled alarm

- Alarm enable. If not enabled, it’s like it does not even exist

–    

retaining alarm

- This remains stored even if its cause was removed

–    

global alarm

- This activates the output assigned to this function

–    

stop motor

– in case of active alarm the motor is stopped

–    

deceleration

– If deceleration is programmed, stops the motor with a deceleration. If the property is not enabled, the motor stops immediately with free wheel

–    

auto reset

– The alarm can be reset automatically depending on the criteria defined in P03.07 and P03.08.

10.1  ALARMS PROPERTIES TABLE

The following table shows the alarm codes, with a description and the default properties of each one. The properties can be modified on the ADXNF version with LOVATO NFC App and on the ADXNP version with

LOVATO NFC App or SAM1 App or Xpress software.

On the basic version ADXNB the alarms properties are fixed according to the following table, except for the wrong phase sequence alarm (A03) which is disabled as default and can be enabled by following the

sequence described at chapter 7.1 Enabling the phase sequence control (ADXNB).

Note. The alarms from A10 to A16 are available only on the advanced version ADXNP. Refer to the table at chapter 7.PROTECTIONS to check the alarms available on each version of ADXN.

           ALARM                                                                                  DESCRIPTION

             

CODE

              A01                   NO POWER LINE                                                                                                                                                                                

              

              

            

 

                              

              A02                   PHASE LOSS                                                                                                                                                                                      

              

              

            

 

                              

              A03                   WRONG PHASE SEQUENCE                                                                                                                                                               

              

              

            

                              

              A04                   FREQUENCY OUT OF LIMITS                                                                                                                                                              

              

              

            

 

                              

              A05                   VOLTAGE OUT OF LIMITS                                                                                                                                                                   

              

              

            

                              

              A06                   SOFT STARTER THERMAL PROTECTION                                                                                                                                           

                                

            

            

                

              A07                   TEMPERATURE SENSOR FAULT                                                                                                                                                         

              

              

                                                    

              A08                   BYPASS RELAY FAILURE

                                                                                                                                                              

              

              

            

 

             

              A09                   SYSTEM ERROR                                                                                                                                                                                 

                                                                                        

              A10                   MOTOR THERMAL OVERLOAD PROTECTION                                                                                                                                    

              

              

            

            

                

              A11                   OVERCURRENT PROTECTION

                                                                                                                                                       

              

              

            

                               

              A12                   LOCKED ROTOR                                                                                                                                                                                 

              

              

            

                               

              A13                   LOAD TOO LOW                                                                                                                                                                                  

              

              

            

            

              

              A14                   CURRENT ASIMMETRY                                                                                                                                                                      

              

              

            

            

              

              A15                   STARTING TIME TOO LONG                                                                                                                                                               

              

              

            

            

                

              A16                   PHASE SHORTED

                                                                                                                                                                          

              

              

            

 

                               

  

The properties of these alarms are fixed and cannot be modified.

  

NOTE. For the alarms related to the line voltage A01, A02, A03, A04 and A05, the properties 'retentive' and 'automatic reset' work according to the following logic.

     –    With the property 'retentive' enabled (ON):

          –   if the property 'automatic reset'= OFF, the alarm remains active as long as the start input ST is closed, even if the condition that generated it ceases.

          –   if the property 'automatic reset' = ON, if the start input ST is closed, after the delay P03.08 the alarm is reset and the soft starter performs a restart attempt. This operation is repeated up to a maximum

number of attempts specified in P03.07. 

     –    With the property 'retentive' disabled (OFF):

          –   if the property 'automatic reset'= OFF, if the start input ST is closed, after a fixed delay of 30 seconds the alarm is reset and the soft starter performs a restart attempt. This operation is repeated for max 

5 attempts every 30 seconds, as long as ST input is closed and the alarm is active. If the alarm conditions are still present after 5 attempts, the alarm remains active (retenitive) and it is necessary to

manually reset it according to the reset mode set in P03.06. Note. This is the mode used for the alarms from A01 to A04 of soft starters type ADXNB (cannot be modified).

          –   if the property 'automatic reset' = ON, if the start input ST is closed, after the delay P03.08 the alarm is reset and the soft starter performs a restart attempt. This operation is repeated up to a maximum

number of attempts specified in P03.07.

  

On these alarms the property stop motor is always forced to ON, independetly by the setting, because the presence of these alarm conditions is critical for the run of the motor. 

Enabled

   

Retentive

Global 

alarm

        

Stop 

motor

          

Deceleration

        

Automatic 

reset

10.2  ALARMS DESCRIPTION

    CODE        DESCRIPTION                                                 REASON OF THE ALARM

     A01          NO POWER LINE                                             All three phases are not present when start command given or during the motor running.

     A02          PHASE LOSS                                                   One phase not present when start command given. Note. For the versions ADXNB and ADXNF the phase loss is detected only at the start command,

                                                                                             not during the ramps or in bypass (motor running at full voltage). 

     A03          WRONG PHASE SEQUENCE                            Phase sequence does not match the setting P03.01 (for basic version ADXNB: phase sequence different from L1-L2-L3, if enabled)

     A04          FREQUENCY OUT OF LIMITS                          Frequency of the line voltage outside of ±5% tolerance around 50Hz or 60Hz in the instant when start command is given.

     A05          VOLTAGE OUT OF LIMITS                               Line voltage L1-L2 lower than the threshold P03.02 for a time longer than P03.03, or line voltage higher than the threshold P03.04 for a time longer than 

                                                                                             P03.05

     A06          SOFT STARTER THERMAL PROTECTION        Soft starter heatsink temperature greater than maximum allowed value

     A07          TEMPERATURE SENSOR FAULT                     Integrated NTC temperature sensor interrupted or broken

     A08          BYPASS RELAY FAILURE                                Bypass relay contacts did not close or open

     A09          SYSTEM ERROR                                             Internal error. Please contact Lovato Electric Technical Support

     A10          MOTOR THERMAL OVERLOAD                       Motor thermal overload protection tripped. See the parameters P03.09-P03.10-P03.11-P03.12.

                     PROTECTION

     A11          OVERCURRENT PROTECTION                         Current >600%Ie (Ie=rated soft starter current) for a time longer than 200msec during starting. Note: This alarm cannot be disabled

     A12          LOCKED ROTOR                                              Current >500%In (In=rated motor current) for a time longer than 200msec during bypass

     A13          LOAD TOO LOW                                              Motor load torque lower than the one set in P03.13 for a time longer than P03.14 during bypass

     A14          CURRENT ASIMMETRY                                   Current asymmetry greater than the threshold P03.18 for a time longer than P03.19 during the motor run

     A15          STARTING TIME TOO LONG                            Starting time (from the start command to the bypass closure) longer than the setting P03.17

     A16          PHASE SHORTED                                            SCR in short circuit or bypass contacts welded

G

B

Summary of Contents for ADXN Series

Page 1: ...nagement of the starting and stopping ramps 4 5 2 Management of starting ramps with current limit only for ADXNP 5 6 Functional diagram 5 7 Protections 6 7 1 Enabling the phase sequence control ADXNB...

Page 2: ...Fi CX02 for programming data download and diagnostic from a PC or App The following table shows the main differences between the functions of the three versions 2 GENERAL CHARACTERISTICS 2 phase cont...

Page 3: ...tatus LEDs Relay outputs 2 x 1NO 3 potentiometers for basic settings starting voltage 30 80 Ue acceleration ramp 1 20s deceleration ramp 0 20s Auxiliary supply voltage A1 A2 and start input ST Status...

Page 4: ...For instance setting a deceleration ramp time of 10 seconds and an end of deceleration step of 20 the actual deceleration time will be 10 seconds minus the contribution of the end of deceleration step...

Page 5: ...en setting this parameter If this situation occurs it will trip the protection for starting time too long or the motor thermal overload protection 6 FUNCTIONAL DIAGRAM Here below it is represented the...

Page 6: ...abled with parameter P03 09 ON trips when the motor thermal status overcomes the limit of the set thermal overload class with consequent trip of the alarm A10 Motor thermal overload protection The tri...

Page 7: ...e against the ADXN front panel it is possible to read or write the parameters Conditions for the operation The smart device must be provided with NFC connectivity which must be activated and the smart...

Page 8: ...ew seconds will be heard a beep 6 At the device recognition the Home Page of the LOVATO NFC App shows the information about the detected device 7 Press the button to access to the ADXN parameters menu...

Page 9: ...hic widgets view live charts to monitor the trends of the electric measures in real time With the Wi Fi device CX02 it is also possible to connect the soft starter ADXNP to the LOVATO SAM1 App freely...

Page 10: ...d V OFF OFF 170 760 P03 03 Minimum voltage trip delay s 5 0 600 P03 04 Maximum voltage threshold V OFF 170 760 OFF P03 05 Maximum voltage trip delay s 5 0 600 P03 06 Alarm reset mode STOP STOP START P...

Page 11: ...against pumps dry running or to detect failure of transmission chains or belts When the torque is lower than this setting after the delay set in P03 14 the alarm A13 Load too low is generated The trip...

Page 12: ...that the current limitation remains active for a time too long a symptom of a mechanical problem A starting time longer than this setting cause the alarm A15 Starting time too long P03 18 P03 19 Contr...

Page 13: ...start input ST is closed after the delay P03 08 the alarm is reset and the soft starter performs a restart attempt This operation is repeated up to a maximum number of attempts specified in P03 07 Wit...

Page 14: ...ont for the connection of the optional RS485 communication module code CX04 compatible with both type ADXNP auxiliary supply voltage 100 240VAC and ADXNP 24 auxiliary supply voltage 24VAC DC With this...

Page 15: ...imum instantaneous current 10 Unsigned long F94h 2 Status Unsigned integer FB0h 2 Motor thermal status Unsigned long FB2h 2 Thyristors temperature C 10 Signed long 2100h 1 ST start input status bool U...

Page 16: ...e capacitors connection can be controlled with a relay output of the soft starter programmed with function TOR Top Of Ramp Do not perform high potential dielectric test on the soft starter In case of...

Page 17: ...6 26 149 5 87 128 4 5 05 45 1 77 35 1 38 2 3 0 09 6 7 0 26 ADXN 025 ADXN 045 31 1 22 23 7 0 93 CX04 45 1 77 35 1 38 2 3 0 09 139 5 47 129 5 08 113 4 4 46 6 7 0 26 ADXNP006 ADXNP018 with CX04 RS485 com...

Page 18: ...elation 1HP kW 1 36 19 CHOOSING THE SOFT STARTER Number of starts hour WITHOUT FAN In 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 3A ADXN006 6A ADXN006 ADXN012 9A ADXN012 ADXN018 12A A...

Page 19: ...OORDINATION WITH THERMAL OVERLOAD RELAY ADXNB AND ADXNF The soft starter type ADXNB and ADXNF don t integrated the function of motor thermal overload protection which is present instead in the advance...

Page 20: ...he drillings Soft starter Motor protection MPCB thermal trip Maximum voltage circuit breaker MPCB adjustment range VAC ADXN 006 SM1R0650 4 6 5 600 ADXN 012 SM1R1400 9 14 600 ADXN 018 SM1R1800 13 18 60...

Page 21: ...C 15 10 Rated frequency 50 60Hz 5 Drawn dissipated power ADXN 100VAC 45mA 1 70W 6 18A 240VAC 27mA 2 40W w o fan 24VAC 135mA 1 85W 24VDC 75mA 1 80W ADXN 100VAC 55mA 2 55W 25 30A 240VAC 33mA 3 20W w o f...

Reviews: